Murrelektronik MVP12 Series User manual

ENGLISH MANUAL
for devices of the MVP12 series
Art.-No. 59710 | 59718 | 59719 | 59810 | 59818 | 59819
© Murrelektronik GmbH

Murrelektronik GmbH
Falkenstraße 3
71570 Oppenweiler
GERMANY
Phone +49 7191 47-0
Fax +49 7191 47-491000
NOTE
Translation of the original instructions
This document applies to the following products:
Document status:
Name Art.-No.
MVP12-P6 DIO16 8xM12A IOLA12 B0 59719
MVP12-P6 DIO16 8xM12A IOLA12 E0 59819
MVP12-P6 DIO8 DIO8 8xM12A IOLB12 B0 59718
MVP12-P6 DIO8 DIO8 8xM12A IOLB12 E0 59818
MVP12-P6 DI16 8xM12A IOLA12 B0 59710
MVP12-P6 DI16 8xM12A IOLA12 E0 59810
Manual number 59719
Language EN
Version 1.2
Date 2021-09

ENGLISH MANUAL
for devices of the MVP12 series Art.-No. 59710 | 59718 | 59719 | 59810 | 59818 | 59819
3 / 65
Table of Contents
1 Introduction 6
1.1 Service and support 6
1.2 Scope of delivery 6
1.3 Applicable documents 7
1.4 Environmentally friendly disposal 7
1.5 About this manual 8
1.5.1 Symbols 8
1.5.2 Trademarks 9
1.5.3 Specifications 9
2 For your safety 10
2.1 General safety instructions 10
2.2 Intended purpose 10
2.2.1 Foreseeable misuse 10
2.2.2 Warranty and liability 10
3 Description 11
3.1 Product Designation Code 12
3.2 Module structure 14
3.3 Pin assignment 15
3.3.1 IO-Link Class A 15
3.3.2 IO-Link Class B 16
4 Technical Data 17
4.1 Art.-No. 59719 17
4.1.1 Electrical data 17
4.1.2 Environmental characteristics 18
4.1.3 Protection 19
4.1.4 Product reliability 19
4.1.5 Mechanical data 19
4.1.6 Conformity, Approvals 19
4.2 Art.-No. 59819 20
4.2.1 Electrical data 20
4.2.2 Environmental characteristics 21
4.2.3 Protection 21
4.2.4 Product reliability 22
4.2.5 Mechanical data 22
4.2.6 Conformity, Approvals 22
4.3 Art.-No. 59718 23
4.3.1 Electrical data 23
4.3.2 Environmental characteristics 24
4.3.3 Protection 25
4.3.4 Product reliability 25
4.3.5 Mechanical data 25
4.3.6 Conformity, Approvals 25

ENGLISH MANUAL
for devices of the MVP12 series Art.-No. 59710 | 59718 | 59719 | 59810 | 59818 | 59819
4 / 65
4.4 Art.-No. 59818 26
4.4.1 Electrical data 26
4.4.2 Environmental characteristics 27
4.4.3 Protection 28
4.4.4 Product reliability 28
4.4.5 Mechanical data 28
4.4.6 Conformity, Approvals 28
4.5 Art.-No. 59710 29
4.5.1 Electrical data 29
4.5.2 Environmental characteristics 30
4.5.3 Protection 30
4.5.4 Product reliability 30
4.5.5 Mechanical data 31
4.5.6 Conformity, Approvals 31
4.6 Art.-No. 59810 32
4.6.1 Electrical data 32
4.6.2 Environmental characteristics 33
4.6.3 Protection 33
4.6.4 Product reliability 33
4.6.5 Mechanical data 34
4.6.6 Conformity, Approvals 34
5 Mounting 35
5.1 Requirements 35
5.2 Dimensions 35
5.3 Mounting distance 36
5.4 Mounting the module 36
5.5 Functional ground 37
6 Installation 38
6.1 Connection lines 38
6.2 Ensure tight seal 39
7 Operation 40
7.1 LED indication 40
7.1.1 LED indication US and IO-Link 40
7.1.2 LED indication UA 41
7.1.3 LED indication for inputs and outputs 42
7.2 IO-Link object directory 42
7.2.1 DPP 42
7.2.1.1 Art.-No. 59719, 59819 42
7.2.1.2 Art.-No. 59718, 59818 44
7.2.1.3 Art.-No. 59710, 59810 46
7.2.2 ISDU 48
7.2.2.1 Art.-No. 59819 48
7.2.2.2 Art.-No. 59818 51
7.2.2.3 Art.-No. 59810 54

ENGLISH MANUAL
for devices of the MVP12 series Art.-No. 59710 | 59718 | 59719 | 59810 | 59818 | 59819
5 / 65
7.2.2.4 Mapping of configurations in pin-based mapping mode 56
7.3 Diagnostic 57
7.3.1 Vendor-specific IO-Link events 57
7.4 Process data 58
7.4.1 Port-Based Bitmapping 58
7.4.2 Pin-Based Bitmapping 60
8 Maintenance and cleaning 62
9 Appendix 63
9.1 Accessories 63
9.2 Tools 63
10 Legal notes 64

Introduction
User manual 59719_hdb_en_12 6 / 65
1 Introduction
Function of this
document
This document instructs the technical personnel of the machine manufacturer
or machine operator on the safe use of the devices described in the scope.
It does not instruct the safe use of the machine in which this Devices are or
will be integrated. Information on this is contained in the operating instructions
for the machine.
Read this chapter carefully before you start working with the documenta-
tion or the device.
Read the documentation carefully before starting up the device.
Store the manual in a place that is accessible to all users at all times for
the entire service life of the device.
You will need general knowledge about automation engineering in order to un-
derstand this manual. In addition, planning and using automation systems re-
quires technical knowledge which is not contained in this manual.
Glossary
You can find explanations of the terms/abbreviations used at:
https://www.murrelektronik.com/products-industries/glossary/
1.1 Service and support
Sales and distribution Our sales employees in the indoor and outdoor service and our technicians
will support you at any time.
Customer Service
Center (CSC)
Our staff of the Customer Service Center will help you with all questions con-
cerning installation and start-up. They support you, for example, if you have
problems with combining hardware and software products from different man-
ufacturers with Murrelektronik products.
A number of support tools and measurement facilities are available for field
bus systems and EMC interferences.
Please do not hesitate to call us at +49 (0) 7191 47-2050 or send an e-mail
to support@murrelektronik.com
Service addresses Murrelektronik GmbH has a policy of customer proximity, both at national and
international level. Please visit our website to find your contact person: https:/
/www.murrelektronik.com/
1.2 Scope of delivery
The scope of delivery includes:
1x MVP12 module
1x Operating instructions
10x Designation label

Introduction
User manual 59719_hdb_en_12 7 / 65
1.3 Applicable documents
The other applicable documents are included in the scope of delivery or can
be downloaded
from https://shop.murrelektronik.com
1.4 Environmentally friendly disposal
Comply
with country-specific
waste disposal regula-
tions!
Always dispose of scrap devices in compliance with the applicable coun-
try-specific regulations on waste disposal
(e.g., the European Waste Code 16 02 14).
Scrap materials may
only be sorted by quali-
fied
persons!
Proceed with caution when dismantling the device since you could injure
yourself.
Sort the separated components into the correct recycling line.
Disposal
The product can be returned to Murrelektronik GmbH free of charge for dis-
posal. The same is true for the original packaging and any batteries or power
packs. Any units that have been contaminated with hazardous substances
will not be accepted for repair or disposal.
Returns
Label the product and the packaging with
“For disposal”.
Package the product.
Send the package to:
Murrelektronik GmbH
Falkenstraße 3
71570 Oppenweiler / Germany
We will make sure that the items are disposed of in accordance with German
legislation. The most recent owner is responsible for transport to the return
point until items arrive at their destination.
Document Art. No.
Operating instructions 59719
Operating instructions 59710
Product data 59719
Product data 59819
Product data 59718
Product data 59818
Product data 59710
Product data 59810

Introduction
User manual 59719_hdb_en_12 8 / 65
1.5 About this manual
1.5.1 Symbols
This document includes information and notes that have to be observed for
your own safety and to avoid injuries and material damage. They are marked
as follows:
DANGER!
Immediate danger
Failure to observe this warning involves an imminent risk of death or seri-
ous injuries.
WARNING!
Possible danger
Failure to observe this warning can lead to death or serious injuries.
CAUTION!
Low-risk danger
Failure to observe this warning can lead to mild to moderate injuries.
NOTICE
Possible material damage
Failure to observe the warning may cause damage to the device and/or
the system.
NOTE
Other technical information and notes of Murrelektronik GmbH.
RECOMMENDATION
Notes with this symbol are recommendations of Murrelektronik GmbH.
PRODUCTS AND ACCESSORIES
This symbol indicates accessories or product recommendations.
Instruction for use An arrow marks instructions.
Read and observe the instructions.
1 | If they are numbered, it is absolutely necessary to follow them in the cor-
rect order.
2 | Read and observe the instructions.

Introduction
User manual 59719_hdb_en_12 9 / 65
1.5.2 Trademarks
Trademarks of the following companies and institutions are used in this docu-
mentation:
1.5.3 Specifications
The features of the IO-Link Specification version 1.1.3 are supported as well.
IO-Link c/o PROFIBUS Nutzerorganisation e.V. (PNO)
Specification Link
IO-Link specification
Version 1.1.2 dated 07/2013
http://www.io-link.com

For your safety
User manual 59719_hdb_en_12 10 / 65
2 For your safety
2.1 General safety instructions
Qualified personnel Only qualified and safety-trained personnel may assemble, commission and
operate the product.
This document is intended for specialists in automation technology.
NOTE
Interventions in the hardware and software of the device dare, if they are not
described in this document, only be carried out by qualified personnel from
Murrelektronik GmbH.
NOTE
The operating instructions must always be available to the operator of the ma-
chine where the device is used.
2.2 Intended purpose
The product has been designed and manufactured for:
industrial use
operation within the specified environmental conditions
field use.
NOTE
Radio interference may occur if the module is used in a domestic or mixed en-
vironment.
Follow standards for domestic or mixed environments!
2.2.1 Foreseeable misuse
Foreseeable
misuse
The module:
must not be altered with regard to design, engineering, or electrical fea-
tures.
should only be used in the application fields described in this manual,
in the technical data or in the operating instructions.
must not be used as a safety-related device. It does not meet the relevant
standards. Safety functions of the system are not
ensured.
should only be used in the respective IP-protected environment.
should only be cleaned with oil-free compressed air and a leather cloth.
must not be used as a climbing aid.
2.2.2 Warranty and liability
Warranty and liability claims cannot be made if
the product is not used according to its intended use
damage is caused due to non-observance of the
operating instructions
the personnel was/is not qualified

Description
User manual 59719_hdb_en_12 11 / 65
3 Description
Art.-No. 59719, 59819
Art.-No. 59718, 59818
Art.-No. 59710, 59810
IO-Link hub in 50 mm plastic housing
1 x M12 IO-Link class A
8 x M12 I/O
16 configurable digital inputs/outputs
IO-Link hub in 50 mm plastic housing
1 x M12 IO-Link class B
8 x M12 I/O
16 configurable digital inputs/outputs
Galvanically isolated voltage groups
IO-Link hub in 50 mm plastic housing
1 x M12 IO-Link class A
8 x M12 I/O
16 digital inputs

Description
User manual 59719_hdb_en_12 12 / 65
3.1 Product Designation Code
The product designation provides information on the module function.
Art.-No. 59719
Art.-No. 59819
Art.-No. 59718
Art.-No. 59818
MVP12-P6 DIO16 8xM12A IOLA12 B0
MVP12-P6 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM12A Number, size, and coding of the
ports
A = A coding
IOLA IOL = IO-Link
A = Class A
B0 Basic Firmware Features
MVP12-P6 DIO16 8xM12A IOLA12 E0
MVP12-P6 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM12A Number, size, and coding of the
ports
A = A coding
IOLA IOL = IO-Link
A = Class A
E0 Extended Firmware Features
MVP12-P6 DIO8 DIO8 8xM12A IOLB12 B0
MVP12-P6 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM12A Number, size, and coding of the
ports
IOLB IOL = IO-Link
B = Class B
B0 Basic Firmware Features
MVP12-P6 DIO8 DIO8 8xM12A IOLB12 E0
MVP12-P6 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM12A Number, size, and coding of the
ports
A = A coding
IOLB IOL = IO-Link
B = Class B
E0 Extended Firmware Features

Description
User manual 59719_hdb_en_12 13 / 65
Art.-No. 59710
Art.-No. 59810
MVP12-P6 DI16 8xM12A IOLA12 B0
MVP12-P6 Product family + module size
DI D = Digital
I = Input
8xM12A Number, size, and coding of the
ports
A = A coding
IOLA IOL = IO-Link
A = Class A
B0 Basic Firmware Features
MVP12-P6 DI16 8xM12A IOLA12 E0
MVP12-P6 Product family + module size
DI D = Digital
I = Input
8xM12A Number, size, and coding of the
ports
A = A coding
IOLA IOL = IO-Link
A = Class A
E0 Extended Firmware Features

Description
User manual 59719_hdb_en_12 14 / 65
3.2 Module structure
Fig. 3-1: Module structure and port designations
Art. No. Port designation Explanation
59719, 59819 X0 ... X7 Digital inputs and outputs US
XZ1 Module supply, IO-Link Class A
59718, 59818 X0 ... X3 Digital inputs and outputs UA
X4 ... X7 Digital inputs and outputs US
XZ1 Module supply, IO-Link Class B
59710, 59810 X0 ... X7 Digital inputs US
XZ1 Module supply, IO-Link Class A

Description
User manual 59719_hdb_en_12 15 / 65
3.3 Pin assignment
3.3.1 IO-Link Class A
Art.-No. 59719, 59819
Art.-No. 59710, 59810
IO-Link XZ1 (M12 male connectors)
Pin 1 24 V US (L+)
Pin 2 n.c.
Pin 3 0 V US (L-)
Pin 4 C/Q IO-Link
Pin 5 n.c.
DIO X0 ... X7 (M12 female connec-
tors)
Pin 1 24 V US
Pin 2 DIO US
Pin 3 0 V US
Pin 4 DIO US
Pin 5 FE
IO-Link XZ1 (M12 male connectors)
Pin 1 24 V US (L+)
Pin 2 n.c.
Pin 3 0 V US (L-)
Pin 4 C/Q IO-Link
Pin 5 n.c.
DI X0 ... X7 (M12 female connec-
tors)
Pin 1 24 V US
Pin 2 DI US
Pin 3 0 V US
Pin 4 DI US
Pin 5 FE

Description
User manual 59719_hdb_en_12 16 / 65
3.3.2 IO-Link Class B
Art.-No. 59718, 59818
IO-Link XZ1 (M12 male connectors)
Pin 1 24 V US (L+)
Pin 2 24 V UA (P24)
Pin 3 0 V US (L-)
Pin 4 C/Q IO-Link
Pin 5 0 V UA (N24)
DIO X0 ... X3 (M12 female connec-
tors)
Pin 1 24 V UA
Pin 2 DIO UA
Pin 3 0 V UA
Pin 4 DIO UA
Pin 5 FE
DIO X4 ... X7 (M12 female connec-
tors)
Pin 1 24 V US
Pin 2 DIO US
Pin 3 0 V US
Pin 4 DIO US
Pin 5 FE

Technical Data
User manual 59719_hdb_en_12 17 / 65
4 Technical Data
4.1 Art.-No. 59719
4.1.1 Electrical data
Total current US
Fig. 4-1: Total current US
Module supply
Operating voltage US 24 V
Operating voltage range US 18 ... 30 V
Total current US ≤50 °C (see Derating) ≤4 A
Power consumption when idling ≤40 mA
Galvanic isolation No
0
0,5
I [A]
1
2,5
1,5
2
-30 0T [°C]
-10 2010
3
30
-20 40 50 60 70
IO-Link
Communication speed COM3
Transfer rate 230,400 bit/s
Bus protocol IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time ≥1 ms
VendorID 0x012F
DeviceID 0x0C0009
Process data 2 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector M12
Operating voltage 24 V
Power supply Per port ≤0.5 A
Input (DI)
Connection/female connector M12
Cable cross section ≤0.75 mm²

Technical Data
User manual 59719_hdb_en_12 18 / 65
4.1.2 Environmental characteristics
Cable length ≤30 m
Input characteristic EN 61131-2 Type 1 + Type 3
Input filter 1ms
Input (DI)
Output (DO)
Connection/female connector M12
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Output current Per pin ≤0.5 A
Switching frequency Resistive load ≤25 Hz
Climatic
Operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Installation height Above sea level ≤3000 m
Relative humidity ≤95 %
Mechanical
Vibration test EN 60068 Parts 2-6 5 ... 500 Hz;
const. amplitude 1 mm;
acceleration 15 g
Shock test EN 60068 Parts 2-27 50 g @ 11 ms
Electrical safety
Degree of protection IP68
Protection class III
Degree of pollution 2
Emitted EMC interference
Radio interference field strength EN 61000-6-4 Emission QP: 40 dBμ V/m
@ 30 ... 230 MHzQP: 47
dBμ V/m
@ 230 ... 1000 MHz
EMC immunity
Electrostatic
discharge (housing)
EN 61000-4-2 ±4 kV @ contact
±8 kV @ air
Electromagnetic high-frequency fields
(housing)
EN 61000-4-3 RF field 10 V/m
Rapid transient electric disturbances
(burst)
DC inputs/outputs
EN 61000-4-4 ±2 kV I/O supply
±1 kV data line/
±1 kV I/O line
Magnetic field EN 61000-4-8 30 A/m @ 50 Hz
Conducted interferences,
high-frequency fields
EN 61000-4-6, asymmetric 10 V

Technical Data
User manual 59719_hdb_en_12 19 / 65
4.1.3 Protection
4.1.4 Product reliability
4.1.5 Mechanical data
4.1.6 Conformity, Approvals
Device protection
Overvoltage protection Yes
Overload protection of module supply To be ensured through load circuit monitoring Yes
Reverse polarity protection of module sup-
ply
Yes
Short-circuit protection, sensor supply Electronically
Short-circuit protection, output (DO) Electronically
Protective circuit for input Internal Suppressor diode
Product reliability
MTTF SN 29500 (at 40 °C and rated data) 57 years
Assembly data
Weight Net 200 g
Dimensions L x W x H 126 x 50 x 34.5 mm
Conformity, Approvals
Product standard EN 61131-2
Programmable logic controllers, Part 2
Compliant
CE 2014/30/EU
2011/65/EU
Compliant
UKCA Compliant
EMC 2014/30/EU Compliant
REACH No. 1907/2006 SVHC List
WEEE 2012/19/EU Compliant
ULus E201820
RoHS 2011/65/EU & 2015/863 Exception 6c&7a
China RoHS SJ/T 11364-2014 25 EPUP

Technical Data
User manual 59719_hdb_en_12 20 / 65
4.2 Art.-No. 59819
4.2.1 Electrical data
Total current US
Fig. 4-2: Total current US
Module supply
Operating voltage US 24 V
Operating voltage range US 18 ... 30 V
Total current US ≤50 °C (see Derating) ≤4 A
Power consumption when idling ≤40 mA
Galvanic isolation No
0
0,5
I [A]
1
2,5
1,5
2
-30 0T [°C]
-10 2010
3
30
-20 40 50 60 70
IO-Link
Communication speed COM3
Transfer rate 230,400 bit/s
Bus protocol IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time ≥1 ms
VendorID 0x012F
DeviceID 0x0C000A
Process data 4 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector M12
Operating voltage 24 V
Power supply Per port ≤0.5 A
Input (DI)
Connection/female connector M12
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Input characteristic EN 61131-2 Type 1 + Type 3
Input filter 1 ... 10 ms, adjustable
This manual suits for next models
12
Table of contents
Other Murrelektronik I/O System manuals

Murrelektronik
Murrelektronik MODLINK MSDD DBL COMBI INSERT User manual

Murrelektronik
Murrelektronik MVP8 Series User manual

Murrelektronik
Murrelektronik DATA PANEL xtremeDB DP-34044-3 User manual

Murrelektronik
Murrelektronik Data Panel xtremeDB xDB08-PVE User manual

Murrelektronik
Murrelektronik xtreme DB DP-34005-12 User manual

Murrelektronik
Murrelektronik CUBE20S User manual