
18
16. IONISATION ELECTRODE
The ionisation electrode is located on the left hand side of the burner and is responsible for
detecting that a flame is present across the entire burner.
The electrode is reliant on the ability of the flame to conduct an electric current.
During combustion large numbers of free electrons and ions are present in the burner
flame, which acts as an electrolyte in which a current can flow.
The voltage to the electrode is supplied from the PCB 96V ac (J6 orange)
To check current connect a multimeter in series with the electrode. Select DC micro amps.
With the burner at maximum power expect 5 to 7 micro amps.
When the flame is detected the green neon will change from the solid green to a flashing
green to indicate that a flame has been detected along the full width of the burner.
17. HIGH LIMIT THERMOSTAT
Located on the front of the primary heat exchanger, the fully enclosed bi metal contacts
open if the temperature exceeds 102 degrees centigrade breaking the circuit to the PCB.
Voltage 22V dc is fed from the PCB (J6 second white) and returns to the PCB (J6 top
white) when the contacts are closed (normal position).
The high limit thermostat automatically resets as cooling takes place, but the boiler will
require the lockout (fault 3) to be manually reset at the control panel, before it will resume
normal operation.
N.B. The thermostat is dry mounted on the heat exchanger, (you can remove without
draining down). Never loosen or tighten using the electrical spade terminals.
21. DOMESTIC HOT WATER THERMISTOR
The thermistor screws into a wet pocket (under mains water pressure) at the hot outlet
side on the hydraulic unit and provides the PCB with the temperature of the domestic hot
water exiting the boiler.
As the temperature of the thermistor increases, the resistance decreases. This information
is used by the PCB and ensures that the gas valve modulates to achieve the correct
temperature as selected at the control panel.
In the domestic hot water mode the boiler has an operating range between 35 – 60
degrees centigrade during normal operation. If the thermistor detects a temperature
greater than 70 degrees centigrade then the boiler will shut down and the ignition
sequence will commence when the hot water temperature is lower than the selected
temperature.
If a fault develops on the hot water thermistor (out of range /false temp readings) lock out
will occur and fault code 10 will be displayed, if the thermistor cools to normal values then
the boiler will reset automatically.
If the thermistor fails to return to within normal range then the lock out will not reset and
the thermistor must be replaced.