
Optical Smoke Detector, Model : DET-C631
Installation and Operation Manual
Page 3
5.3) After proper termination on all the detector bases is done, cap the Detector Head onto the Base using the
line marking at the side as a guideline to assist in positioning. Twist the Detector Head clockwise to secure
it onto the Base, and the second line marking of both the Detector Head and Base shall be aligned when
properly installed.
6) Troubleshooting
No Alarm when the Detectors are tested :-
6.1) Ensure that the Fire Alarm Panel is power up without any fault indications.
6.2) Check whether the Detector is securely installed onto the Base.
6.3) There should be 24VDC between terminals 1 and 5 at the Base. Otherwise, check the Zone output at the
Fire Alarm Panel and the wiring for open circuit.
Fault or False Alarm:
6.4) Check the LED on the detector whether it is in Alarm (Red), otherwise it may be due to a Panel problem.
6.5) Check the wiring for open or short circuit, and rectify if necessary.
6.6) Check whether the correct value of End-of –Line resistor is been used.
6.7) Check whether the Smoke Chamber is dusty, and needs to be cleaned or replaced.
6.8) May be caused by ambient conditions due to wrong detector positioning, such as to close to cooking
appliances, exhaust fume, or exposed to high air velocities from ventilation systems, and etc…
7) Caution
7.1) The Detectors installation and maintenance must be performed by qualified technical personnel.
7.2) Ensure that there is no obstruction within a perimeter of 0.5m around the detector.
7.3) The distance from the detector any Air Diffuser Outlet shall not be less than 1.5m.
7.4) The distance from the detector to any wall shall not be less than 0.5m.
7.5) The detector shall be installed horizontally. If it has to be installed slanted, the gradient angle should not
be more than 45o.
7.6) The Detector Alarm Status LED Indicator shall be easily visible, otherwise a Remote Status LED Indicator
shall be provided at a prominent location.
7.7) Ensure that Dust Covers, if any, are removed once the Fire Alarm System is commissioned.
7.8) Test and maintained the Fire Alarm System regularly to ensure that it is in proper operation condition.
7.9) Besides the above, installation of the detectors must be in compliance to the rules and regulation of the
Authority having jurisdiction, and the relevant Code-of-Practice.
Line aligned once
Detector is secured
Side View of the Detector
Use mark as guide to position
the Detector onto the Base
Position and twist the
Detector Head clockwise
to secure onto the Base