- 10 -
2.6 SETTING MOTOR TYPE BY MANUFACTURER (Set Motor Type):
To Program the Actuator Motor Speeds:
1. Enter the Technical Service password (Up/Down/Left/Right), scroll
using Left/Right arrows (1) until Set Motor Type is displayed on screen,
then press the Select/Save Button (2).
2. You will be prompted to enter an additional password (re-enter the
password in reverse sequence: Right/Left/Down/Up)
3. Use the Left/Right arrows (3) to scroll through and select the motor
output (from control box) for which you would like to adjust the amperage
(i.e.; Tilt, Recl, Back, Elev, LLeg, RLeg, etc....)
Set
Motor Typ 1
2
TILT
UL2
IMPORTANT! When programming, the upper line of the screen display will only indicate the
assigned/programmed motor outputs (i.e. only the motor outputs being used will be displayed).
3
WARNING! Current limit adjustment beyond the factory settings is not necessary under typical operating
conditions. Improper adjustment may cause damage to the actuator and/or the positioning system.
Always contact Motion Concepts Technical Service Dept. prior to making any current limit adjustment.
Motor Type adjustments allow for programming of current/amperage limits for each individual motor.
The available current settings are provided in the reference matrix provided (refer to Table 1.0).
SAVE
OK
5
Select/Save
Exit/Back
(Press TWICE to
Save following
each change)
4. Before saving, verify that the angle & tipsy position you wish to set
are displayed on the screen (e.g. DLO, 25
°
), then press the Select/Save
button (5) TWICE to save changes.
Each tipsy position must be saved individually following
an adjustment
5. Repeat steps 2 - 4 as necessary to program remaining limits/angles.
6. To exit press the Exit/Back button once to return to the Program
Options screen. Press twice to exit program mode.
2.5 SETTING LIMITS AND LOCKOUT ANGLES (Set Tipsy): (... cont’d)
IMPORTANT! RECOMMENDED TIPSY ANGLES (SAFETY LIMITS)
Please refer to the following factory recommended limits/lockout angles when programming the Tipsy Sensor:
HOME POSITION 0° to 20°
REDUCED SPEED DRIVE Max. Limit = 20°
DLO (Drive Lockout) Limit1Max. DLO = 30° (Max DLO = 25° if No Reduced Speed Drive )
MAX BACK ANGLE Limit2Max. Tilt Limit = 55° (MCT systems), 50° (50T Mod.) or 45° (45T12 Tilt/Lift Mod.)
Max. Tilt/Recline Limit = 168° (Tilt/Recl, Recl-only)
1Note: DO NOT exceed the maximum recommended DLO Limit
2Note: for Bariatric (MCT-B) systems, the Max.Tilt Limit may be limited to 30° or 45° based on client weight
Resetting the Tipys Sensor: There are two options available to reset the existing tipsy settings- Default or Reset
DEFAULT (Factory Default Settings) = 15°Home, 20°Slow Down, 30°DLO, 168°Max Angle
RESET*= 0°Home, 0°Reduced Speed Drive, 0°DLO, 168°Max Angle
*Note: Requires the Home, Reduce and DLO limits to be re-programmed