
K3138V1 5/06 Rev. A 
 
ZR530
ZR530ZR530
ZR530 
 
 
PASSIVE INFRARED MOTION
PASSIVE INFRARED MOTIONPASSIVE INFRARED MOTION
PASSIVE INFRARED MOTION 
 
 DETECTOR/TRANSMITTER
DETECTOR/TRANSMITTERDETECTOR/TRANSMITTER
DETECTOR/TRANSMITTER 
 
 
INSTALLATION INSTRUCTIONS 
 
GENERAL INFORMATION 
The ZR530 Passive Infrared Motion 
Detector/Transmitter is a battery-operated wireless 
device. 
Designed for use in commercial and residential 
installations, the ZR530 is a wall-mounted unit with 
a standard lens that provides wide-angle 
protection up to a range of 12m. For best 
coverage, mount the detector so that the likely 
direction of intruder motion is across the pattern. 
This document provides installation instructions 
for the ZR530, but the installer must be familiar 
with the Installation Instructions for the FBII control 
panel with which the ZR530 is intended to be 
used. 
FEATURES 
•Wireless operation for fast installation. 
• Dual-element pyro-electric sensor provides 
positive protection while minimizing false 
alarms. 
• Alternate polarity pulse count option offers 
greater stability in adverse environments. 
• Provision to turn LED on while walk testing 
(LED is turned off after testing). 
• Tamper-protected cover – unit transmits 
message if cover is removed. 
• Wall or corner mounting options. 
• Optional Pet Alley and Long Range lenses 
available. 
SYSTEM DESCRIPTION 
Optical System 
Uses efficiently designed Fresnel lenses. 
Radio Transmitter 
The built-in transmitter serves only as the 
communication link to the alarm system's 
Receiver/Control, and can send alarm, tamper, 
supervisory, and battery status messages to the 
system's receiver/control. The transmitter is not 
used for detection purposes. Each detector has a 
unique ID code permanently assigned at the 
factory. You must program this ID into the control 
system at the time of installation. The ID allows 
each detector used in the system to be uniquely 
identified. You can program the ZR530 as 
"supervised " or "unsupervised." 
To conserve battery life during normal operation, 
no more than one transmission sequence will 
occur within a 3-minute period. There is no such 
time restriction in "test" mode. 
Alternate Polarity Pulse Count 
Two jumper-selectable detection response modes 
are provided: Instant response (Pulse Count OFF) 
and Alternate Polarity Pulse Count (Pulse Count 
ON). With Pulse Count OFF, any detected change 
in infrared energy will trigger an immediate alarm 
signal. This mode is recommended when the 
detector is used to monitor a narrow hallway 
where coverage is provided by only a single zone. 
Use the Pulse Count ON mode when the detector 
is installed in areas where periodic changes in 
infrared energy levels are normal (for example, 
where forced-air heating ducts are present). In this 
mode, at least two changes in infrared energy 
must be detected within a short period before an 
alarm will be triggered. 
Important Note: If the detector is to be used in 
the Pulse Count mode, be sure to walk test the 
unit in this mode. 
 
SPECIFICATIONS 
Transmission 
Frequency: 433.92 MHz 
Coverage: 12m 17m 
 18 zones (9 long, 5 inter-
 mediate, 4 short range). 
Pulse Count: Installer-selectable On/Off 
 link. 
Detectable 
Walk Rate: 0.15 – 1.5m/sec. 
Mtg. Height: 2.1m, but may be mounted 
 at other nominal heights 
 (see Table 1). 
Walk Test 
Indicator: Red LED with Test/Normal 
 (disable) link. 
Batteries: Two 3-volt lithium batteries. 
 Use only Duracell DL123A, 
 Panasonic CR123A, or 
 Sanyo CR123A. 
0perating 
Temperature: 0°C – 50°C 
Operating 
Humidity: Up to 95% RH (max.), non- 
 condensing. 
Dimensions: 68mm x 127mm x 48mm. 
 
 
 
Figure 1. 
Standard Wide -Angle Protection Pattern 
 
BATTERY INSTALLATION 
1. Remove front cover by inserting a large 
screwdriver blade (or small coin) in groove 
between cover and base at the location shown 
in Figure 2; rotate blade to override snap fit, 
then lift cover off. 
2. Observing correct polarity, install the two 
lithium batteries (supplied) into the battery 
holders, as shown in Figure 4. Make sure the 
batteries are firmly seated. 
3. Replace the cover (snap fit). 
Battery Caution: 
Risk of fire, explosion, and burns. Do not 
recharge, disassemble, heat above 100°C, or 
incinerate. Dispose of used batteries promptly. 
Keep away from children. 
Programming Note: If you have not yet 
programmed the detector’s ID into the system 
(i.e., this is an initial detector installation), refer 
to the PROGRAMMING section below and 
perform the ID “programming” procedure 
before mounting or testing the detector. 
 
PROGRAMMING 
You must enroll the detector’s ID during 
installation of the system. Program the control to 
enroll the ZR530 as "supervised." 
INSTALLATION HINTS 
•Do not install where the detector is exposed to 
direct sunlight or directly above strong sources 
of heat. 
•Make sure the detection area does not have 
obstructions (curtains, screens, large pieces of 
furniture, plants, etc.) which may block the 
pattern of coverage. 
•Avoid locating a unit in areas which contain 
objects likely to produce a rapid change in 
temperature, such as central heating, radiators, 
or ducts (or heaters of any kind), air 
conditioners, open flame, etc. 
•Do not mount on an unstable surface. 
INSTALLATION 
Radio Transmission Path Check 
Verify that a strong transmission path between the 
ZR530 and the QED's system Receiver/Control 
exists before permanently mounting the 
detector. Do this by performing the Walk Test 
(described later) with the detector temporarily 
mounted in its proposed location. The ZR530 will 
transmit when sensing motion (waving an arm or 
walking into an area). Sometimes, moving the 
detector only a few centimeters means the 
difference between a strong and weak 
transmission path. Experiment until you are 
satisfied that the location provides the strongest 
transmission path, while still being practical for the 
protection pattern desired. This test also verifies 
that the detector has been correctly programmed 
into the system. 
Normal Mounting 
Mount the unit to a firm vertical surface (flat on a 
wall or in corner). 
1. Remove the front cover. 
2. Temporarily loosen (do not remove) the screw 
holding the PC board in the detector base (see 
Figure 5 for location of this screw). 
 The board can then be moved up or down for 
access to the knockout mounting holes in the 
base. 
3. Refer to Figure 3 for location of knockout 
holes in the base. Break out only those holes 
required. 
4. Mount the detector with screws, using the 
selected mounting holes. 
5. Before fully tightening the PC board holding 
the screw, make sure the board is positioned 
so that the arrow is in line with the appropriate 
setting on the graduated scale on the right-