MS Electronics WMPD2 User manual

Product Guide
WMPD2
WMPAD2
WMPAD2-L
today, tomorrow and in the future
mselectronics.co.uk
Wall Mounted
Presence/Absence Detectors
2-wire versions
WMPD2 Presence Detector
WMPAD2 Presence/Absence Detector
WMPAD2-L with LED indicator
energy saving controls
Issue 1.0

WMPD2 · WMPAD2 · WMPAD2-L2
Figure 2 Typical wiring example and dimensions (in millimetres)
Product Overview
The Wall Mounted Presence/Absence Detector range provides
exible occupancy-based switching for lighting, heating, air
conditioning and ventilation equipment. The built-in PIR (passive
infra-red) sensor detects motion of body heat, providing
convenient activation of the connected load whilst saving energy
by switching it off automatically when the space becomes
unoccupied (after an adjustable period). An adjustable ambient
light threshold optionally inhibits initial activation when the area is
adequately lit, reducing wasteful use of lighting.
• The WMPD2 Presence Detector offers fully-automatic
operation, switching on the load upon detection of motion, and
switching off when the area has been unoccupied for the set
period.
• The WMPAD2 Presence/Absence Detector includes a
touch-sensitive override button and offers the exibility of
two operating modes to suit either manual or automatic initial
activation.
• The WMPAD2-L provides an illuminated button to aid location
of the unit in the dark (when used in Absence Mode). The LED
also acts to facilitate accurate setup of the light sensor function.
The units are simple to install and t a standard single-gang UK
pattress or back box (22mm min. depth). Ideal applications include
small booths or rooms, workshops, entrance halls, staircases,
toilets, store cupboards, hired sports courts and rooms plus many
more.
Figure 1a WMPD2
Figure 1b WMPAD2
Figure 1c WMPAD2-L

3mselectronics.co.uk
Positioning
Figure 3 illustrates the typical detection pattern
of the PIR sensor when the unit is wall-mounted.
Ensure that the proposed mounting position will
offer the required area of detection.
High Sensitivity Zone:
Detects e.g. arm movement.
Low Sensitivity Zone:
Detects e.g. whole body movement.
Tips
• The sensor is most sensitive to motion across
its eld of view, rather than directly towards or
away from the sensor.
• Avoid mounting the unit close to a light or heat
source (the one being switched, or otherwise)
since this may interfere with the detection.
• Multiple units may be wired in parallel to
extend the detection eld – see Using Multiple
Detectors.
Figure 3 PIR sensor detection pattern
Electrical Requirements
Before attempting to install the unit, ensure that the intended load and wiring arrangement
comply with the following requirements. Figure 2 shows a typical wiring example.
• 2-wire (live/load) connection: The unit connects ‘inline’ with the load, and is therefore
suited to replacing an existing standard light switch (or similar) with no permanent mains
neutral conductor available at the switch location.
• Minimum load: This 2-wire model requires a minimum load of 20W (per detector) in
order to function correctly. If this is not met, or if faults occur in use (such as the load not
switching off), a load capacitor (MS Electronics product code CAP68) may be required.
Also available: WMPD3 / WMPAD3 / WMPAD3-L (3-wire versions) – No minimum load;
volt-free relay output (can be used with an independently-powered load or as a contact
closure). Requires a permanent mains live/neutral connection.
• Maximum load: The maximum load rating is 16A (4000W), however for high inrush
loads (such as most types of lighting) a lower limit applies: see Technical Specication.

WMPD2 · WMPAD2 · WMPAD2-L4
Installation
All electrical installation and maintenance must be carried out by a competent person. If in doubt,
consult a qualied electrician. Any new wiring must be carried out by qualied personnel in
accordance with the current edition of the IET Wiring Regulations (BS7671).
!
Ensure the electrical supply is isolated before making any connections or adjustments.
!
1. Select a suitable location for the unit (following the guidelines under Positioning) and
prepare a single-gang pattress or back box as necessary.
2. The unit contains a battery, which must be switched on prior to use. Using e.g. a small
screwdriver, move Switch 1 to the ‘ON’ position as indicated on the accompanying label.
3. Adjust the controls according to the operational requirements.
− Rotate the Timeout and Lux Level thumbwheels to the desired settings. For non-
lighting loads, ensure the latter is set correctly. See Controls below.
WMPAD2-L only The button illumination LED may be used to assist setup of the Lux
Level control: see LED Indicator below.
− WMPAD2(-L) Use Switch 2 to select the desired operating mode: see Controls below.
WMPD2 only Switch 2 is not used and should not be adjusted.
4. Connect the wiring as shown in Figure 2 (or in any suitably appropriate form) using
mains cable having a current rating appropriate to the load.
5. Fix the unit into position with the two screws and caps supplied.
Controls
• Timeout (10 seconds to 60 minutes): Sets the period of time over which no motion must
be detected, after which the load is switched off.
• Lux Level: Sets the ambient light level threshold, below which the unit will permit
activation upon detecting motion. For non-lighting loads, and in other cases where
operation should be permitted at any light level, turn the control fully towards ‘Light’.
• Operating Mode WMPAD2(-L): Select either Presence Mode (‘Pres.’) or Absence Mode
(‘Abs.’). See Operation for details.
Additional Guidelines
• If the unit will be disconnected from the mains supply for an extended period, return
Switch 1 to the ‘OFF’ position until it is next required.
• The screw caps may be removed at a later date with the aid of an adhesive putty such
as Blu-Tack.
LED Indicator WMPAD2-L only
The LED indicator lights when the load is off, and the ambient light is below the threshold
set by the Lux Level thumbwheel. As well as aiding location of the unit in darkness (when
used in Absence Mode), it can be used to check that the Lux Level setting is appropriate.
The electrical supply to the unit MUST be isolated before making adjustments.

5mselectronics.co.uk
Operation
The diagrams below illustrate the sequence of operation, according to the model and
operating mode of the unit.
Operation Notes
• After establishing the mains supply to the unit, the PIR sensor requires approx. 1 minute
to stabilise before motion detection is possible.
• If the unit does not respond to motion during testing, remember that the ambient light
level must be low enough (with respect to the Lux Level setting) to permit activation.
• The Lux Level setting only affects whether motion will switch the load on. Once on, any
motion detected will prevent the timeout from expiring, regardless of the light level.
WMPAD2(-L) In Absence Mode, the light sensor is not used since the load is switched on
manually.
Key
WMPAD2(-L)
Absence Mode
WMPAD2(-L)
Presence Mode
WMPD2 only

WMPD2 · WMPAD2 · WMPAD2-L6
Using Multiple Detectors
If the detection pattern of the unit does not fully cover the desired area, multiple units may
be connected in parallel to extend the detection coverage.
The following wiring example is intended only as a recommendation. Proper wiring practice must be
observed with relevance to the particular installation.
!
Figure 4 illustrates a typical wiring arrangement using two WMP(A)D2 units; Figure 5
represents the same conguration as applied to a typical ceiling rose lighting circuit. This
method can typically reuse pre-existing wiring from a 2-way switching installation where
3-core cable has been run between the switch locations, noting that only two of the cores
are needed.
Each unit detects motion independently and operates its own timing cycle, but the load
is shared. When either or both units detect motion (or are overridden to ‘ON’ using their
respective touch-sensitive button), the load will switch on. Once both units have detected
no motion for their respective timeouts, the load will switch off.
WMPAD2(-L) When using the override button to switch the load off, the load will remain
powered if the other unit is still in the ‘ON’ state.
The total minimum load requirement increases in line with the number of detectors sharing
the same load, e.g. for two units, 2 × 20W = 40W. If necessary, connect a load capacitor –
see Electrical Requirements.
Figure 4 Typical wiring schematic for two units
Figure 5 Typical ceiling rose plan

7mselectronics.co.uk
TechnicalSpecication
Power supply 220V - 240V AC 50Hz (in-the-line)
Output switch rating 16A, 250V AC (resistive)
Minimum load 20W
Maximum lighting load
Incandescent: 12A (3000W)
Fluorescent: 10A (2500W)
Compact Fluorescent: 10A (2500W)
Timeout selection 10 seconds to 60 minutes
Detection angle 100°
Detection range High sensitivity: up to 5m
Low sensitivity: up to 10m
Mounting hardware 22mm (min.) single-gang UK pattress box
Operating temperature -10°C to +40°C
Guarantee 5 Years
Weight 98g
Dimensions 86mm x 86mm x 35mm
Fault Finding
Ensure the electrical supply to the unit is isolated before making any adjustments.
!
Load will not switch on
a) Unit is not powered correctly (or load circuit is faulty)
• Ensure the unit is correctly connected to an active mains supply and load circuit.
• Ensure the internal battery is switched on using Switch 1 on the back of the unit.
• Check that the load works on its own by bypassing the detector.
b) Unit is not set up correctly
• WMPAD2(-L) Ensure the operating mode has been selected appropriately. In
Absence Mode, the override button must be used to switch on the load.
• Wait 1 minute after connecting the mains supply for the PIR sensor to stabilise.
• Ensure the Lux Level setting is appropriate (including for non-lighting loads).
• Ensure the unit is sited away from strong light and heat sources.
c) Internal battery is low (WMPAD2-L only the LED ashes continuously)
• Leave the unit powered for at least 3 hours (WMPAD2-L only or until the LED stops
ashing) to allow the battery to charge before retrying.
Loadswitcheson,butdoesnotswitchoff(orlightingloadickers)
• Ensure the minimum load requirement has been met: see Electrical Requirements.
Load does not switch off, or switches on unexpectedly
• Ensure the set period is allowed to elapse with no motion in the detection zone.
• Ensure the unit is sited away from strong light and heat sources, including the load.
• Ensure there are no other inadvertent sources of triggering. To test this, tape thick
paper or card over the sensor lens (and wait for the set timeout period to elapse).

e: info@mselectronics.co.uk
t: 0333 666 1176 f: 0333 666 1436
mselectronics.co.uk
Follow us on twitter: @mselec
MS Electronics reserves the right to change this specification without prior notice.
energy saving controls
Technical Support
For further help or information on this and other products in the MS Electronics range
visit www.mselectronics.co.uk or call 0333 666 1176.
Alternatively, email techsupport@mselectronics.co.uk
Additional copies of this product guide can be downloaded from our website.
Product Warranty
MS Electronics guarantees all their products against manufacturing defects for
5 years from the purchase date. If your product is found to be faulty, MS Electronics will,
at their discretion, repair or replace the product free of charge.
Note
Any modification or damage to the product including damage due to abuse or
incorrect wiring may invalidate the guarantee.
This manual suits for next models
2
Table of contents
Popular Security Sensor manuals by other brands

TimeTec
TimeTec Water Leak Detector user guide

Acuity Controls
Acuity Controls nLight nCM RJB Series instructions

STEINEL PROFESSIONAL
STEINEL PROFESSIONAL sensIQ KNX instructions

Dr. Smart
Dr. Smart Inverter Air-Conditioner Detector Operation manual

B.E.G. LUXOMAT
B.E.G. LUXOMAT PD2N-KNX-BA Mounting instructions

Autonics
Autonics LSE-4A5R2 manual

Apollo
Apollo Smoke Detector XP95 Installation & maintenance guide

DMP Electronics
DMP Electronics 1183 Series installation guide

Ecolink
Ecolink TX-E611 Installation sheet

FireClass
FireClass FC400CH quick start guide

New Cosmos Electric
New Cosmos Electric PS-7 Operation manual

Ansell
Ansell VIKING PROTECH II owner's manual