Moore Inductries Smart HART HTZ User manual

HTZ
HTZ
Smart HART®Humidity
and Temperature Transmitter
Smart HART®Humidity
and Temperature Transmitter
May 2016
238-722-00F
All product names are registered trademarks of their respective companies.

Table of Contents
Introduction ............................................................................................................................................. 4
About This Manual ........................................................................................................... 4
Model and Serial Numbers............................................................................................... 4
Inputs ............................................................................................................................... 4
Outputs............................................................................................................................. 4
Specifications ................................................................................................. 5
HDM Dimensions ............................................................................................................. 6
HSM Dimensions ............................................................................................................. 7
Configuring the HTZ....................................................................................... 8
Installing the Configuration Software ............................................................................... 8
Connecting the HTZ to the PC......................................................................................... 9
Connecting the HTZ to the HART Communicator............................................................ 9
PC Configuration Software Summary ........................................................ 11
Menu and Tool Bar Legend ............................................................................................ 12
Configuration Screens................................................................................. 12
Input ............................................................................................................................... 12
Trimming......................................................................................................................... 13
Display ........................................................................................................................... 14
Analog Outputs (-AO1 and -AO2) .................................................................................. 15

Using the HART Communicator.................................................................. 17
Programming when a Device Description is Available ................................................... 17
The HART Communicator Menu With a Device Description .......................................... 19
The HART Communicator Menu Without a Device Description ..................................... 22
HART Status Information............................................................................. 24
Installation..................................................................................................... 28
Mounting ........................................................................................................................ 28
Making the Electrical Connections................................................................................. 28
Recommended Gound Wiring Practices ........................................................................ 28
Additional Grounding Information................................................................................... 28
Operation....................................................................................................... 28
Maintenance................................................................................................................... 28
Calibration ...................................................................................................................... 29
Replacing RH Sensor................................................................................... 29
Customer Support........................................................................................ 29

4 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Introduction
This is the user’s manual for Moore Industries’ HTZ
Smart HART Humidity and Temperature Transmitter.
The HTZ is a loop-powered, HART enabled,
transmitter that measures temperature and relative
humidity and calculates dew point. The HTZ consists
of two specialized components. The Humidity/
Temperature Sensor Module (HSM) has temperature
and humidity probes which can easily be removed
from the housing for replacement or service. The
second component, the Humidity/Temperature Display
Module (HDM), can remain connected to output wiring
when the sensor assembly (HSM) is removed thus
maintaining the output current loops.
The HTZ comes with optional factory trimming
(VTB) that offers higher temperature measurement
accuracy. It is applied to the sensor module (HSM)
and is independent of the display module (HDM).
For ease of viewing, the HSM and HDM may be
placed apart from each other using a dedicated 10ft
(3m) (standard), 20ft (6m) or 30ft (9m) (optional)
cable utilizing quick disconnect connectors at both
ends.
About this Manual
Wherever you see a “Note”, “Caution” or “WARNING”
pay particular attention.
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that
could damage or destroy the unit.
Note - Information that is helpful for a procedure,
condition, or operation of the unit.
Model and Serial Numbers
Moore Industries uses a system of model and serial
numbers to keep track of all of the information on
every unit it sells and services. The HSM and the
HDM each have a different, unique serial number.
If a problem occurs with your HTZ, check for a tag
listing these numbers affixed to the suspect module.
Supply the Customer Support representative with this
information when calling.
Inputs
The HTZ includes a pre-calibrated relative humidity
sensor and a fixed Pt3850 1000 ohm RTD
temperature sensor. The temperature sensor’s ohms
measurement is linearized to temperature.
Outputs
Analog Outputs
The HTZ is equipped with two analog outputs (-AO1
and -AO2). Both -AO1 and -AO2 are externally
powered (sink only) by 12-42Vdc and output a
4-20mA range with their outputs isolated from each
other.
Both are configurable to output current proportional to
any of the three available input variables (temperature,
relative humidity and dew point).
-AO1
This output powers the HTZ. It provides primary loop
power for the unit. It may be used without -AO2.
HART communications may only be utilized using
-AO1.
-AO2
This output requires its own separate loop power. It
may not be used if -AO1 is not in use.
There is no HART communication capability at this
output.

The Interface Solution Experts 5
HTZ
Smart HART® Humidity
and Temperature Transmitter
Specifications
Performance Performance
(continued)
Performance
(continued)
Ambient
Conditions
Adjustments
Weight
Indicators
Humidity Input
Measurement Range:
0-100% RH
Calibrated Accuracy*:
±0.75% RH between
33-75% RH; ±1% below
33% RH and above 75%
RH (with -VTRH calibration
option); Nominal accuracy
without -VTRH calibration is
±1.8% between 20-80% RH
Ambient Temperature
Effect: 0.005%/°C
Long Term Stability: ±1%
RH/year
Response Time: 10
seconds to 90% of final
value on a step input
change @25°C, 1m/s air
Temperature Input
Measurement Range:
-40°C to +110°C
(-40°F to +230°F)
Calibrated Accuracy*:
±0.036°C at trim points (with
-VTB calibration option);
Nominal Accuracy without
-VTB calibration is ±0.1°C
Ambient Temperature
Effect: 0.003°C/°C
Long Term Stability:
1 year: 0.1°C
3 years: 0.17°C
5 years: 0.24°C
Response Time: 200msec
maximum for the output to
change from 10% to 90%
of its scale for an input step
change of 0%
to 100%
Dewpoint
Range: -45°C to +100°C
(-49°F to +212°F)
(calculated from
temperature and RH inputs)
Accuracy*: Typical @25°C,
±0.5°C between 40-95%
RH; ±1-2°C between
10-40% RH
EW = 10^ (0.66077 + (7.5 * T / (237.3 + T) ) )
EW_RH = EW * RH / 100
Dew Point (Dp)= ( (0.66077 – log10 (EW_RH) ) * 237.3) / (log10 (EW_RH) – 8.16077)
This is the saturation vapor pressure over water
Multiply EW with RH
Equation 1. Dew Point Calulation
* High accuracy relative humidity measurements are achieved within a RH range of 33-75% using the trimming feature of Moore Industries’ Intelligent PC
Configuration Software with the RH sensor calibrated against a controlled RH environment (See the -VTRH option under “Sensor Length/Calibration” in Ordering
Information). High accuracy temperature measurements are achieved using the trimming feature of the Intelligent PC Configuration Software with the temperature
sensor immersed in a temperature calibration bath (Sensor-to-Transmitter matching factory calibration; See the -VTB option under “Sensor Length/Calibration”
in Ordering Information). High accuracy dew point measurements are achieved using the trimming feature of the Intelligent PC Configuration Software at 25°C,
between 40-90% RH. Stated accuracies do not include ambient temperature effects. .
Ambient Temperature
Effect: 0.005°C/°C
Long Term Stability:
± 0.5°C RMS over 1 year
Response Time:
10 seconds to 90% of final
value
Dew Point Calculation:
EW * RH / 100 (refer to
Equation 1 for explanation)
Analog Output
Output Range: 4-20mA
Linear Region:
3.8-21.4mA
Hardware Limits:
3.6-23.6mA
Accuracy: ±2 microamps
Ambient Temperature
Effect: 0.009% of span
(16mA)/°C
Long-Term Stability:
1 year: 0.012%
3 years: 0.020%
5 years: 0.026%
Rise Time: 100msec
maximum for the output to
change from 10% to 90% of
its scale for a step change of
the sourcing variable of 0%
to 100%
Damping: User-set between
0-30 seconds
Power Supply
Requirements: 12-42Vdc at
output terminals
Power Supply Effect:
±0.002 of span per 1V
change
Load Effect: Negligible
within specified power limits
Load Capability:
(500 ohms@24V)
Supply Voltage - 12V
0.024A
Ripple: 10mVpp,
frequencies up to 120Hz,
measured across a 250 ohm
load resistor
Start up Time: <5sec
(trimming disabled)
Isolation: 500Vac between
each output and between
outputs and case
Overall Accuracy: Sum of
input and output accuracy,
ambient temperature effect
and long term stability
Analog Output Response
Time: 500msec from step
input until the analog output
reaches 90% of its final value
Operating Range:
-40°C to +85°C
(-40°F to +185°F)
HDM Storage Range:
-40°C to +85°C
(-40°F to +185°F)
HSM Storage Range:
Recommended 10-50°C (50-
122°F), 20-60%RH; Maximum
0-80°C (32-176°F), 0-95%RH
Humidity Sensor
Temperature Limits: -40°C
to +110°C (-40°F to +230°F)
Humidity Sensor Maximum
Pressure: 125psia
Relative Humidity:
0-95% relative humidity,
non-condensing
RFI/EMI Protection:
20V/m@80-1000MHz, 1kHz
AM, when tested to IEC61326,
1998
All adjustments made using
Moore Industries’ Intelligent
PC Configuration Software or
HART-enabled hand-held
or host
LCD: 2x5 14-segment
characters, alphanumeric
readout accurate to the
nearest digit.
Range: -99999 to 99999;
Decimal point can be
user-set
HDM: 918g (32.4 oz)
HSM: 601g (21.2 oz)
Cable: 3m, 250g (8.8 oz);
6m, 454g (1.0 lbs);
9m, 658g (1.45 lbs)

6 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Figure 1. HDM Dimensions
1.17 in
(29.7mm)
4.66 in
(118.5mm)
0.51 in
(12.8mm)
5.08 in
(128.9mm)
5.59 in
(141.9mm)
6.20 in
(157.5mm)
2.70 in
(68.6mm)
3.42 in
(86.9mm)
1.34 in
(34.0mm)

The Interface Solution Experts 7
HTZ
Smart HART® Humidity
and Temperature Transmitter
Figure 2. HSM Dimensions
P Bracket OptionZ Plate Option
82.3mm
(3.24 in)
110.2mm
(4.34 in)
120.4mm
(4.74 in)
68.6mm
(2.70 in)
88 9mm
187.4mm
(7.38 in)
149.1mm
(5.87 in)
87.1mm
(3.43 in)
ZPl t
<< FLOW DIRECTION >>
Back Plate
47.6mm
(1.88 in)
95.3mm
(3.75 in)
105.1mm
(14.14 in)
95.3mm
(3.75 in)
41.3mm
(1.63 in)
Ø50.8mm
(2.00 in)
Ø6.4mm
(0.25 in)
4 Places
Ø38.1mm
(1.50 in)
12” Probe
311.4mm (12.26 in)
18”Probe
463.8mm (18.26 in)
Probe
e HumidityRelativ
82.3mm
(3.24 in)
87.1mm
(3.43 in)
12”Probe
299.2mm
(11.78 in)
18”Probe
451.6mm (17.78 in)
T
emper
ature
Probe
6”Probe
159mm(6.26 in)
6”Probe
146.8mm
(5.78 in)

8 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Connecting the HTZ to the PC
Connect the RS-232 end of the cable to the PC’s
COM port.
Refer to Table 1 for information on the necessary
equipment.
Connecting the HTZ to the HART
Communicator
Connect the HART modem cable into the loop as
shown in Figure 3.
Once the Configuration Program is installed onto
your PC, the HTZ can be connected to equipment
to simulate input and monitor output. You can then
change the operating parameters of your unit.
No Transmitter Needed
It is not necessary to connect the transmitter to a PC
to create configuration files using the software. The
Configuration Program can be run without connecting
a transmitter, and most parameters can be set
without benefit of input from a HTZ.
This makes it easy to create a set of operating
parameters, save and download them to one or more
transmitters at a later time.
The HTZ must be connected to the PC in order
to: trim input, trim output, assign a tag, perform an
output test, receive (via download) a configuration file
and save the configuration file from the transmitter’s
memory.
Installing the Configuration Software
Refer to Table 1 for the equipment needed.
1. Insert the Moore Industries Interface Solution
Configuration Tools CD into the CD drive of
the PC. Access the CD and open the following
folders: Configuration Software and Tools/HTZ
Configuration Tools/HTZ PC Configuration
Software.
2. Double-click the installation program located
in the folder. Follow the prompts to correctly
install the program.
Configuring the HTZ
One of the benefits of the HTZ is that there are no
internal or external controls to adjust or settings to
change. All operating parameters are set using Moore
Industries’ Intelligent PC Configuration software or
a HART configurator if using HART communication
capabilities (-AO1 only).
Once these software settings are made, they are
downloaded to the instrument in the form of a Con-
figuration File and stored in the unit’s nonvolatile
memory. You can choose to save a backup copy of
the file on your PC hard drive or external media. The
HTZ communicates with the PC through a proprietary
communications cable via the PC’s serial (COM) port
or using a HART modem cable if HART communica-
tions are used.
Table 1. Necessary Equipment to Configure the HTZ
Power Supply
Precision Load Resistor
Multimeter (optional)
Personal Computer
(Required only if using a PC for setup)
Moore Industries Interface Cable
HART Modem Cable
(Required only if using HART
Communication capabilities)
Moore Industries PC Configuration Software
(Required only if using a PC)
HART Communicator
(Required only if NOT using a PC)
24Vdc, ±10% (One for each analog output (-AO)
250 ohms, ±0.01% HART specifies that total loop resistance is to be maintained between
250 ohms and 1100 ohms (one for each analog output)
Accurate to ±0.025% of span; e.g., Fluke Model 87
80386-based(or faster) IBM PC, or 100% compatible;
CD Drive; 4Mb free RAM; 8Mb recommended; 20Mb free disk space on hard drive
(More RAM & hard disk space is required for Windows 2000, XP, Vista, or 7);
Microsoft Windows®2000, XP, Vista, or 7; 1 (one) serial port (COM 1, 2, 3 or 4)
set to 9600 baud, no parity, 8 data bits and 1 stop bit
Part Numbers: 803-040-26 (RS232) or Optional USB Cable Part# 208-236-00
Part Number: 803-048-26, or equivalent
Version 1.0 or greater, successfully installed to the hard drive
Fisher-Rosemount Model 275 or equivalent (with HTZ Device Description loaded)
Device Specifications

The Interface Solution Experts 9
HTZ
Smart HART® Humidity
and Temperature Transmitter
Figure 3. HTZ Hook-Up Diagram with AO1 Configured for HART Communications and AO2 Utilized
+
–
12-24Vdc
Power
Supply
THE HART Communicator
or the PC can be connected
at any point on the output
side of the loop. Total loop
resistance must equal between
250 and 1100 ohms for proper
HARTcommunications.
Current Meter
Load=250 ohms
+
–
PC
To serial
(COM) port
of PC
OR
HART Modem
connects to
serial (COM)
port of PC
+
–
12-24Vdc
Power
Supply
COM
HSM Connection
250 ohms
Voltmeter
+
–
To USB
(COM)
Port of PC
OR

10 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
PC
To serial
(COM) port
of PC
+
–
12-24Vdc
Power
Supply
12-24Vdc
Power
Supply
+
–
HSM Connection
250 ohms
250 ohms
Voltmeter
+–
Voltmeter
+
–
COM
To USB
(COM)
Port of PC
OR
Figure 4. HTZ Hook-Up Diagram with AO1 and AO2 Powered

The Interface Solution Experts 11
HTZ
Smart HART® Humidity
and Temperature Transmitter
maximum). Use the Address box to change the unit’s
address (0-15).
To utilize a longer Tag identifier (up to 32 characters,
maximum) you may access the Long Tag feature
located in the View dropdown menu. Enter the
desired information and click Set. To view the Long
Tag, click Read.
Identification parameters are stored in the HDM.
6. HTZ Device Info– This read-only display indicates
serial numbers, firmware versions and hardware
versions of both the HSM and HDM. This information
is also displayed in the Device Information section of
the View drop down menu.
7. Communications– Notifies user of current PC
connection/communications status. The address
displayed in the Address box must match the address
of the unit if HART Communications are being used
(Analog Output 1 only).
8. Input/Trimming/Display/Analog Outputs 1 and
2–These tabs change the right side of the screen
to allow you to set the appropriate part of the HTZ’s
configuration. See corresponding sections of this
manual for additional information regarding these tabs.
Figure 5. HTZ PC Configuration Software Screen
Once the default configuration has been saved, it is
safe to program other parameters. The PC Software
is made up of these sections:
1. Menu Bar/Tool Bar– Dropdown menus and
corresponding icons allow you to perform various
functions throughout the PC Configuration Program.
Refer to the Menu and Tool Bar Legend for a
complete description.
2. Program Status– This portion of the program
displays the activity of the connected unit. It will
display such messages as: Idle, Monitoring, Uploading
and Downloading.
3. HTZ Status– Indicates if there are problems or
faults with the instrument.
4. Process Variable– Displays the present Process
Variable readings. Available Process Variables
include Temperature (Temperature Probe), Relative
Humidity and Dew Point.
5. Identification Parameters– Use this parameter to
place an identifying Ta g (8 alphanumeric characters,
maximum), Descriptor (16 alphanumeric characters,
maximum) or Message (32 alphanumeric characters,
PC Configuration Software Summary

12 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Configuration Screens
Note:
Unless otherwise noted, ensure that the PC
Program is idle before making any selections
or configuration changes to the parameters and
windows of the program. Also, when attempting to
download or upload, monitoring must be stopped.
To do this, click “Stop” in the Monitoring dropdown
menu, or click the “Stop Monitoring” icon.
Input
HSM Settings– Allows for setting HSM parameters.
Temperature– Selects the unit in which temperature
is displayed. This affects the Sensor Range limits as
well as Dew Point ranges on the page.
Filter– This setting is used to configure the input filter.
This filter is designed to reduce the effects of mains-
induced noise. The input filter frequency value should
be set to the frequency of the local AC supply– either
50Hz or 60Hz.
Relative Humidity Range– Permits you to set the
lower and upper limits of your allowed relative humid-
ity range.
Enter your desired values in the Lower and Upper
Range text boxes.
Sensor Range– Allows you to set your upper and
lower range values within the unit chosen in the Tem-
perature section.
Figure 6. Input Tab
Allows such functions as New,
Open, Save and Print functions
Allows you to Upload and
Download configurations and
perform an Address Search
Allows selection of PC COM
ports as well as Communication
Method (Auto, RS232 or HART)
Allows you to Monitor and
Stop monitoring processes
Controls whether Tool and
Status Bars are viewed on the
screen as well as Additional
Status Information, Long Tag
and Device Information
Displays the version of the
PC Configuration Program
Allows you to enable Burst Mode
Menu and Tool Bar Legend

The Interface Solution Experts 13
HTZ
Smart HART® Humidity
and Temperature Transmitter
Enter your desired values in the Lower and Upper
Range text boxes.
Dew Point Range– Permits you to set the lower and
upper limits of your allowed dew point range.
Enter your desired values in the Lower and Upper
Range text boxes.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
drop down menu located in the Status Bar. Or, click
the button in the Tool Bar.
Trimming
Trimming– Trimming increases the measurement
accuracy of your instrument by matching the reading
of its actual input, to either a calibrated source or the
device to which it is connected. This verifies that the
input to the transmitter is being interpreted correctly.
You may trim any point between 0% and 100% along
the scale. Note that 1 Point trimming applies an offset
to the sensor reading, while 2 Point trimming applies
both an offset and a gain.
By default all three variable options are disabled. To
perform trimming each variable must be enabled
(individually). In order to enable each variable, user
must place a check mark in front of the variable that
requires trimming (See Figure 7.). This can be done
using the Trimming Menu on the Menu/Tool Bar (Refer
to Figure 6. for Trimming Menu location).
Figure 7. Trimming Tab
Figure 8. Trimming Enable/Disable Menu
Temperature Trimming– By default this option is
disabled. Once enabled, take the following steps to set
trim variable (temperature probe) to desired values.
1. Select either 1 Point (one-point trimming) or
2 Points (two-point trimming) by clicking the
appropriate button. Each pair consists of Set
Value and Tr i m Value fields. The following
prompt will appear:
Warning:
-Please confirm you wish to do this. Changing
the trimming mode will reset the trimming
values.
Hit “YES” button to continue or “NO” button to
abort.
2. Enter the values that require trimming into the
Set Value field.
3. Apply the targeted signal to the input, wait
until it settles, and click Tr i m to capture the
measured value.
4. If you chose 2 Points, repeat the steps above
for the second point.
Relative Humidity Trimming– By default this option
is disabled. Once enabled, take the following steps to
set trim variable to desired values.
1. Select either 1 Point (one-point trimming) or
2 Points (two-point trimming) by clicking the
appropriate button. Each pair consists of Set
Value and Tr i m Value fields. The following
prompt will appear:
Warning:
Please confirm you wish to do this. Changing
the trimming mode will reset the trimming
values. Changing the Relative Humidity will
affect the Dew Point.
Hit “YES” button to continue or “NO” button to
abort.
2. Enter the values that require trimming into the
Set Value field.

14 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
3. Apply the targeted signal to the input, wait
until it settles, and click Tr i m to capture the
measured value.
4. If you chose 2 Points, repeat the steps above
for the second point.
Note:
The Relative Humidity probe has a monolithic
chip which produces a Relative Humidity and
a temperature measurement. These two
measurements are used to calculate the Dew Point.
The temperature probe reading is not used in the
Dew Point Calculation.
Dew Point Trimming– By default this option is
disabled. Once enabled, take the following steps to set
trim variables to desired values.
1. Select either 1 Point (one-point trimming) or
2 Points (two-point trimming) by clicking the
appropriate button. Each pair consists of Set
Value and Tr i m Value fields. The following
prompt will appear:
Warning:
Please confirm you wish to do this. Changing
the trimming mode will reset the trimming
values. Changing the Relative Humidity will
affect the Dew Point. It is recommended to
trim the Relative Humidity before trimming the
Dew Point.
Hit “YES” button to continue or “No” button to
abort.
2. Enter the values that require trimming into the
Set Value field.
3. Apply the targeted signal to the input, wait
until it settles, and click Tr i m to capture the
measured value.
4. If you chose 2 Points, repeat the steps above
for the second point.
Trimming data resides in the HSM allowing for factory
service or user-trimming which is independent from
the installed display assembly.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
dropdown menu located in the Status Bar. Or, click
the button in the Tool Bar.
Figure 9. Display Tab
Display
Display Source– From here you may select which
variable is viewed on your instrument’s display (HDM)
by clicking the desired variable.
By selecting the Scroll option, your display will toggle
through each of the variables every four seconds
displaying each setting.
Use Custom Label– (Applicable only to Temperature
display)
Allows you to assign a specific label (alphanumeric, 5
characters max.), or EGU (Engineering Unit).
1. Check the Use custom label box.
2. Enter the value you wish viewed into the
Custom Label text box.
Precision– Select the number of decimal places/
resolution of your display. Allowed settings are Auto,
0, 1, 2 or 3 decimal places.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
drop down menu located in the Status Bar. Or, click
the button in the Tool Bar.

The Interface Solution Experts 15
HTZ
Smart HART® Humidity
and Temperature Transmitter
Fail Mode– In the case of an input failure, you have
the ability to set a mode you choose to alert of the
failure.
High– Choosing this option will send the output
to a High fail mode (user-selectable
between 20.0mA to 23.6mA).
Low– Choosing this option will send the output
to a Low fail mode (user-selectable
between 3.6mA to 4.0mA).
Hold Last– This will display the last value present
before the failure.
The Sensor Error Value box displays your selected
value.
Damping– Output Damping allows you to introduce a
delay (0-30sec) into the response of your unit in order
to stop short-lived spikes from setting off alarms.
1. Select Enabled if you choose to use Damping.
2. Enter your damping time into the associated
text box.
Output Current – Displays the value present at your
output when the PC Configuration Software is in
Monitor mode.
Trimming– Output Trimming increases the accuracy
of your instrument by calibrating its analog output to
the device that is receiving the output. This ensures
that the instrument is being correctly interpreted.
1. Click the Lower button to trim the Lower Output
Range.
2. To “fine tune” trimmed values, place the value
read on the external multimeter, connected to
your instrument for trimming, in the Measured
Loop Current text box and click Tr i m .
3. Click the Upper button and repeat Step 2 to
trim the Upper Output Range.
4. Once you have performed your output
trimming, click Unfix.
Note:
Do not click the Reset button in the Trimming menu
unless you want to disregard your trimmed values
and return to the manufacturer’s trim values.
Analog Output
Steps discussed in this section apply to both the
Analog Output 1 and Analog Output 2 tabs of the HTZ
PC Configuration Software.
Source– This user-configurable parameter defines
the variable that the analog output will monitor. By
default, AO1 monitors the humidity value; AO2
monitors temperature.
Source Range– These values reflect the Lower
Range and Upper Range values as displayed in the
Sensor Range section of the Input tab.
Output Range– Sets the analog output range limits.
Default value is 4-20mA.
1. Enter your low and high limit values into the
text boxes.
2. In the Under Range Min. Value box, enter the
lowest value your output can reach (typically
between the Fail Low and the Zero % output
value). The allowed limits are 3.6mA to 4.0mA.
Default is 3.8mA.
3. In the Over Range Max. Value box, enter the
highest value your output can reach (typically
between the Fail High and the 100% output
value). The allowed limits are 20.0mA to
23.6mA. Default is 21.8mA.
Figure 10. Analog Output (-AO) Tab

16 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Output Test– This test may be performed in order to
check output performance and accuracy and to trim
other instruments in your setup. Your output will be a
current value, in mA, equal to the value you enter into
the text box. You can check the other devices on the
system and calibrate them to this signal.
This feature is independent of the input. If you find
that the output requires adjustment, you may perform
the Trimming function.
1. Ensure that HTZ monitoring is stopped. In the
Fix current text box, enter a value between 3.6-
23.6mA and click the Fix button.
2. Return to monitoring the HTZ. You will see the
“fixed” value in the Output Current display and
on the external multimeter.
3. Once you have finished, click Unfix.
Note:
Once you have configured all parameters, download
to the unit by selecting Download in the Transfer
dropdown menu located in the Status Bar. Or, click
the button in the Tool Bar.

The Interface Solution Experts 17
HTZ
Smart HART® Humidity
and Temperature Transmitter
Using the HART
Communicator
The HTZ can be programmed using a HART
Communicator. If your communicator is equipped
with the Device Description (DD) for your
transmitter, The HART Communicator Menu with a
Device Description section gives an overview of the
menus and instructions for programming.
The HTZ DDs are available on the HART
Foundation’s Device Driver Library Release
December 2007 and later. To determine if
your communicator has the appropriate Device
Description, follow the manufacturer’s instructions.
A list of companies will appear which, if you have
the appropriate Device Description, will include
Moore Industries HTZ.
If your communicator is not equipped with the
required Device Description, go to The HART
Communicator Menu without a Device Description
section of this manual. Some capabilities can only
be accessed if your communicator is equipped with
the proper Device Description.
If you are using a Fisher-Rosemount Model 375
HART Communicator, you may download the latest
Moore Industries DD at www.miinet.com.
If you are using a Fisher-Rosemount Model 275
HART Communicator and require the latest version
of the DD, you must either send the Communicator
to Moore Industries or the HART Foundation. To
send the instrument to Moore Industries contact
our Customer Service department for a Returned
Material Authorization (RMA).
Include Moore Industries’ configuration sheet
indicating the Device Descriptions that you require.
We will load the Device Descriptions of your choice
for a nominal charge.
For installation of the latest device description through
the HART Foundation, send the
Communicator to the address below:
HART Communication Foundation
9390 Research Blvd., Suite I-350
Austin, TX 78759-6540
USA
Phone: (512) 794-0369
Fax: (512) 794-3904
www.hartcomm.org
Ensure that you contact the HART Foundation
to determine their requirements in sending the
instrument to their facility.
Programming When a Device
Description is Available
With the transmitter connected as illustrated in
Figure 3 apply power and turn on the communicator.
After a brief self-test, the communicator will show the
main menu and identify the unit as an HTZ.
This section contains the instructions for programming
the transmitter using a HART Communicator that
has been programmed with a HART Device
Description. If your communicator does not have the
appropriate Device Description, skip to The HART
Communicator Menu without a Device Description
section of this manual.
Figure 11 shows an overview of the programming
menus for the configuration process.

18 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Figure 11. HTZ HART Communicator Configuration Menu Summary
Online Menu
1 Model
2 Device Setup
3PV
4 PV LRV
4 PV URV
6 AO1
7 AO2
1 Process Variable
2 Setup
3Diagnostic &
Services
4 Review
1 PV
2 SV
3TV
4 AO1
5 AO2
Setup
1 Configure
Inputs
2 Configure
Output
3Configure
Dev Info
4 Configure
Display
Configure Inputs
Sensor Information
1 PV LSL
2 PV USL
3PV Min Span
4 SV LSL
5 SV USL
6 SV Min Span
7 TV LSL
8TV USL
9TV Min Span
Configure Output
1 Analog output
2 HART output
HART Output
1 Poll addr
2 Burst mode
3Burst option
Configure Dev Info
1 Tag
2 Descriptor
3Message
4 Date
5 Final asmbly num
6 Device id
7 Hardware rev
8HSM Device ID
9HSM HW Rev.
10 HSM FW Rev.
Configure Display
1 Mode
2 Decimal Places
3Custom Label
4 Label Displayed
Diagnostic &
Services
Review
1 Device
Parameters
2 Device
Information
PV Trimming
1 Trim Mode
AO1 Loop Test
1 4mA
2 20mA
3Other
4 End
Device Parameters
Model
Measure Mode
PV Input Type
PV Snsr S/N
Filter
PV LRV
PV URV
PV LSL
PV USL
PV Min Span
SV LRV
SV URV
SV LSL
SV USL
SV Min Span
TV LRV
TV URV
TV LSL
TV USL
TV Min Span
AO1 URV
AO1 ORV
AO1 Fail Mode
Fail AO1
AO2 URV
AO2 ORV
Fail Mode
Fail AO2
Device Information
Tag
Descriptor
Message
Date
Dev id
Universal rev
Fld dev rev
Software rev
Hardware rev
Physicl signl code
Poll addr
Burst mode
Num reqpreams
HSM Device ID
HSM FW Rev.
HSM HW Rev.
Key
Process Variable
1 Filter
2 EGU Selection
3PV LRV
4 PV URV
5 SV LRV
6 SV URV
7 TV LRV
8TV URV
9PV Snsr S/N
10 Sensor Information
1 Test device
2 PV Trimming
3SV Trimming
4 TV Trimming
5 AO1 Loop Test
6 AO2 Loop Test
PV = Primary Variable (Temperature)
SV = Secondary Variable (Relative Humidity)
TV = Third Variable (Dew Point)
AO1 = Analog Output 1
AO2 = Analog Output 2
# PREAMBLES= Number of Preamble
Characters
AO = Output Current
AO ORV = Analog Output
Over Range Value
AO URV = Analog Output
Under Range Value
DAMP = Damping Value
DEV ID = Device Identification
DIAG = Diagnostic
LRV = Lower Range Value
MAX VALUE = Maximum Process Value
MIN VALUE = Minimum Process Value
OFFS= Offset
POLL ADDR = Polling Address
URV = Upper Range Value
1
23
4
A
B
C
5
6
Device Setup
AO1
1 AO1 Source
2 AO1 Zero
3AO1 Full
4 AO1 Damping Rate
5 AO1 URV
6 AO1 ORV
7 AO1 Fail Mode
8Fail AO1
9AO1 Trim
10 AO1 Trim Reset
Analog Output
1 AO1
2 AO2
AO2
1 AO2 Source
2 AO2 Zero
3AO2 Full
4 AO2 Damping Rate
5 AO2 URV
6 AO2 ORV
7 Fail Mode
8Fail AO2
9AO2 Trim
10 AO2 Trim Reset
AO2 Loop Test
1 4mA
2 20mA
3Other
4 End
D
Test device
1 Status
-AO1 Only
SV Trimming
1 Trim Mode
2 SV Trim
TV Trimming
1 Trim Mode
2 TV Trim

The Interface Solution Experts 19
HTZ
Smart HART® Humidity
and Temperature Transmitter
The HART Communicator Menu With a
Device Description
To program your HTZ, if your communicator is
equipped with the Device Description for your
instrument, follow the steps below. For all steps
outlined below, refer to Figure 11 for menu
parameters.
1. Online Menu– The Online menu displays the
present process value of your application, the PV
lower and upper range values and the actual output
current (-AO1 and -AO2). Use the Device Setup
menu to configure the HTZ.
2. Device Setup Menu– The Device Setup menu
allows you to access the following menus: Process
Variable, Setup, Diagnostic & Services and Review.
3. Process Variable Menu– The Process Variable
menu displays the present values of parameters
listed on the Communicator display which include the
Primary, Second and Third Variables (PV, SV and TV)
and analog outputs (AO1 and AO2).
4. Setup Menu– Scroll through the Setup menu
to access configuration menus for the following
parameters: Configure Inputs, Configure Output,
Configure Dev Info and Configure Display.
A. Configure Inputs
This menu allows access to input configuration.
1 Filter– This is used to configure the input filter
which helps reduce mains-induced noise. The value
selected should match the frequency of the local AC
supply (50Hz or 60Hz).
2 EGU Selection– Specify an EGU setting using this
parameter. This affects the PV and TV. The SV has a
constant EGU read in percentage (%).
3 PV LRV / 4 PV URV– Select your primary
process variables (Temperature) lower and upper
range values, respectively. Ranges are displayed in
temperature.
5 SV LRV / 6 SV URV– Select your primary process
variables (Relative Humidity) lower and upper
range values, respectively. Ranges are displayed in
percentage.
7 TV LRV / 8 TV URV– Select your primary process
variables (Dew Point) lower and upper range values,
respectively. Ranges are displayed in temperature.
9 PV Snsr S/N– Enter your Temperature sensor’s
serial number.
10 Sensor Information– Displays the Lower Sensor
Limit (LSL), Upper Sensor Limit (USL) and the
minimum span of PV, SV and TV of the HTZ.
B. Configure Output
This menu allows you to configure the analog outputs
(-AO1 and -AO2) as well as the HART output (-AO1
only).
Analog Output
These instructions apply to both -AO1 and -AO2
configuration. By default, AO1 monitors humidity;
AO2 monitors temperature. You may select to change
this.
1 AO1 Source– Select the variable that this output
will monitor.
2 AO1 Zero– Enter your zero range output value.
This value corresponds to the unit of measure (°C, °F
or Kelvin) as selected in the EGU selection section.
Default value is 4mA.
3 AO1 Full– Enter your upper range output value.
Allowed values range from 3.6mA to 23.6mA. This
value corresponds to the unit of measure (°C, °F or
Kelvin) as selected in the EGU selection section.
Default value is 20mA.
4 AO1 Damping Rate– Damping allows you to
introduce a delay into the response for your unit
in order to stop short-lived spikes from setting off
alarms. To utilized damping, select a value between
0-30sec.
5 AO1 URV– Select a value between 3.6mA and
4.0mA as your analog output under range value (AO1
URV). If the analog output drops below the set value,
a fault will be declared. Default value is 3.8mA.
6 AO1 ORV– Select a value between 20.0mA and
23.6mA as your analog output over range value (AO1
ORV). If the analog output exceeds the set value, a
fault will be declared. Default value is 21.8mA.
7 AO1 Fail Mode– In the case of an input failure, you
have the ability to set a mode you choose to alert of
the failure. Select from:
High– Choosing this option will send the output to
a High fail mode (user-selectable between 20.0mA to
23.6mA). If selecting High fail mode, enter your value
in the following step (Fail AO1).

20 The Interface Solution Experts
HTZ
Smart HART® Humidity
and Temperature Transmitter
Low– Choosing this option will send the output to
a Low fail mode (user-selectable between 3.6mA to
4.0mA). If selecting Low fail mode, enter your value
in the following step (Fail AO1).
Hold Last– Selecting this will display the last
value present before the failure occurred.
8 Fail AO1– Select your High or Low fail mode value.
Allowed values are 20.0mA to 23.6mA for High Fail
mode and 3.6mA to 4.0mA for Low Fail mode.
9 AO1 Trim– Output trimming increases the accuracy
of your instrument by calibrating its analog output to
the device that is receiving the output. This ensures
that the instrument is being correctly interpreted.
Connect a multimeter to your HTZ output to indicate
present output reading.
Setting fld device to Output Zero will be displayed on
your communicator. Select OK if ready to proceed.
When prompted, enter the value displayed on the
multimeter into your communicator. Press Enter. If
your output matches the value on the multimeter,
select Ye s .
Next, Setting fld dev to Out Full is displayed on
your communicator. Select OK if ready to proceed.
When prompted, enter the value displayed on the
multimeter into your communicators. Press Enter.
If your output matches the value on the multimeter,
select Ye s .
10 AO1 Trim Reset– Select this in order to use
manufacturer’s trim values.
Note:
Do not perform the Output Trim Reset function
unless you want to disregard your trim values and
return to the manufacturer’s values.
Repeat Steps 1 to 10 to configure -AO2, if required.
HART Output
Use this portion of the menu to configure the Poll
Address, Burst mode and Burst Option.
1 Poll addr– The HART polling address is
represented by a number between 0 and 15. This
identifies the transmitter on the loop. In a loop with
only one HART slave on it, this address should be
0. In a multidrop loop, any of these numbers can be
used.
Note:
If the polling address is set to 0, the transmitter is
automatically set to analog mode. Multiple units on
the same bus must have different addresses.
2 Burst mode– This function allows you to achieve a
higher data rate. When enabled (On), your instrument
repeatedly transmits a data message as if it were
being commanded to do so. The Master device
receives the data more frequently than if it were
only polling the transmitter, achieving a higher data
transfer rate.
3 Burst option– Once Burst Mode is enabled, choose
which value is transmitted–PV, % range/current or
Process vars/crnt (Process variables/current).
C. Configure Dev Info
This menu allows you to configure identification
parameters for your HTZ.
1 Tag– Place a unique label that corresponds to your
instruments location or specific usage (8 characters
maximum).
2 Descriptor– Place text that is used as a description
of how the instrument is being used (16 characters,
maximum).
3 Message– Place additional information that may
be helpful in describing the instrument or its use (32
characters, maximum).
4 Date– Store a date that corresponds to specific
system function, i.e. instrument configuration date,
calibration due date, preventive maintenance
schedule, etc.
5 Final asmbly num– You may enter a number that
is used for identification purposes, and is associated
with the field device (8 characters, maximum).
6 Dev id– This is a read-only value that uniquely
identifies the field device when combined with the
manufacturer identification and device type.
7 Hardware rev– This is a read-only value that
corresponds to the revision of the electronics
hardware of the field device.
8 HSM Device ID– Displays the device identification
of the connected Humidity/Temperature Sensor
Module (HSM).
Table of contents
Other Moore Inductries Transmitter manuals
Popular Transmitter manuals by other brands

Daystrom
Daystrom Heathkit IG-72 Assembly manual

Lightware
Lightware SW4-OPT-TX240RAK quick start guide

Siemens
Siemens SITRANS LR140 operating instructions

M-system
M-system 27TS instruction manual

Sentera Controls
Sentera Controls DSTHG-2 Mounting and operating instructions

Mindray
Mindray NetGuard Service manual

aci
aci B5C Installation, operation and maintenance manual

Sapcon
Sapcon CAPVEL-ICT instruction manual

Siemens
Siemens SITRANS TW Operator's manual

JAROLIFT
JAROLIFT TDRCT04W Original assembly and operating instructions

GREISINGER electronic
GREISINGER electronic GLMU 200 MP operating manual

Zamel
Zamel RNK-02 manual