MS Electronics WMPD3 User manual

WMPD3
WMPAD3
WAPIR
Product Guide
3-Wire Wall Mounted PIR
Occupancy Switch
today, tomorrow and in the future
mselectronics.co.uk

WAPIR Issue 1.0 2
Product Overview
The 3-wire wall or ceiling mounted passive infra-red occupancy switch (WAPIR) should be wall
mounted at a locaon where a neutral connecon is available. The WAPIR incorporates a passive
infra-red quad sensor to detect movement of a warm body within the detecon zone (diagram B
or C) and a photocell to monitor the ambient light level.
Upon detecng movement, if the ambient light is dark enough, the
WAPIR switch will turn the load on. The ambient threshold can be set
by the user to between approx. 30 lux and 1000 lux and maximum
(photocell inacve) at the PIR via the LUX adjuster (diagram A). If no
more movement is detected within a pre-selected me, then the
WAPIR switch will turn the load o. This me lag can be set via the
TIME adjuster to 10, 20, 40 seconds, 1 min 15 secs, 2 min 30 sec, 5m,
10m, 20m or 40 mins ( diagram A).
The WAPIR also incorporates a sensivity adjuster. Turn fully clockwise
for maximum range and sensivity of the occupancy detecon.
Several WAPIR units can be wired in parallel, using re-wired 2-way lighng wiring to allow
mulple PIR detectors (diagram E).
Loading Limits:
The WAPIR should only be connected to a 230V 50Hz AC supply.
The PIR switches can switch up to:
•6 amps (1500W) of electronics or wire wound transformers
•6 amps (1500W) of compact uorescent loads
•3 amps (750W) of electronic and wire wound transformer loads
•2 amps (500W) of CFL. 2D Lamps, LED Drivers and LED lamps and ngs
•1 amp (250W) of fans
Minimum Load
Minimum load 2W resisve, suitable for most energy saving lamps, LEDs and emergency ngs.
Figure 1.

WAPIR Issue 1.0 3
Installaon Procedure
1. The switch should be placed facing the area where acvity is expected, if wall mounted at
between 1 and 1.8 mm high (diagram C). If the photocell override facility is required, the
switch must be sited in a posion where daylight can give greater illuminaon than the
arcial light
2. Connect the WAPIR as:
a. L – Live in
b. N – Neutral in
c. SL – Switched line out.
3. A few WAPIR’s products can be wired in parallel to control the same load (see diagram E).
4. There are three adjustments on the underside of the switch: TIME, LUX and SENS
(sensivity) (Diagram A).
5. When the wiring has been completed and veried, switch on the supply and test operaon.
When the PIR is powered up, it will switch on the load for 1 minute, the load will then switch o
and the PIR will enter its Operang Mode. If a manual override-o switch is posioned before
the PIR in the circuit (Diagrams D&E, note 1).
It will do this each me the wall switch is switched on. Alternavely, if the wall switch is placed
aer the PIR (Diagrams D&E, note 2) it will not enter the start-up mode each me.
LUX and Time Set-up
For convenience, ensure that the TIME is set to the minimum and the WAPIR is set to automac
mode when seng up the LUX level.
Aerwards se the TIME and SENS to values suitable for the applicaon. The LUX is best set up
when the local ambient light is close to the minimum desired light level. With the LUX set fully
clockwise, wait for the WAPIR to switch OFF. Rotate the LUX adjuster slowly anclockwise (- to +)
whilst waving your hand approximately 1m in front of the WAPIR, unl the load switches ON.
Adjustment – Typical Sengs
For indicaon see typical seng:
TIME: 10-20mins
LUX: Set fully clockwise (See above) SENS: 100%
All electrical installaon and maintenance must be carried out by a competent person. If in doubt,
consult a qualied electrician. Any new wiring must be carried out by qualied personnel in
accordance with the current edion of the IET Wiring Regulaons (BS7671).
Ensure the electrical supply is isolated before making any connecons or adjustments.

WAPIR Issue 1.0 4

WAPIR Issue 1.0 5
Volt Free Variant
VF Switches a secondary signal rather than the supply voltage.

WAPIR Issue 1.0 6
Relay Logic Diagrams

WAPIR Issue 1.0 7
Fault Finding:
The load will not switch on:
❖The LUX adjuster is set too low and is inhibing the switch.
❖The moving body is not eming more than the background (person wearing insulang
clothing in a warm environment).
❖Person is too far from the PIR switch (see detecon diagram)
❖Person is moving unusually slowly (perhaps when tesng)
The load switches on when nobody is present:
❖Heater causing infra-red variaons in a small cold room.
oReduce the sensivity adjuster or re-site the WAPIR.
TECHNICAL SPECIFICATION
Power Supply
220V-240V AC 50Hz (in the line)
Output switch rang
16A, 250V (resisve)
Minimum load
2W resisve
Maximum lighng load
Incandescent: 6A (1500W)
Fluorescent: 10A (2300W)
Compact Fluorescent: 6A (1500W)
Fans: 1A (250W)
Timeout
10 seconds to 40 mins
Detecon Angle
120°
Detecon range
High sensivity: up to 5m
Low sensivity: up to 10m
Mounng hardware
22-32mm single-gang UK paress box
Operang temperature
-30°C to +40 °C
Guarantee
2 years
Weight
180gm
Dimensions
86mm x 86m x 22mm

WAPIR Issue 1.0 8
Technical Support
For further help or informaon on this and the other products in the MS Electronics
range
visit www.mselectronics.co.uk or call 0333 666 1176.
Alternavely, email techsupport@mselectronics.co.uk
Addional copies of this product guide can be downloaded from our website.
Product Warranty
MS Electronics guarantees all their products against manufacturing defects for
5 years from the purchase date. If your product is found to be faulty, MS Electronics will,
at their discreon, repair or replace the product free of charge.
Note
Any modicaon or damage to the outer casing of the product, as well as any
damage to the product due to abuse or incorrect wiring may invalidate the guarantee.
t: 0333 666 1176 f: 0333 666 1436
mselectronics.co.uk
Follow us on twier: @mselec
MS Electronics reserves the right to alter or change this specicaon without prior
noce.
This manual suits for next models
2
Table of contents
Other MS Electronics Switch manuals





















