MULTIGUARD micro User manual

multiGuard® micro
Remote control and alarm via GSM
Manual
Ver. 2.02
Profort A/S • Gunnar Clausens Vej 3 DK 8260 Viby J • Tel. +45 70233600 Fax +45 70233601 • E-mail: [email protected] www.profort.dk
INDHOLD
1. SYSTEM DESCRIPTION...................................................2
2. MOUNTING ...................................................................3
Prepare the central unit ..................................3
Install SIM-card...............................................3
Electric mounting ............................................3
DIP switches for analog inputs........................3
3. PREPARE PC ..................................................................4
3.1 Connect PC ...............................................4
3.2 Set-up via USB-RS232 serial converter......4
3.3 Find Com-number .....................................4
4. INSTALLATION OF PC-PROGRAM ..................................5
5. SETTING UP WITH ”QUICK-SETUP” ...............................6
Window 1: Modem .........................................6
Window 2: Receiver(s) ....................................7
Window 3: Inputs............................................8
6. SETTING UP WITH SMS................................................13
Shift PIN-code ...............................................13
Lost password ...............................................13
Deactivate password.....................................13
Setting up receiver(s) ....................................13
Delete receiver ..............................................14
Setting up zone for receiver ..........................14
Approve telephone numbers.........................14
Change the priority of receivers ....................14
6.1 SETTING UP DIGITAL INPUT.......................................14
Set up text.....................................................14
Send alarm only if text is entered..................14
Set up zone for digital input..........................15
Use input 0 for connection/disconnection .....15
Set up filter on input .....................................15
Use input for counting pulses........................15
Activate 24V .................................................16
Execute command in text field......................16
6.2 SET UP ANALOG INPUTS ...........................................16
6.3 SETTING UP OUTPUT .................................................17
Activate output in case of alarm ...................17
Set up macro .................................................17
Record IR-code ..............................................18
Transmit IR-code ...........................................18
6.4 SYSTEM MESSAGES AND ALARMS ............................18
Acknowledge command................................18
Send alarm immediately on power failure.....18
Send status message.....................................19
Set time in the unit........................................19
Time controlled connection/disconnection ....19
Text to and from serial port (RS232) .............19
Data communication with PLC ......................19
6.5 COMMANDS FOR SET-UP ..........................................20
7. OPERATION................................................................. 26
Connect/disconnect the unit..........................26
Control by SMS..............................................26
Control by DTMF ...........................................26
Acknowledge alarm ......................................26
Requests to the unit ......................................26
Restore to default settings ............................27
9. FREQUENTLY ASKED QUESTIONS ................................29
10. SPECIFICATIONS........................................................ 31

multiGuard® micro
Remote control and alarm via GSM
Mounting
Ver. 2.02
2
1. SYSTEM DESCRIPTION
The unit is used for controlling relays and data/alarm-
transmission via the GSM-network. It contains GSM-
modem and a built-in antenna. Power supply: 8-24V
DC
The unit can be set up with alarm texts of your own
choice via SMS or via the PC COM-port and the
enclosed ”Quick-setup” program.
Extra equipment:
•External antenna with 2,5 m. cable
(Profort no. 3690003)
•3,6V rechargeable LiIon battery
(Profort no. 009010)
•Temperature probe
(Profort no. 007995)
•Advanced PC-program “Basic” for many settings
on PC
(Profort no. 900902)
Functions
1 digital input
•Make (NC) / break (NO)
•Gnd/24V DC
1 analog input
•0-10 V
•0-20 mA
•PT100
•Profort temperature probe
•as digital input
1 Infra Red input
•Learns up to 10 IR-codes from a IR remote
control
Activation of 1relay-output
•Activate remotely with SMS and DTMF
•Activate as a function of input (from 10
sec. to 16 min. or follows input).
1 Infra Red output
•Transmits up to 10 IR-codes by SMS/DTMF
Forward alarms to max. 25 recipients
•as SMS messages
•as voice call with DTMF-tones
•as e-mail (depending on the telephone
company)
Calls 3 times in case of no answer.
Acknowledgement of alarm by pressing # during
the message (the call list will be interrupted).
Automatic alarm in case of sabotage and power
failure (also in disconnected state).
Back-up 14 days in case of power failure with
3,6V battery and in ‘sleep mode’.
Time functions:
Time based connection/disconnection
Time based status messages
Time registration in the log
Commands in the text for inputs
Alarm from 8 zones
Log: 256 records
Data communication with PLC via RS 232
Variable filter time for inputs: 10 sec. to 30 min.
Delay alarms for 30 sec. when connecting
/disconnecting the unit
Remote control of the unit with macros
System overview

multiGuard® micro
Remote control and alarm via GSM
Mounting
Ver. 2.02
3
2. MOUNTING
The unit has a built-in GSM-modem. All types of SIM-
cards can be used except from 3G cards. However it is
recommended to use a SIM-card “Pay and go”
instead of an ordinary SIM-card because the latter
often has an expiry date after e.g. 6 months.
Prepare the central unit
1. Lift the front cover of the unit.
The unit must be turned off!
2. Connect all relay-outputs and inputs to the unit.
Use at least 24 AWG – or stronger if possible.
Install SIM-card
3. Insert the SIM-card to be used
into a GSM-mobile phone.
4. Check that the SIM-card’s PIN
code is set to 1234 (default for
most telephone companies). If not, set the PIN
code to 1234 or deactivate the PIN code.
5. Check if it is possible to call from the card, and
send/receive SMS.
6. Remove the SIM-card fromf the GSM-mobile
phone and insert it into the GSM-unit.
7. Check that any inputs and relay-
outputs are properly connected
and place the front cover onto
the central unit again.
8. Connect the central unit to 230 VAC or
12-24 V AC/DC. Wait approx. 10 sec. while the
GSM-modem makes contact to the GSM-network.
When you hear 4 ’beeps’ and the red LED lights
continuously for approx. 20 sec. the unit is ready.
9. Send, if necessary, a SMS with ”1234 OK” to
get the GSM signal strength. It must be higher
than 25%.
Electric mounting
The unit can be mounted on a DIN-rail.
1. If the GSM-conditions are bad, replace the
internal antenna by an external antenna.
2. Mount, if necessary, 9V rechargeable battery.
3. Connect outputs:
Relay-outputs are potential free relay contacts that
break (NO) or make (NC) by means of instructions to
the unit. As default all relay-outputs are open.
4. Connect digital inputs:
Digital inputs are optocouplers. The inputs are
activated by 0V default (gnd) or 24 VDC on inputs
(can be changed in the set-up program). If the
supply is removed the inputs will deactivate. In both
cases an alarm can be sent from the central unit.
NB! Input 0 can also be used for
activating/deactivating the unit (toggle switch or
bell switch). Input 1 can be used for counting pulses.
GND or 24V on inputs, selected as option in the PC-
software.
5. Connect analog inputs:
As default the analog inputs function as ordinary
digital inputs (all Dip - switches off). If the analog
inputs are to be adapted to standard equipment: 0-
10VDC, 0-20 mA or PT100 probe, the Dip-switches
in the GSM-modem must be adjusted as illustrated
below.
DIP switches for analog inputs
Digital: Dip-switch 1-4 off
0-10VDC: Dip-switch nr. 1 on
0-20mA: Dip switch nr. 2 on
PT100: Dip switch nr. 3 on
Profort probes: Dip switch nr. 4 on
Each analog input has 4 Dip-switches.
Equipment and probes must be connected
between gnd and Ain1.

multiGuard® micro
Remote control and alarm via GSM
Prepare PC
Ver. 2.02
4
3. PREPARE PC
Start by connecting the serial converter and finding
the COM-port number on the PC.
3.1 Connect PC
1. Connect the COM-port output of the unit to
COM1 or the USB plug on the PC. Use a 9
pole serial cable or a USB to RS 232 serial
converter. The illustration below shows the
connections used in a RS232 cable.
Minimum requirements, PC:
Windows 95, 32 Mbyte RAM
Monitor, 800x600 screen
COM-port or USB-port
3.2 Set-up via USB-RS232 serial converter
When the USB cable is connected to the USB plug on
the PC Windows provides the PC with a COM-
number. A PC can have more than one COM-port,
and the actual COM-number provided by Windows
depends on which COM-port is used for setting up
the unit. Therefore it is necessary to check which
COM-number Windows has given to the selected
COM-port.
1. Install the driver enclosed with the USB-
converter and follow the instructions for this
product.
2. Connect the USB-cable to the USB-plug on
the PC.
Notice that the next time you connect the
USB-cable to either the same or another
COM-port the given COM-number can have
been changed.
3.3 Find Com-number
3. Select the menu START on your PC.
4. Select Control panel > System.
5. Select Hardware > and the first button
just below.
6. Select Ports.
Read the USB-to-Serial COM-Port.

multiGuard® micro
Remote control and alarm via GSM
Installation of PC-program
Ver. 2.02
5
4. INSTALLATION OF PC-PROGRAM
When the COM-no. is identified start the PC-
program for setting up the unit.
Install the set-up program on the PC:
1. Check that the COM-port output of the
unit is connected to COM1 or the USB
plug on your PC.
2. Insert CD-ROM in PC and click OK.
Windows suggests to install the setup-program
in C:\Programmes\Profort
To change this location, press Change Directory
and select the required folder.
3. Click the button in the upper left corner in
order to start the installation.
The installation runs automatically and
takes about 20 sec.
4. Start the setup-program on the PC. If the
text ”Version conflict” appears select the
latest version.
5. Enter the product key in the
window ’Product key’ which is automatically
displayed: The product key is written on the
cover of the CD-ROM.
If you have entered a product key to access
Quick-setup the screen below will be displayed:
6. Select the number of the COM-port to
which the unit is connected. If a correct
COM-port is selected the text
”Connection to multiGuard” in the
bottom
left corner will appear.
NB! If the text ”No Connection” appears
either a wrong COM-port is selected, the
unit is turned off or the RS232 cable is
defect.
If the text ’Connection to multiGuard’ doesn’t
appear, you have to check if
the correct COM-port has been selected.
7. Click the ‘Back’ button. Select
Communication port, only available
communications ports are listed.
8. Click the ’Next’ button and you will be
guided step by step through 4 setting
windows (see Setting up with Quick-
setup).

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
6
5. SETTING UP WITH ”QUICK-SETUP”
Start Quick set-up on the PC and follow the set-up instructions through the 4 windows. The settings will
be stored in unit’s ’flash memory’ and can be recovered in case of power failure. If the unit is coded
without a SIM-card the front cover must be removed.
Window 1: Modem
Present password: The password of the unit. When starting set-up the default password 1234 must be
applied. Remember that the PIN-code of the SIM-card in the unit also has to be
1234 when starting set-up.
GSM-number: Here the telephone number of the SIM-card in the unit is entered (optional unless the
clock-function is applied).
New password: Only numbers – not letters (4 digits). Here a new password, if required, is entered.
The PIN-code of the SIM-card will be changed similarly. If the password must be
deactivated the new password must be: 0000.
ID: Numbers or letters. Here an ID of the unit (max. 32 digits), if required, is entered.
Can be sent with all alarms.
NB! The password is applied for sending commands to the unit. The ID is transmitted
from the unit in case of alarm. If no ID is entered the password will also be the ID.

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
7
Window 2: Receiver(s)
It is possible to encode max. 25 receivers/ telephone numbers.
Forward alarms
Alarm messages can be forwarded as SMS, DTMF or E-mail. If you wish to receive both a SMS and an
analog voice message it is necessary to set up the same telephone number twice. A phone number can be
of max. 15 digits. An E-mail address can be of max. 48 characters.
Zone
In the field ’Zone’ (optional) is indicated whether all alarm messages are to be forwarded to the entered
telephone number or if this actual telephone number is to be called only in case of alarm from a specific
zone (0-7). Only one zone can be entered. If the same telephone number is to be called in case of alarm
from e.g. 2 zones the actual telephone number must be entered twice. If the field ’Zone’ is empty, alarm
from all zones will be received. The field ‘Zone’ disappears when the option ‘Approve’ is active.
Approve telephone numbers
If one or more telephone numbers are selected in the field ‘Approve’ the unit accepts SMS and analog
calls only from these numbers.
NB!: If the approved telephone number is not correct it is necessary to connect a cable in order to contact
the unit.

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
8
Window 3: Inputs
if the unit is not to be set up with user defined texts the unit will send the following standard messages in
case of alarm:
•S0: Make/close on input 0.
•B0: Break/open on input 0
If the unit is to be set up with user defined texts these can be encoded by means of the enclosed program
”Quick-setup”.
Text for inputs
In the window ’Inputs’ the text (max. 64 characters) to be displayed when an input changes position
is entered.
It is not necessary to enter a text also for closed position. That is if the activated relay is within a distance
of where it is possible to go inspect the problem. But it can be helpful if you are far away from the
activated relay and need a feedback on whether e.g. an irrigation plant has been inspected and again
functions normally.
If an alarm is to be sent only from the inputs which have a text, select either ‘ID + Text’ (return ID an
alarm text) or ‘Text’ (return only alarm text) in the field ‘Only send the alarm if text is entered’. Thereby
empty inputs will be filtered.
If ’Only send the alarm if text is entered’ is empty all alarms will be sent whether a text is entered or not.

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
9
Zone
”Zone” is optional and can be used for locating alarms in categories, e.g. some alarms in zone 1 and
other alarms in zone 2.
Filter
If “Filter” is selected, alarms will be sent only if the position of the input has been constant during the
filter time. See description of filter time below.
Analog input
The central unit has 1 analog input to which technical equipment can be connected in order to measure
an exact value, e.g. a temperature. In the field ‘Type’ select measuring equipment (0-10 V, 0-20 mA, PT
100, Profort 007995, Profort 007990). If the field ’Type’ is empty the analog inputs function as digital
inputs.
For 0-10V and 0-20mA the values for voltage and milliamp are optional for volt (fra –999 til +999). No
decimales.
Example:
In Scale (min max) define the values for 0V and 10V. ‘Min’ corresponds to 0V and ‘Max’
corresponds to 10V (default setting). Define e.g. that -20ºC corresponds to 0V and 60ºC corresponds to
10V. For the other measuring equipment in the list the values are already entered but can be modified.
In Alarm (min max) define the allowed interval. Define e.g. that min. is 0ºC and max. is 30ºC.
If the value gets higher or lower than the values in the Alarm (min/max) interval an alarm text (max. 64
characters) will be sent. For instance if the temperature drops below 0ºC or rises to 31ºC. The message
will be displayed in the inbox or on a mobile phone.
An Ok text (max. 64 characters) will be returned when the value is again between Alarm min. and max. If
information on a value is required, e.g. the temperature in a room, a request can be sent to the unit either
by SMS with the command V1 R
Set up input
’Input 0 used for connecting/disconnecting: Select how to change position on input. Either by using
‘Level’ (level control) or ‘Pulse’ (pulse control). If empty input 0 is a regular alarm input.
‘Input 1 used for counting pulses’: If selected input 1 is used for counting pulses. If empty
input 1 is a regular alarm input.
’Filter time’: Indicates a variable filter time for inputs. In the field ‘Filter’ for inputs is selected which
inputs are going to use the entered filter time. Select 10 sec., 20 sec., 40 sec., 1 min., 2 min., 4
min., 8 min., 15 min. and 30 min.
‘Only send the alarm if text is entered’: If a text is entered for inputs and wireless detectors, the alarm will
be sent. If there is no text, the alarm will not be sent. ‘ID + Text’: sends position, ID and text.
‘Text’: sends only text. The alarm text can be adapted to interface to pager systems or CCTV via
the serial port.

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
10
’Activate digital input’: The input can be set to GND or 24 VDC mode. In GND mode the input is activated
by a 0 VDC supply (GND) and input is closed. If the supply is removed inputs will open. In 24
VDC mode the input is activated by a 24 VDC supply and input will close. If the supply is
removed the input will open.
All digital inputs are either gnd or 24 VDC mode.
Activating commands in the text field
It is possible to enter one or more commands in the text field for digital and analog inputs so that a SMS-
message will be sent and at the same time a command will be carried out when the input changes it’s
position.
Commands in the beginning of the text field means that the command will be carried out also if the unit
is disconnected. If the command is at the end of the text field the command will not be carried out when
the unit is disconnected.
Example of a command in the text:
In this example the command OK means that the unit sends the actual GSM signal strength to all
telephone numbers when input 0 is open, e.g. by pressing a button. The receiver gets a SMS with the
signal strength in percent.
If no message is to be sent when input 0 shifts from open to closed position no text is to be entered in the
field ”Text when input is closed”.
Several commands must be separated
by a semicolon.
Commands start with < and ends with > ,
e.g.: <S0> will close relay.

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
11
Window 4: Output
Setting up output
’Activate relay outputs on alarms’: Indicates if output must activate (close) in case of alarm and for how
long. 10 sec., 20 sec., 40 sec., 1 min., 2 min., 4 min., 8 min., 15 min., Infinitely, Reflect inputs.
0 indicates that outputs don’t activate. ‘Reflect inputs’ indicates that outputs reflect the
corresponding inputs, if a text is entered.
’Relay outputs reflect connected/disconnected’: If selected outputs will be closed when the unit is
disconnected and open when the unit is connected. If the field is not completed the relay
functions as usual.
‘Send message to receivers’: If selected an alarm message will be sent to approved receivers/phone
numbers in the list when connecting or disconnecting the unit. If not selected no message will
be sent when connecting or disconnecting the unit.
‘Return command’: If selected the unit returns the command to approved receivers/ telephone numbers in
the call list when the unit is connected/disconnected. If not selected the unit doesn’t return a
command.
‘Send also sabotage alarm…’: If selected a sabotage alarm will be sent also when the unit is
disconnected. If not selected no sabotage alarm will be sent when the unit is disconnected.
‘Send power alarm immediately’: If selected the unit sends the text ‘Power alarm’ immediately in case
that the external power supply fails. Afterwards the unit runs for 30 min., where after it shuts
down. If the power returns, within 30 min., the default text ‘Power Ok’ will be sent. If not
selected: the unit runs for 30 min. waiting for the power to return. If the power doesn’t return

multiGuard® micro
Remote control and alarm via GSM
Setting up with
Quick set-up
Ver. 2.02
12
the unit sends the same power alarm as before after 30 min. and then shuts down. When the
power returns the unit sends the standard text ‘Power Ok’.
Status
’Interval’: Select either ‘Every week’, ‘Every day’, or ‘Number of 15 min’ for how often the unit must send
a status message from inputs. If the status function is active the unit sends a status
message also when it is disconnected. The function is available for analog and digital inputs
with a text. Can show closed/open state, an analog value or number of pulses. If there is a
command in a text field for the actual input the command will be carried out at the same time.
’Time’: Indicates the time for sending a status message about the position of inputs. Use TTMM for
‘Every week’ (always Wednesday) and ‘Every day’. For ‘Number of 15 min’ indicate the interval
between status messages, e.g. 0004 for each hour.
’Timer’: Indicates the time for automatic disconnection/connection of the unit. If only automatic
connection is needed, the option ‘Disconnect’ must be empty. Use the format TTMM.
Output
’Open’: Indicates normal position of relay. If outputs must
close
by activation of alarm, select the
option ‘Open’. Outputs will be open when starting the set-up.
’Closed’: Indicates normal position of relay. If outputs must
open
by activation of alarm, select the
option ‘Closed’. Outputs will be closed when starting the set-up.
Macros
’Macro name’: Here a command of free choice is entered by using a text of up to 16 characters, e.g. ‘Start
pump’. This macro text replaces the system command and is to be sent to the unit as SMS or
instruction in stead of an ordinary command.
’Commands’: Here enter the command or more commands to be attached to the selected
macro name. Several commands must be separated by semicolon, e.g. S0; PS 5; B0 for closing
relay 0, pause for 5 sec. and then open relay 0.
Max. 10 macros can be registered (M0-M9).
When the set-up procedure is conducted press the button ’Execute’. Remember that there has to be a
serial connection to the unit (or a modem). The text “Connection to Modem” will appear in the bottom
left corner. During the transmission of the settings the unit ’beeps’ several times.

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
13
6. SETTING UP WITH SMS
The unit can be set up with SMS from a GSM-
mobile phone. The set-up will then be
transferred as SMS-commands.
Commands consists of the following:
•Password of 4 digits *
•space *
•Command of 2 characters
•space
•parameter as text
max. 64 characters.
*) only omitted if the password is deactivated.
Example:
1234 A0 PUMP OFF
NB!: Each part of the command must be
separated by a semicolon. The text can
be of max. 64 characters. Spaces count
as a character.
When starting the set-up use the
password of the unit as PIN-code when
the SIM-card is taken in use.
The PIN-code of the SIM-card must
always be 1234 the first time the unit
is installed or a new SIM-card is
installed.
If you don’t know the password the
unit can always be restarted by
changing the PIN-code to 1234 in a
mobile phone, if necessary enter PUK-
code and reinstall the SIM-card.
Password will now be 1234
The following commands for setting up the unit
can be sent by SMS.
Shift PIN-code
1234 N0 99999999 yyyy
(99999999 = mobile nr. of the unit. Y = new
password of 4 digits).
Changing the PIN-code is optional but protects
against unauthorized use. If the clock-function is
activated it is necessary to encode own
telephone number. Otherwise the information is
not applied.
Lost password
If you have lost the password do the following:
1. Remove the power from the unit, incl.
back-up battery.
2. Insert the SIM-card in a mobile phone
and change the PIN-code to 1234
(PUK code can be necessary).
3. Mount the SIM-card in the unit and
connect the power.
The password for setting up the unit by SMS is
now 1234
Deactivate password
1234 N0 99999999 0000
If deactivated 1234 is omitted when sending
commands.
Setting up receiver(s)
Before the unit can send alarms it is necessary to
set up receivers. Max. 25 receivers named 1..9
and A (10), B (11) up to P (25) can be set up.
Alarms can be received as:
1. SMS
2. DTMF (IBS protocol)
3. e-mail (service depends on the telephone
company)
Example:
1234 N1 99999999
Sets up receiver nr. 1: SMS.
(99999999 = telephone nr.)
Example:
1234 N2 99999999 *
Sets up receiver nr. 2: DTMF call.
If the person who receives a DTMF call presses
the # button the call will not be forwarded to
other receivers, if any. The unit ends the calling
sequence immediately.
Example:

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
14
Sets up receiver nr. 4: e-mail (200= Telephone
company’s e-mail service). The E-mail address =
max. 48 characters.
N5..N9 and NA..NP address the other 21
receivers in the call list.
Delete receiver
1234 Nn
Deletes receiver on position n. (n=1..9, A..P).
Setting up zone for receiver
Receivers can be connected to certain zones so
that certain alarms will be sent to certain
receivers. Requires that inputs are put into zones
(see ”Setting up alarm in zone”).
1234 zn 99999999
z=zone 0..7, n=receiver 1-9, A-P, 99999999=
telephone nr.
Example:
13 = zone 1 on receiver no. 3
41 = zone 4 on receiver no. 1 etc.
Approve telephone numbers
If only certain telephone numbers are allowed to
contact the unit send the following command:
1234 Nn 99999999 +
n = available receiver position: 1..9, A..P.
Only telephone nr. 99999999 can contact the
unit. Other numbers are rejected.
If more telephone numbers should be approved
send one more command with a telephone nr.
In order to cancel the approval it is necessary to
delete the receiver.
Change the priority of receivers
The order of alarm calls can be changed with
just one SMS. This is used for instance in order
to change duty rosters so that one week alarms
will be directed to nr. 1, 2 and 3, the following
week to nr. 4, 5 and 6. It is only necessary to
send one SMS at the start of the week e.g. ‘1234
NR 123’.
1234 RN nnn…(n=0..9 , A..P).
Calls are executed only to selected positions and
in the listed order.
1234 RN
The calling sequence is restored to normal: from
the first to the last receiver.
6.1 SETTING UP DIGITAL INPUT
In stead of default texts it is possible to set up
user defined texts which are displayed when
inputs changes their position. The text can be
defined for open and for closed position. The
following commands are sent by SMS:
Set up text
1234 A0 TEXT
Sets up text for input which will be shown on
open/break.
1234 L0 TEXT
Sets up text for input which will be shown on
close/make.
Delete text
1234 A0
Deletes text on input x (x=0..7) on open/break.
1234 L0
Deletes text on input x (x=0..7) on close/make.
Send alarm only if text is entered
If an alarm is wanted only when input is open or
closed enter a text only in the wanted position
and send the following command:
1234 CT
Sets the unit to send only text from inputs which
have a text.
1234 CN
Sets the unit to send position, ID and text from
inputs which have a text.
1234 CF
Sets the unit to send alarm even if no text is
entered.

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
15
Set up zone for digital input
Inputs can be put into zones in a way that
alarms from certain inputs are directed to certain
receivers. Zones can also be applied to prevent
an input from sending alarm if there hasn’t been
entered any number for the actual zone (e.g.
heat control).
1234 A0 Zy TEXT
Sets up text for input in zone y (y=0..7) on
open/break.
1234 L0 Zy TEXT
Sets up text for input in zone y (y=0..7) on
close/make.
Use input 0 for
connection/disconnection
1234 RN
Sets up connection/disconnection by means of a
level switch (toggle switch).
1234 RP
Sets up connection/disconnection by means of a
pulse switch (call switch).
1234 RF
Deactivates connection/disconnection on
input 0.
Set up delayed alarms by
connection/disconnection
Alarms can be delayed for 30 sec., so that
connection/disconnection can be done without
activating alarm.
1234 L0 Wy TEXT
Sets up text for input on ’close/make’ and delays
the alarm for 30 sec. in zone y (y=0..7).
1234 A0 Wy TEXT
Sets up text for input on ’open/break’ and delays
the alarm for 30 sec. in zone y (y=0..7).
Set up filter on input
1234 Fx
Sets up filter time x on all inputs with filter
(x=1..9). F1: 10 sec. (default). F2: 20 sec., F3: 30
sec., F4: 1 min., F5: 2 min.., F6: 4 min., F7: 8
min., F8: 16 min. F9: 30 min.
1234 A0 Xy TEXT
Sets up text for input x (x=0..7) on ’open/break’
with a filter in zone y (y=0..7).
1234 L0 Xy TEXT
Sets up text on input x (x=0..7) on ’close/make’
with a filter in zone y (y=0..7).
Use input for counting pulses
1234 UN
Activates pulse counting. Start value = 0.
1234 UN 999999
Activates pulse counting. 9 = start value
between 0-999999, enter e.g. 50. The counting
starts from 50 pulses.
1234 L1 999999
Sets a value limit and sends an alarm if the value
is exceeded (1-999999). The counter is reset
after alarm.
1234 A1 TEXT
Sets the unit to send an alarm text if the limit
value is exceeded.
1234 UF
Deactivate pulse counting.
Use input for counting minutes
1234 UM
Activates minute counting. Start value = 0.
1234 UM 999999
Activates minute counting. 9 = start value
between 0-999999, enter e.g. 50. The counting
starts from 50 pulses.
1234 L1 999999
Sets a value limit and sends an alarm if the value
is exceeded (1-999999). The counter is reset
after alarm.
1234 A1 TEXT
Sets the unit to send an alarm text if the limit
value is exceeded.
1234 UF
Deactivate pulse/minute counting.
Set up delay on DTMF message
DTMF-sequence can be delayed for up to 10 sec.
from ”B-answer” to the message is played.

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
16
1234 Xx (x=0..9).
Sets up delay on message in x number of sec.
(standard is 2 sec.).
Activate 24V
1234 WN
Sets inputs to activate by 24 V.
Deactivate 24V
1234 WF
Sets inputs to activate by GND.
Execute command in text field
It is possible to enter one or more commands in
the text field for digital and analog inputs so
that a SMS-message will be sent and at the
same time a command will be carried out when
the input changes it’s position.
Example:
1234 PULSE30 <S0;PS 30;B0>
Make relay, pause in 30 sec. break relay.
Commands start with < and end with > More
commands must be separated by a semicolon.
Commands in the beginning of a text means that
the command will be carried out even if the unit
is disconnected.
6.2 SET UP ANALOG INPUTS
The GSM-unit can read analog values on two
analog inputs (Ain1 + Ain2) and, if required,
control the outputs as a function of the reading:
The following information must be entered:
Scale (min/max): limit values of the
measuring equipment.
Alarm (min/max): lower and upper limit
for alarm.
Alarm text: Message when the measuring
goes from normal interval to alarm
interval.
Ok text: Message when measuring goes
from alarm interval to normal interval.
Scale:
1234 V1 S min max
Sets up minimum and maximum scale for
measuring equipment:
Vx (x=1..2), min (-999..999) and max (-
999..999).
Alarm (min/max):
1234 V1 M min max
Sets up minimum and maximum for normal
interval: min (-999..999) and max (-999..999).
Alarm text:
1234 V1 A TEMPERATURE ALARM
Sets up text for input when outside normal
interval.
Ok text:
1234 V1 L TEMPERATURE OK Sets up
text for input when inside normal interval.
Set up zone for analog input
1234 V1 A Zy TEMPERATURE ALARM
Sets up text for input in zone y (y=0..7) for alarm
interval.
1234 V1 L Zy TEMPERATURE NORMAL
Sets up text for input in zone y (y=0..7) for
normal interval.

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
17
6.3 SETTING UP OUTPUT
Relay-output can be activated when the inputs
changes their position.
The outputs are deactivated as default. They can
be activated as follows:
1. From 10 sec. to 15 min. or constant.
2. Output follows input. Output follows
input 0 incl. Ain1 but only for inputs
where a text is entered. This set-up
excludes ”show connection/
disconnection”.
3. Output shows connection/
disconnection. Output shows
connection/disconnection on zone
0..3.
4. Disconnection in case of alarm.
Activate output in case of alarm
1234 Gx
x=1: 10 sec. =2: 20 sec., =3: 30 sec., =4: 1 min.,
=5: 2 min.., =6: 4 min., =7: 8 min., =8: 16 min.
=9: constant.
Sets relay-outputs to activate in case of alarm on
inputs.
Output follows input
1234 GA
Sets output to reflect position on inputs. Only
inputs with a text will reflect outputs. Alarm on
input 1 activates output 1. etc.
NB! If there is a text for both analog and digital
inputs, analog inputs have priority. This
command can not be applied together with
”shows connection/disconnection” 1234 QN
NB! “Send alarm only if a text is entered” must
be active 1234 CN or 1234 CT
No activation of outputs
1234 G0
Sets relay-outputs to not activate by alarm on
inputs.
Output reflect
connection/disconnection
1234 QN
Sets outputs to show position of zones. Output 0
will close when the unit is connected and break
when the unit is disconnected (default).
If there is no ”zone” entered in the set-up, only
output 0 will be activated.
If output 0 must be open when the unit is
connected send first 1234 S0
The same is actual for other outputs
S1;S2;S3.
Delete output reflect
connection/disconnection
1234 QF
Sets outputs to not show state of zones.
Set up macro
By a macro it is possible to gather one or more
commands in a ”super command” named after
your own choice. The macro can be activated by
the selected name in a SMS or with a telephone
call and DTMF. Max. 10 macros can be set up.
1234 Mx TEXT <command…>
x=0-9. Sets up a macro with the name TEXT
(max. 16 characters) and activates one or more
commands listed in <…> and separated by ;
Commands in macro:
Sx Closes output x
PS x Pauses in x sec.
Bx Breaks output x
xx Other commands
Example:
1234 M0 PULSE5 <S0;PS 5;B0>
Sets up macro nr. 0 with the name ”PULSE5”
which pulls output 0 for 5 sec.
Afterwards the macro can be activated by SMS:
1234 PULSE5 or with a call and DTMF:

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
18
1234
2 tones *60 (see the chap. ”Operating”).
Example:
1234 A0 SEND SIGNAL STRENGTH
<OK>
The command OK means that the unit will send
the current GSM signal strength to all receivers
when input 0 breaks. The receiver gets a SMS
with the signal strength in percent.
More commands must
be separated by a semicolon.
Commands start with < and ends with >
,e.g.: <S3;TP T 0001> (close
output 0 and send STATUS every 15
min.).
Record IR-code
You can record up to 10 infra red signals from a
remote control and transmits them by SMS or
DTMF.
1234 Mx NAME
1. Create a macro (x=0..9) with the name
NAME (max. 16 char.)
2. When the red diode flashes, point
remote control towards ”IR-ind” and
press the relevant function within 30 sec.
3. The diode lights shortly an blinks
hereafter normally. The code is stored.
Transmit IR-code
Connect the IR-transmitter (Profort: 009065) to
the AUX output.
1234 NAME
The IR-code stored under NAME is transmitted.
Transmission can also be activated by DTMF-call.
Call the unit, press 1234 (2 tones) *6x
(x=number on macro). Ref. to chapter
“Operation”.
Delete macro
1234 Mx
x=0-9. Deletes macro x.
6.4 SYSTEM MESSAGES AND ALARMS
The unit can be set up to send important system
messages and -alarms.
Send message on
connection/disconnection
SMS is sent to receivers in zone 0 on
connection/disconnection with information on ID
and which zones that are active or inactive
(+or -):
ON id ++++++++ or
OF id --------
1234 EN
Activates send message on connection/
disconnection.
1234 EF
Deactivates send message on connection/
disconnection.
Acknowledge command
The unit can return a command by means of
OK>> command for known command, and
??>> command for unknown command. The
command is returned to the receiver.
1234 KN
Activates return command.
Deactivate acknowledge command
1234 KF
Deactivates return command.
Send sabotage and power alarm when
the unit is disconnected
1234 YN
Activates the function.
1234 YF
Deactivates the function.
Send alarm immediately on power
failure
1234 JS

multiGuard® micro
Remote control and alarm via GSM
Setting up with SMS
-
Ver. 2.02
19
Sends alarm immediately in case of power
failure (after ca. 30 sec.) 9V rechargeable battery
must be installed.
1234 JF
Sets the unit to send alarm in case of power
failure after approx. 30 min. (default). 9V
rechargeable battery must be installed.
Send status message
1234 N0 99999999 yyyy
Sets the unit to automatically send status
message to all receivers. Requires that GSM-nr
(99999999) is known.
Every 15 minutes:
1234 TP T kkkk
Sends status message every 15 minutes
kkkk=number of 15 minutes. (kl. :00, :15, :30
and :45).
Every day:
1234 TP D ttmm
Sends status message every day at: tt:mm
Every week:
1234 TP W ttmm
Sends status message every week (Wednesday)
at: tt:mm
Deactivate send status message
1234 TP
Deactivate the function.
Set time in the unit
The clock-function is used for time registering in
the log, automatic connection/disconnection and
sending of status messages. There are 2 ways to
set the time:
1234 TM
Sets the time from the GSM-net in the unit.
1234 TM
yy/mm/dd,tt:mm:ss
Sets the time in the unit manually.
Delete time in the unit
1234 TF
Deletes time from the GSM-net in the unit.
Time controlled
connection/disconnection
Requires that the time is set in the unit.
1234 TI TTMM ttmm
Activates automatic timing of connection/
disconnection. The unit is connected with an
interval from TT:MM to tt:mm
Deactivate time controlled
connection/disconnection
1234 TI
Deactivates automatic timing of connection/
disconnection.
Text to and from serial port (RS232)
The unit can work as a modem and send/ receive
data from the serial port with the command
1234 TX (see the chap. Operating). In that
way the unit can be used for controlling
technical equipment, e.g. a PLC. The speed of
the data transmission is 9600 baud.
Receive text from PLC
If an ASCII-text sequence from a PLC ends with
CR+LF (max. 160 characters) the text will be
sent as SMS to all receivers in zone 0.
Send text to PLC
1234 TX TRANSFER THIS TEXT
a text sequence ”TRANSFER THIS TEXT” which
ends with CR+LF will be transferred with 9600
baud to e.g. a PLC on RS232.
Data communication with PLC
With a GSM-modem connected to a PC the unit
will be able to send and receive data from a PLC
when the call is made as ”data call”. Can be
used e.g. with the program Hyper Terminal.

multiGuard® micro
Remote control and alarm via GSM
Code summary
- Commands for set-up-
Ver. 2.02
20
6.5 COMMANDS FOR SET-UP
The code summary below joins all commands used for
setting up
the unit. These commands feeds the
unit with information about what to do in case of alarm on an input, for instance who is supposed to
receive the alarm.
With a password
Always start with the password of the unit (4 digits) followed by a space when sending commands to the
unit. Commands always have the following syntax: Password [space] + command (2 characters) [space] +
e.g. an additional text.
Without password
If the unit is set up to function without a password (set password to 0000) it is possible to start with the
command followed by an additional text. From a mobile phone, enter e.g. only S0 (in stead of 1234 S0) in
order to close relay-output 0.
Change password:
1234 N0 22222222 4488
Changes existing password of the unit. 22222222 is
the telephone number of the unit. 1234 is existing
password; 4488 is new password. Password must
be of 4 digits. If 0000 is entered as new password it
will not be necessary to enter the password in front
of the command.
Change ID-code:
1234 N0 22222222 4488 TEST Sets up ID-code for the unit. ID will automatically
be transmitted with alarms to the receiver.
If no ID-code is entered, the ID code will be the
same as the password. The ID-code, hier named
TEST can be numbers or letters.
The ID-code can be of max. 32 characters.
Set up receiver, SMS:
1234 N1 77777777
Sets up alarm receiver nr. 1 for zone 0 = N1. Max.
25 receivers can be entered. 77777777 is the
telephone number of the alarm receiver. Same
procedure for N1 to N9 and for NA to NP.
Notice:
The command for the first 9 receivers is N1 to
N9. Receiver 10 to 25 is NA, NB, NC etc.
up to NP.
Set up receiver, DTMF(dual tone multi frequency):
1234 N1 77777777 *
Sets up alarm receiver nr. 1 to zone 0 = N1. Max.
25 receivers can be set up. 77777777 is the
telephone number of the alarm receiver. Same
procedure for N1 to N9 and for NA to NP.
Notice:
The command for the first 9 receivers is N1 to
N9. Receiver 10 to 25 is NA, NB, NC etc.
up to NP.
Table of contents
Other MULTIGUARD Remote Control manuals