Motorline professional MC60 Use and care manual

v4.2 REV. 08/2022
HW 1.2 FW V2.REV126
MC60MC60 EN
USER’S AND INSTALLER’S MANUAL

2A 2B
A
B
B
A
A
B
A
A
B
A
B
A
A
B
B
A
A
B
B
A
A
B
B
B
A
A
B
A
ENEN
INDEX INDEX
. CONTENT . CONTENT
. SAFETY INSTRUCTIONS
. CONTROL BOARD
. CONNECTION SCHEME
. INSTALLATION
. PROGRAMMING "P"
. PROGRAMMING "E"
. DISPLAY
. CONNECTION SCHEME
CHARACTERISTICS
SLIDING GATES [SC]
BUTTONS AND LEDs
BARRIERS [BR]
AUTOMATIC BOLLARDS [PL]
MASTER-SLAVE
CONNECTORS
SECTIONAL DOORS [SE]
BASE INSTALLATION PROCESS
REMOTE CONTROLS
FUNCTIONS
EXCLUSIVE FACTORY VALUES
"P" MENUS
"E" MENUS
P0COURSE PROGRAMMING
P1SLOWDOWN TIME ADJUSTMENT
E2COURTESY LIGHT TIME
P7OPERATING LOGIC
P4PAUSE TIME
P2SETTING DOWN TIME
E3FOLLOW ME
E4COURSE TIME ADJUSTMENT
P8FLASHING LIGHT
P5PHOTOCELLS 1 PROGRAMMING
E7MANUEVERS COUNTER
E0HUMAN PRESENCE
P3PEDESTRIAN COURSE TIME
E5BRAKE/LOCK/PUSH
P9REMOTE PROGRAMMING
P6PHOTOCELLS 2 PROGRAMMING
E8RESET RESET FACTORY VALUES
E9RGB OUTPUT
E1SOFT START
DISPLAY INDICATIONS
CONNECTIONS MAP
E6SLOWDOWN SPEED

3EN
GENERAL WARNINGS
•This manual contains very important safety and usage
information. very important. Read all instructions carefully
before beginning the installation/usage procedures and keep
this manual in a safe place that it can be consulted whenever
necessary.
•This product is intended for use only as described in this manual.
Any other enforcement or operation that is not mentioned is
expressly prohibited, as it may damage the product and put
people at risk causing serious injuries.
•This manual is intended firstly for specialized technicians, and
does not invalidate the user’s responsibility to read the “User
Norms” section in order to ensure the correct functioning of the
product.
•The installation and repair of this product may be done by
qualified and specialized technicians, to assure every procedure
are carried out in accordance with applicable rules and norms.
Nonprofessional and inexperienced users are expressly
prohibited of taking any action, unless explicitly requested by
specialized technicians to do so.
•Installations must be frequently inspected for unbalance and
the wear signals of the cables, springs, hinges, wheels, supports
and other mechanical assembly parts.
•Do not use the product if it is necessary repair or adjustment is
required.
•When performing maintenance, cleaning and replacement of
parts, the product must be disconnected from power supply.
Also including any operation that requires opening the product
cover.
•Theuse,cleaningandmaintenanceofthisproductmaybecarried
out by any persons aged eight years old and over and persons
whose physical, sensorial or mental capacities are lower, or by
. SAFETY INSTRUCTIONS
ATTENTION:
This product is certified in accordance with European
Community (EC) safety standards.
This product complies with Directive 2011/65/EU of the
European Parliament and of the Council, of 8 June 2011, on
the restriction of the use of certain hazardous substances
in electrical and electronic equipment and with Delegated
Directive (EU) 2015/863 from Commission.
(Applicable in countries with recycling systems).
This marking on the product or literature indicates that
the product and electronic accessories (eg. Charger, USB
cable, electronic material, controls, etc.) should not be
disposed of as other household waste at the end of its
useful life. To avoid possible harm to the environment or
human health resulting from the uncontrolled disposal
of waste, separate these items from other types of waste
and recycle them responsibly to promote the sustainable
reuse of material resources. Home users should contact
the dealer where they purchased this product or the
National Environment Agency for details on where and
how they can take these items for environmentally safe
recycling. Business users should contact their vendor
and check the terms and conditions of the purchase
agreement. This product and its electronic accessories
should not be mixed with other commercial waste.
This marking indicates that the product and electronic
accessories (eg. charger, USB cable, electronic material,
controls, etc.) are susceptible to electric shock by direct or
indirect contact with electricity. Be cautious when handling
the product and observe all safety procedures in this
manual.

4EN
persons without any knowledge of the product, provided that
these are supervision and instructions given by persons with
experienced in terms of usage of the product in a safe manner
and who understands the risks and dangers involved.
•Children shouldn’t play with the product or opening devices
to avoid the motorized door or gate from being triggered
involuntarily.
WARNINGS FOR TECHNICIANS
•Before beginning the installation procedures, make sure that
you have all the devices and materials necessary to complete
the installation of the product.
•You should note your Protection Index (IP) and operating
temperature to ensure that is suitable for the installation site.
•Provide the manual of the product to the user and let them know
how to handle it in an emergency.
•If the automatism is installed on a gate with a pedestrian door,
a door locking mechanism must be installed while the gate is in
motion.
•Do not install the product “upside down” or supported by
elements do not support its weight. If necessary, add brackets
at strategic points to ensure the safety of the automatism.
•Do not install the product in explosive site.
•Safety devices must protect the possible crushing, cutting,
transport and danger areas of the motorized door or gate.
•Verify that the elements to be automated (gates, door, windows,
blinds, etc.) are in perfect function, aligned and level. Also verify
if the necessary mechanical stops are in the appropriate places.
•The central must be installed on a safe place of any fluid (rain,
moisture, etc.), dust and pests.
•You must route the various electrical cables through protective
tubes, to protect them against mechanical exertions, essentially
on the power supply cable. Please note that all the cables must
enter the central from the bottom.
•If the automatism is to be installed at a height of more than 2,5m
from the ground or other level of access, the minimum safety
and health requirements for the use of work equipment workers
at the work of Directive 2009/104/CE of European Parliament
and of the Council of 16 September 2009.
•Attach the permanent label for the manual release as close as
possible to the release mechanism.
•Disconnect means, such as a switch or circuit breaker on the
electrical panel, must be provided on the product’s fixed power
supply leads in accordance with the installation rules.
•If the product to be installed requires power supply of 230Vac
or 110Vac, ensure that connection is to an electrical panel with
ground connection.
•The product is only powered by low voltage satefy with central
(only at 24V motors)
WARNINGS FOR USERS
•Keep this manual in a safe place to be consulted whenever
necessary.
•If the product has contact with fluids without being prepared,
it must immediately disconnect from the power supply to avoid
short circuits, and consult a specialized technician.
•Ensure that technician has provided you the product manual
and informed you how to handle the product in an emergency.
•If the system requires any repair or modification, unlock the
automatism, turn off the power and do not use it until all safety
conditions have been met.
•In the event of tripping of circuits breakers of fuse failure, locate
the malfunction and solve it before resetting the circuit breaker
or replacing the fuse. If the malfunction is not repairable by
. SAFETY INSTRUCTIONS . SAFETY INSTRUCTIONS

5A 5B
ENEN
The MC60 is a control board with built-in radio control system, developed for the
automation of sliding, sectional gates, barriers or 24V electromechanical bollard.
consult this manual, contact a technician.
•Keep theoperationareaof themotorized gate freewhilethe gate
in in motion, and do not create strength to the gate movement.
•Do not perform any operation on mechanical elements or hinges
if the product is in motion.
RESPONSABILITY
•Supplier disclaims any liability if:
•Product failure or deformation result from improper
installation use or maintenance!
•Safety norms are not followed in the installation, use and
maintenance of the product.
•Instructions in this manual are not followed.
•Damaged is caused by unauthorized modifications
•In these cases, the warranty is voided.
MOTORLINE ELECTROCELOS SA.
Travessa do Sobreiro, nº29
4755-474 Rio Côvo (Santa Eugénia)
Barcelos, Portugal
SYMBOLS LEGEND:
• Important safety
notices
• Useful information
• Programming
information
• Potentiometer
information
• Connectors
information
• Buttons
information
. SAFETY INSTRUCTIONS CHARACTERISTICS
. CONTROL BOARD
107mm
130mm
• Power Supply 20 Vac
• Flashing light’s output 24VDC 4W Max.
• RGB Flashing light’s output 24Vdc 100mA Max.
• Motor’s output 24Vdc 180W Max.
• Auxiliary accessories output 24V DC 8 W Max.
• Security and BT remote controls 24V DC
• Working temperature -25°C to + 55°C
• Incorporated Radio Receptor 433,92 Mhz
• OP remote controls 12bits or Rolling Code
• Maximum Memory Capacity 100 (full opening) - 100 (pedestrian opening)
• Control Board Dimensions 130x107 mm
• Fuse 8AL 250V

6A 6B
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
1
ANT
2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
BG R Y
V+
LK
LO FCF0 LE
LS LBLA
ANT
ENEN
VAC 01 • Power Supply Input - 20Vac
02 • Power Supply Input - 20Vac
BATT 03 • 24Vdc Input for Emergency Battery 24V + max 7Ah
04 • COM Input (Solar Panel ou Emergency Battery)
05 • 24Vdc Input for Solar Panel (28V max. 30W)
LAMP 06 • 24Vdc Flashing light's Output (max 4W)
07 • 0V Flashing light's Output
MOT1 08 • 24Vdc Motor Output (max 180W)
09 • 24Vdc Motor Output (max 180W)
V+ 10 • 24Vdc power supply output for accessories (max 8W)
11 • 0V power supply output for accessories
LK 12 • 24Vdc Electric Lock Output (max 12W)
13 • 0V Electric Lock Output
LO 14 • Total Opening Input (NO)
LS 15 • Pedestrian Opening Input (NO)
FO 16 • Closing limit-switch input
FC 17 • Opening limit-switch input
18 • Common
LE 19 • Exterior Photocells (NC)
LA 20 • Interior Photocells (NC)
LB 21 • NC input for emergency device
22 • Common
ANT 23 • Antenna
24 • GND
MENU • Access the Menu
CMD • Remote controls programmation
UP • Navigate through menus/values
DW • Navigate through menus/values
LO • LED ON when total opening input is
active
LS • LED on when the pedestrian opening
input is active
FO • LED OFF when the opening limit switch
is active
FC • LED OFF when closing limit switch is
active
LE • LED OFF when the signal from the
exterior photocells is interrupted
LA • LED OFF when the signal from the
interior photocells is interrupted
LB • LED OFF when the safety button is
active
BT • LED ON when the battery is connected
upside down
VDD • LED ON when power is supplied to
the microcontroller
CONNECTORS
. CONTROL BOARD BUTTONS AND LEDs
. CONTROL BOARD

7
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
ANT
~ ~
V+
R
G
B
RG
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
EN
SLIDING GATES [SC]
. CONNECTION SCHEME
• Motor
• Flashing Light
• Bateries
or or
• Photocells
•
Limit switch
• Pushbutton or
Key Selector (total)
• Pushbutton or Key Selector (pedestrian)
CLOSE
OPEN
• RGB Flashing Light
• Transformer
230/110Vac / 20V
120W Max.
• Fuse
230Vac: 2A
115Vac: 3A
• Power supply
Fuse
8AL 250V

8
COM
NC
NC
2
3
4
5
6
7
1
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
ANT
2
3
4
5
6
7
1
ON
1 2
ANT
STRSECSIGNL R G B + -
A1
A2
2
3
4
5
6
7
1
~ ~
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
EN
SECTIONAL DOORS [SE]
. CONNECTION SCHEME
• Limit Switches
Connections
• Motor
• Dock leveler
• Magnetic contact
• MX13
• MR13
OPTIONAL (security service)
• Relay
• Battery 24V 7A Max.
• Flashing Light
• Electric Lock
• Photocell
• Maneuvering board
White
Green
Orange
Blue
Brown
Gray
Black
Fuse
8AL 250V
• Fuse
230Vac: 2A
115Vac: 3A
• Power supply

9
12V+
1 2 3
BI RI
4 5 6
GI RGI SEI
8 97
SEO
1 2
RGOROBO
2 3 4 51
GOV+
LGHI SEO
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
ANT
~ ~
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
EN
BARRIERS [BR]
. CONNECTION SCHEME
• Barrier cover
• LED strip
(Flashing Light)
• Motor
• Barrier
• Transformer
230/110Vac / 20V
120W Max.
• Fuse
230Vac: 2A
115Vac: 3A
Blue
Brown
• MC60 control board
(Interior of the barrier)
•
Limit switch
• Safety edge
(Optional)
• LED strip
(Boom)
• Power supply
12VDC
36 W
• Module MP106
• MP106 module
in the interior
OPEN
CLOSE
In case of inversion of the
boom, replace the blue wire
with the brown and the micro
of the limit switches, marked by
1 and 2.
• Photocells
• Power supply
Fuse
8AL 250V
• Battery 24V 7A Max.

10
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
ANT
LIGHT
VR1
+-
SEL SET
MONO TEMP. I.CMD
12V24V 0V
M1 M2 FLH FC 24v
24v
RGB
R
G
B
GND
GND
~ ~
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
EN
AUTOMATIC BOLLARDS [PL]
. CONNECTION SCHEME
• Bollard
• MSC50
• Photocells
• 24V Battery
MSC50 is a twilight sensor.
When turned on, the LEDs will
operate only during the night,
remaining off during the day.
If you want them to always be
connected, disconnect LB and
COM wires.
The use of photocells or a
magnetic loop is essential
to ensure the safety of the
automation.
• LED strip
•
Module
If limit switches are not used,
Shunt the FO - FC - ↓ inputs.
Red
Yellow
Black
Green
• Transformer
230/110Vac / 20V
120W Max.
• Fuse
230Vac: 2A
115Vac: 3A
• Power supply
If the LED strip
is 12V, there
must be a
resistance of
180 Ohms/5
watts in series
with the 24V
of the relay
module.
Fuse
8AL 250V

11
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
ANT
BG R Y
V+
LK LO
V+ FCF0 LE
LS LBLA
LAMP MOT1
SP
24v
BATT
20V
VAC
ANT
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
EN
MASTER - SLAVE
. CONNECTION SCHEME
• Transformer
230/110Vac / 20V
120W Max.
• Transformer
230/110Vac / 20V
120W Max.
• Fuse
230Vac: 2A
115Vac: 3A
• Fuse
230Vac: 2A
115Vac: 3A
• Power supply
• Power supply
To use this mode, select the function at P0 (page 14B).
The values are updated automatically.
Fuse
8AL 250V Fuse
8AL 250V

12A 12B
ENEN
01 • Connect all accessories according to the connections diagram.
02 • Connect the control board to a 20V power supply
03 • Check if the gate movement is the same as shown on the display:
04 • Make a course programming - menu P0 (page 14B).
05 • If necessary, adjust the slowdown time of the gate at opening and closing - menu
P1 (page 15A).
06 • Adjust the gate force - menu P2 (page 15A).
07 • Re-program the course - menu P0 (page 14B).
08 • Enable or disable the use of Photocells in menu P5 and P6 (page 16A and 16B).
09 • Program a remote control (page 12B).
The control board is now fully configured!
Check the pages of the menu programming if you want to configure other features of the
Control board.
CLOSE OPEN
If the display does not match the
movement of the gate, switch off the power
supply center and change the wires of
Motor (8 and 9) and check the direction of
the limit switches.
The installation process assumes that the gate already has mechanical or
electrical limit switches installed. For more information read the motor's
manual.
BASE INSTALLATION PROCESS
. INSTALLATION
05 • Press cmd for 3 sec
and the location will be
empty.
The display will blink
and the position will
be free.
02 • The display will show
dL, confirming that all
remote controls have been
erased.
01 • Press the cmd button
for 5 sec.
01 • Press the
cmd button for
1 sec.
Remote control programming for total opening. Remote control programming for pedestrian opening.
02 • Select (SU or
SP) use↓↑.
03 • Press cmd
once to confirm.
(SU or SP).
04 • Use ↓↑
to select the
remote controls
location you want
to delete.
04 • The first free
position appears.
05 • Press the remote
controls button you want to
program. The display will
blink and move to the
next free location.
03 • Press cmd
once to confirm.
(SU or SP).
01 • Press the
cmd button for
1 sec.
02 • Select the
function where you
want to program
the remote controls
(SU or SP) use ↓↑.
• PROGRAMMING REMOTE CONTROLS
• ERASE ALL THE REMOTE CONTROLS
• ERASE REMOTE CONTROLS
•If you do not press any button for 10 sec.
the control board will return to standby
• Whenever you store or delete a
the display will flash and show the next
position. You can add or delete remote
controls without needing back to point 01.
REMOTE CONTROLS
. INSTALLATION

13A 13B
ENEN
1 • To access the P menu press the MENU button for 1 sec.
2 • Use ↓↑ to navigate through the menus.
3 • Press MENU when you want to confirm access to a menu.
4 • Press ↓↑ simultaneously to exit programming.
1 • To access the E menu press the MENU button for 5 sec.
2 • Use ↓↑ to navigate through the menus.
3 • Press MENU when you want to confirm access to a menu.
4 • Press ↓↑ simultaneously to exit programming.
1 2
3 4
The functions of the plant are divided into 2 areas:
FUNCTIONS
. INSTALLATION
We can only go into programming with the gate electrically stumbled.
"P" MENU
"E" MENU
"P" MENUS
. INSTALLATION
1 2
3 4
EXCLUSIVE FACTORY VALUES
. INSTALLATION
MENU SUB-MENU SC SE BR PL
- 1 1
1
1
MENU FUNCTION MIN. MAX. STATE FACTORY
VALUE PAGE
Course Programming
- -
Automatic Programming
sc
B
Manual Programming
System type
Slide gates
Sectional gates
Electromechanical barriers
Bollard
Master/Slave Master
Slave
Slowdown time
adjustment s .s
Opening slowdown
Closing slowdown See
table
p.A A
Time ramp at the opening
Time ramp at the closing
Force and sensibility
adjustment Force Adjustment in Opening
Force Adjustment in Closing
Sensitivity adjustment
See
table
p.A A
Pedestrian Course
time s s Time setting in pedestrian mode s B
Pause time s s Full closing pause time adjustment
Pedestrian lock pause time
adjustment s B
Photocells
programming - -
Disables
Active
A
In Opening
In Closing 01
Invert
STOP
Invert 2 sec. and Stop
Photocells
programming - -
Disables
Active
B
In Opening
In Closing
Invert
STOP
Invert 2 sec. and Stop 01
Disables security band input
Activates security band input
Operating logic - - Automatic mode function
Step by step mode
Condominium mode function 01 B
Flashing light - - Flashing (opening and closing)
Step by step mode
Courtesy light A
Remote programming - - Distance PGM OFF
Distance PGM ON A

14A 14B
ENEN
MENU FUNCTION MIN. MAX. STATE FACTORY
VALUE PAGE
Human presence - -
Disables Human presence
Active at closing
Active during opening and closing 00
B
Disables push buttons mode
Activates push buttons mode 00
Disables emergency device input
Activates input for Emergency
Active input for twilight sensor 00
Soft start - - Deactivates Soft start
Activates Soft start A
Courtesy light time Courtesy light time adjustment A
Follow me - -
Desactivates follow me
00 B
Activates follow me (fully
open)
Activates follow me (in open
or fully open position)
s s Set closing time (sec)
Course time
adjustment
m m Opening course time (minutes) 00
B
s s Opening course time (seconds) 10s
m m Closing course time (minutes)
s s Closing course time (seconds) s
Brake/Lock/Strokes - -
Disables electronic brake
Active electronic brake
A
Activates lock on opening
Activates lock with polarity
See
table
p.A
Slowdown Speed
Adjusting the slowing down at the
opening
Adjusting the slowing down at the
closing
See
table
p.A A
Manuevers counter - - Shows the number of maneuvers - B
Reset - Restore factory
settings - - Deactivated
Reset activated
RGB Output - - Continued output
Intermittent output
"E" MENUS
. INSTALLATION COURSE PROGRAMMING
. PROGRAMMING "P"
Automatic course
scheduling
This menu allows you to
automatic motor
programming and
slowdown.
To cancel the
programming press the
UP and DOWN buttons
simultaneously.
You can use the remote
control instead of the
MENU button.
Automatic programming:
01 • Press MENU for 1 sec. until it appears .
02 • Press MENU once until it appears .
03 • Press MENU to start automatic programming. The following
maneuvers will be carried out:
a • Closes in slowdown
b • Opens 4 sec. at normal speed.
c • Closes in slowdown
d • Fully opens at normal speed.
e • Closes 4 sec. at normal speed.
f • Opens in slowdown.
g • Closes total at normal speed.
Manual course
programming
This menu allows
manually program the
motor and slow down.
Manual programming:
01 • Press MENU for 1 sec. until it appears .
02 • Press MENU once until it appears .
03 • Press UP until it appears .
04 • Press MENU to start programming the opening time.
05 • Press MENU to start programming the slowdown time at the opening.
06 • Press MENU to start programming the closing time.
07 • Press MENU to start programming the slowdown time at closing.
08 • Press MENU to finish programming.
System type
This menu allows you
to program the type of
system with which the
control board will work.
Sliding gates:
Emergency device deactivated
Deactivate Push button function
Opening ramp time at 0
Closing ramp time at 0
Programming system type:
01 • Press MENU for 1 sec.
until it appears .
02 • Press MENU once until it
appears .
03 • Press UP until it appears
.
04 • Press MENU to select
one of the systems.
Sectional doors:
Emergency device activated
Disables func. pushbutton
Ramp time at opening to 0
Ramp time at closing to 0
Activates lock with polarity
Electromechanical barriers:
Emergency device disabled
Disables func. pushbutton
Ramp time at opening to 25
Ramp time at closing to 25
Activates lock on opening
Bollard:
Deactivate Push button function
Opening ramp time at 30
Closing ramp time at 30
Master/Slave
Communication model
for hardware devices
where one device has
one-way control over
another device.
Master
Controls the main functions of the Slave Programming Master/Slave:
01 • Press MENU for 1 sec.
until it appears .
02 • Press MENU until it
appears .
03 • Select or .
04 • Press MENU to confirm
a function.
Slave
It is controlled by the Master

15A 15B
ENEN
SLOWDOWN TIME ADJUSTMENT
01 • Press MENU for 2 sec. until appears .
02 • Use UP until appears .
03 • Press MENU will appear . Use UP or DW to navigate the parameters.
04 • Press MENU to edit the chosen parameter value.
05 • The factory set time appears. Use UP and DW to change the value.
06 • Press MENU to save the new value.
This menu allows to set the slowdown time at opening and closing.
Opening slowdown
Allows to set the time that the gate will act
with slowdown in the opening.
(Default value 3)
Closing slowdown
Allows to set the time that the gate will act
with slowdown in the closing.
(Default value 3)
Time ramp at the opening
Allows to set the slowdown ramp time at the
opening.
(Default value: SC=00; SE=00; BR=25; PL=30 )
Time ramp at the closing
Allows to set the slowdown ramp time at the
closing.
(Default value: SC=00; SE=00; BR=25; PL=30 )
. PROGRAMMING "P"
0s
min. max.
9.9s
AJUSTE DO TEMPO DE ABRANDAMENTO
. PROGRAMMING "P" FORCE AND SENSIBILITY ADJUSTMENT
A very low value in this parameter F0 or Fc, can cause the motor not to have
enough torque to move the gate, or FS too high.
Opening force adjustment
Allows to set the force that
is injected into the opening
when the engine moves at
normal speed.
Closing force adjustment
Allows to set the force that
is injected into the closing
when the motor moves at
normal speed.
Sensibility adjustment
Allows to adjust the
sensitivity of the motor in
the presence of obstacles.
The higher the sensitivity,
the less effort it will take
to detect any obstacle and
reverse direction.
min. max.
9
0
(Default value:
SC=05; SE=05; BR=09; PL=05 )
min. max.
9
0
(Default value:
SC=05; SE=05; BR=09; PL=05 )
min. max.
9
0
(Default value:
SC=00; SE=00; BR=07; PL=05 )
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
01 • Use UP until appears .
02 • Press MENU. The factory set time appears.
03 • Use UP and DW to change the value.
04 • Press MENU to save the new value.
The pedestrian mode allows the gate to be opened for the passage of
people, without it needing to open in its entirety.
In this function you can schedule the time you want the gate to open.
For pedestrian mode to work, it is necessary that the
minimum work is 1 second, and 0 disables the pedestrian.
(Default value 10 seconds)
99s0s
min. max.
TEMPO DE PAUSA E ATRASO DE PORTAS
Pause time adjustment for automatic closing
This menu allows to set the total opening
pause time.
Pause time adjustment for automatic closing in
pedestrian closing
Allows to set the pause time at the pedestrian
opening.
(Default value 0) (Default value 0)
When the values are at zero, there is no automatic closing.
99s
min. max.
0s
99s
min. max.
0s
FORCE AND SENSIBILITY ADJUSTMENT
. PROGRAMMING "P"
PEDESTRIAN COURSE TIME
. PROGRAMMING "P" PAUSE TIME
. PROGRAMMING "P"

16A 16B
ENEN
01 • Use UP until appears .
02 • Press MENU will appear . Use UP or DW to navigate the parameters.
03 • Press MENU to edit the chosen parameter value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
00 (off)
01 (active)
Enable or disable security
entry.
00 (opening photocells)
01 (closing photocells)
This menu can only be changed
when the LE menu is active.
Allows you to define whether
this security will act on the
opening or closing of the gate.
00 (the gate is reversed)
01 (gate stops and resumes 5
sec after security is disabled)
02 (gate reverses for 2 sec. and
stop)
It allows to define the
behavior that the gate will
have when this security is
activated.
(Default value 0) (Default value 1) (Default value 0)
Allows to program the security behavior LE (photocell 1).
01 • Use UP until appears .
02 • Press MENU will appear . Use UP or DW to navigate the parameters.
03 • Press MENU to edit the chosen parameter value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
PAUSE TIME
PHOTOCELLS PROGRAMMING
. PROGRAMMING "P"
. PROGRAMMING "P"
01 • Use UP until appears .
02 • Press MENU will appear . Use UP or DW to navigate the parameters.
03 • Press MENU to edit the chosen parameter value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
00 (off)
01 (active)
Enable or disable
security entry.
00 (opening
photocells)
01 (closing photocells)
This menu can only be
changed when the LA
menu is active. Allows
you to define whether
this security will act on
the opening or closing
of the gate.
00 (the gate is
reversed)
01 (gate stops and
resumes 5 sec after
security is disabled)
02 (gate reverses for 2
sec. and stop)
Allows to set the
behavior that the gate
will have
when this security is
activated.
00 (disables safety
edge)
01 (active safety
edge)
(Default value 0) (Default value 0) (Default value 1) (Default value 0)
Allows to program the security behavior LA (photocell 2).
This menu allows to set the operating logic of the automation
Automatic Mode
Whenever there is an order the
movement is reversed.
Step by step mode
1st impulse - OPEN
2nd impulse - STOP
3rd impulse - CLOSE
4th impulse - STOP
Stopping movement during closing
disables automatic closing.
Condominium Mode
Does not respond to orders
during opening and pause time.
(Default value: SC=01; SE=01; BR=02; PL=02)
PHOTOCELLS PROGRAMMING
. PROGRAMMING "P"
OPERATING LOGIC
. PROGRAMMING "P"

17A 17B
ENEN
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
Flashing
(opening and closing)
During the opening/closing
movement of the gate, the
flashing light will operate
intermittently.
Opening - flashing 2s
Closing - flashing 1s
Step by step mode
In the opening and closing
movement, the flashing light is
permanently ON.
When stopped, it remains off.
Courtesy light
In the opening and closing
movement the flashing light is
permanently ON. When in
pause time remains ON.
When stopped or closed,
remains on for the time set
in E2.
Default value (00)
This menu allows to set the operation mode of the flashing light (LAMP).
Distance PGM OFF Distance PGM ON
This menu allows to enable or disable the programming of new remote control without
directly accessing the control board, using a previously stored remote control
(memorize remote controls page 11B).
Default value (00)
OPERATING LOGIC
FLASHING LIGHT
REMOTE PROGRAMMING
. PROGRAMMING "P"
. PROGRAMMING "P"
. PROGRAMMING "P"
Remote Programming Operation (PGM ON):
• Press the buttons indicated in the image simultaneously for 10
seconds and the flashing light will flash (the 1st free position appears
in the display).
Each time you store 1 remote control, the control board will exit remote
programming. If you want to memorize more remote control, you will
always have to repeat the process of pressing the remote controls
buttons simultaneously for 10 seconds for each new remote control.
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
00 (disables human presence)
Whenever a order to ls input and
the motor performs a complete
maneuver.
Human presence
01 (active at closing)
The motor only works if you keep
the LS button pressed.
Human presence
02 (active during opening
and closing)
The motor only runs if you keep the
LS button pressed.
When human presence active, the
RF remote controls do not work.
00 (disables pushbutton mode)
01 (active pushbutton mode)
Allows you to define the way
Operation of the LB input
00 (disables input to
emergency stop device)
01 (input for
emergency stop)
02 (twilight sensor input - outputs
for LEDs that run at night and
remain out of the day)
(Default value 00)(Default value
SC=00; SE=01; BR=00; PL=02)
LS LO
01
ACTIVE Full
closing Full
opening
00
OFF
Pedestrian
opening
Full
opening
01 • Press MENU for 5 sec. until it appears .
02 • Press MENU will appear . Use UP or DW to navigate the parameters.
03 • Press MENU to edit the chosen parameter value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
REMOTE PROGRAMMING
HUMAN PRESENCE/PUSHBUTTON
. PROGRAMMING "P"
. PROGRAMMING "E"

18A 18B
ENEN
00 off
01 active
Enables or disables the soft start. With the soft start function activated, at each start of move-
ment the control board will control the motor start, increasing the speed gradually in the first
second of operation.
(Default value 01)
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
Allows to adjust the courtesy light time. The courtesy light is activated the set time when the
gate is in the closed, opened and stopped position.
The E2 menu will only be available if the courtesy light function is activated in the P8 menu
option 2 (see page 16A).
(Default value 00)
SOFT START
COURTESY LIGHT TIME
. PROGRAMMING "E"
. PROGRAMMING "E"
Opening course time
(minutes) Opening course time
(seconds) Closing course time
(minutes) Closing course time
(seconds)
(Default value 0) (Default value 10) (Default value 0) (Default value 10)
Allows to adjust the working time for the opening and closing courses at normal speed
01 • Use UP until appears .
02 • Press MENU will appear . Use UP or DW to navigate the parameters.
03 • Press MENU to edit the chosen parameter value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
FOLLOW ME
COURSE TIME ADJUSTMENT
. PROGRAMMING "E"
. PROGRAMMING "E"
01 • Press MENU for 5 sec. until appears.
02 • Press MENU until appears. Use UP or DW to navigate parameters.
03 • Press MENU to edit the value of the chosen parameter.
04 • Choose the desired value. Use UP and DW to change the value.
05 • Press MENU to save the new value.
00 function disabled
01 function activated after opening
02 function activated on opening
Allows you to activate the Follow me option.
With this option activated, the control board,
when in the open position or in opening, gives
a closing order of 5 sec. after the safety device
detects the passage of an object / user.
01 - 09 closing time function
Allows setting the closing time (sec) after
the safety device detects the passage of an
object/user.
(Default value 00)

19A 19B
ENEN
00 (disables electronic brake)
01 (activates electronic brake)
Allows you to activate the electronic brake.
00 (activates lock at opening 1 sec.)
01 (activates lock with polarity)
Allows you to select how the lock works.
(Default value 0) (Default value 0)
Allows to activate the electronic brake and change the behaviour of the LK output (lock)
This menu allows you to adjust the slowdown speed.
The higher the level, the faster the slowdown.
01 • Use UP until appears .
02 • Press MENU will appear . Use UP or DW to navigate the parameters.
03 • Press MENU to edit the chosen parameter value.
04 • The factory set time appears. Use UP and DW to change the value.
05 • Press MENU to save the new value.
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
BRAKE/LOCK/PUSH
SLOWDOWN SPEED
. PROGRAMMING "E"
. PROGRAMMING "E"
Setting of the slowing speed at the opening
Allows you to adjust the slowing speed in the motor
opening.
Setting of the slowing speed at the closing
Allows you to adjust the slowing speed in the motor
closing.
min. max.
9
0
(Default value: SC=05; SE=05; BR=02; PL=05)
min. max.
9
0
(Default value: SC=05; SE=05; BR=01; PL=05)
This menu allows you to view the number of maneuvers performed.
(complete maneuver means opening and closing).
Resetting the control board does not clear the maneuver count.
Example: 13456 maneuvers
01- Hundred thousand / 34- Thousands / 56- Dozens
01 • Press MENU for
10 seconds. 02 • E0 appears.
Press UP until
appears E7.
03 • Press MENU.
1º 2º
display flashes display flashes
04 • The maneuvers count is displayed in the following order (example: 130 371)
05 • E8 appears.
3º dozens
2º thousands
1º hundred thousand
MANUEVERS COUNTER
. PROGRAMMING "E"

20 EN
Continuous light Flashing light
(Default value 00)
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
01 • Use UP until appears .
02 • Press MENU will appear .
03 • Press MENU to edit the value.
04 • Use UP and DW to change the value.
05 • Press MENU to save the new value.
RESET - RESET FACTORY VALUES
RGB OUTPUT
. PROGRAMMING "E"
. PROGRAMMING "E"
Resetting the control board does not erase the maneuver count.
Disabled Reset enabled
(Default value 00)
Other manuals for MC60
1
Table of contents