Murrelektronik MVP8 Series User manual

ENGLISH MANUAL
for devices of the MVP8 series
Art.-No. 59504 | 59507 | 59604 | 59607
© Murrelektronik GmbH

Murrelektronik GmbH
Falkenstraße 3
71570 Oppenweiler
GERMANY
Phone +49 7191 47-0
Fax +49 7191 47-491000
NOTE
Translation of the original instructions
This document applies to the following products:
Document status:
Name Art.-No.
MVP8-P3 DIO8 8xM8-3 IOLA12 B0 59507
MVP8-P3 DIO8 8xM8-3 IOLA12 E0 59607
MVP8-P3 DIO4 DIO4 8xM8-3 IOLB12 B0 59504
MVP8-P3 DIO4 DIO4 8xM8-3 IOLB12 E0 59604
Manual number 59507
Language EN
Version 1.2
Date 2021-09

ENGLISH MANUAL
for devices of the MVP8 series Art.-No. 59504 | 59507 | 59604 | 59607
3 / 51
Table of Contents
1 Introduction 5
1.1 Service and support 5
1.2 Scope of delivery 5
1.3 Applicable documents 6
1.4 Environmentally friendly disposal 6
1.5 About this manual 7
1.5.1 Symbols 7
1.5.2 Trademarks 8
1.5.3 Specifications 8
2 For your safety 9
2.1 General safety instructions 9
2.2 Intended purpose 9
2.2.1 Foreseeable misuse 9
2.2.2 Warranty and liability 9
3 Description 10
3.1 Product Designation Code 11
3.2 Module structure 12
3.3 PIN assignment 13
3.3.1 IO-Link Class A 13
3.3.2 IO-Link Class B 13
4 Technical Data 14
4.1 Art.-No. 59507 14
4.1.1 Electrical data 14
4.1.2 Environmental characteristics 15
4.1.3 Protection 16
4.1.4 Product reliability 16
4.1.5 Mechanical data 16
4.1.6 Conformity, Approvals 16
4.2 Art.-No. 59607 17
4.2.1 Electrical data 17
4.2.2 Environmental characteristics 18
4.2.3 Protection 18
4.2.4 Product reliability 19
4.2.5 Mechanical data 19
4.2.6 Conformity, Approvals 19
4.3 Art.-No. 59504 20
4.3.1 Electrical data 20
4.3.2 Environmental characteristics 21
4.3.3 Protection 22
4.3.4 Product reliability 22
4.3.5 Mechanical data 22
4.3.6 Conformity, Approvals 22

ENGLISH MANUAL
for devices of the MVP8 series Art.-No. 59504 | 59507 | 59604 | 59607
4 / 51
4.4 Art.-No. 59604 23
4.4.1 Electrical data 23
4.4.2 Environmental characteristics 24
4.4.3 Protection 25
4.4.4 Product reliability 25
4.4.5 Mechanical data 25
4.4.6 Conformity, Approvals 25
5 Mounting 26
5.1 Requirements 26
5.2 Dimensions 26
5.3 Mounting distance 27
5.4 Mounting the module 27
5.5 Functional ground 29
6 Installation 30
6.1 Connection lines 30
6.1.1 Ensure tight seal 31
7 Operation 32
7.1 LED indication 32
7.1.1 LED indication US and IO-Link 32
7.1.2 LED indication UA 33
7.1.3 LED indication for inputs and outputs 34
7.2 IO-Link object directory 34
7.2.1 DPP 34
7.2.1.1 Art.-No. 59507, 59607 34
7.2.1.2 Art.-No. 59504, 59604 36
7.2.2 ISDU 38
7.2.2.1 Art.-No. 59607 38
7.2.2.2 Art.-No. 59604 39
7.3 Diagnostic 43
7.3.1 Vendor-specific IO-Link events 43
7.4 Process data 44
7.4.1 Port-Based Bitmapping 44
7.4.2 Pin-Based Bitmapping 46
8 Maintenance and cleaning 48
9 Appendix 49
9.1 Accessories 49
9.2 Tools 49
10 Legal notes 50

Introduction
User manual 59507_hdb_en_12 5 / 51
1 Introduction
Function of this
document
This document instructs the technical personnel of the machine manufacturer
or machine operator on the safe use of the devices described in the scope.
It does not instruct the safe use of the machine in which this Devices are or
will be integrated. Information on this is contained in the operating instructions
for the machine.
Read this chapter carefully before you start working with the documenta-
tion or the device.
Read the documentation carefully before starting up the device.
Store the manual in a place that is accessible to all users at all times for
the entire service life of the device.
You will need general knowledge about automation engineering in order to un-
derstand this manual. In addition, planning and using automation systems re-
quires technical knowledge which is not contained in this manual.
Glossary
You can find explanations of the terms/abbreviations used at:
https://www.murrelektronik.com/products-industries/glossary/
1.1 Service and support
Sales and distribution Our sales employees in the indoor and outdoor service and our technicians
will support you at any time.
Customer Service
Center (CSC)
Our staff of the Customer Service Center will help you with all questions con-
cerning installation and start-up. They support you, for example, if you have
problems with combining hardware and software products from different man-
ufacturers with Murrelektronik products.
A number of support tools and measurement facilities are available for field
bus systems and EMC interferences.
Please do not hesitate to call us at +49 (0) 7191 47-2050 or send an e-mail
to support@murrelektronik.com
Service addresses Murrelektronik GmbH has a policy of customer proximity, both at national and
international level. Please visit our website to find your contact person: https:/
/www.murrelektronik.com/
1.2 Scope of delivery
The scope of delivery includes:
1x MVP8 module
1x Operating instructions
10x Designation label

Introduction
User manual 59507_hdb_en_12 6 / 51
1.3 Applicable documents
You will find the applicable documents included in the scope of delivery or on-
line under https://shop.murrelektronik.com
1.4 Environmentally friendly disposal
Comply
with country-specific
waste disposal regula-
tions!
Always dispose of scrap devices in compliance with the applicable coun-
try-specific regulations on waste disposal
(e.g., the European Waste Code 16 02 14).
Scrap materials may
only be sorted by quali-
fied
persons!
Proceed with caution when dismantling the device since you could injure
yourself.
Sort the separated components into the correct recycling line.
Disposal
The product can be returned to Murrelektronik GmbH free of charge for dis-
posal. The same is true for the original packaging and any batteries or power
packs. Any units that have been contaminated with hazardous substances
will not be accepted for repair or disposal.
Returns
Label the product and the packaging with
“For disposal”.
Package the product.
Send the package to:
Murrelektronik GmbH
Falkenstraße 3
71570 Oppenweiler / Germany
We will make sure that the items are disposed of in accordance with German
legislation. The most recent owner is responsible for transport to the return
point until items arrive at their destination.
Document Art.-No.
Operating instructions 59507
Product Data 59507
Product Data 59607
Product Data 59504
Product Data 59604

Introduction
User manual 59507_hdb_en_12 7 / 51
1.5 About this manual
1.5.1 Symbols
This document includes information and notes that have to be observed for
your own safety and to avoid injuries and material damage. They are marked
as follows:
DANGER!
Immediate danger
Failure to observe this warning involves an imminent risk of death or seri-
ous injuries.
WARNING!
Possible danger
Failure to observe this warning can lead to death or serious injuries.
CAUTION!
Low-risk danger
Failure to observe this warning can lead to mild to moderate injuries.
NOTICE
Possible material damage
Failure to observe the warning may cause damage to the device and/or
the system.
NOTE
Other technical information and notes of Murrelektronik GmbH.
RECOMMENDATION
Notes with this symbol are recommendations of Murrelektronik GmbH.
PRODUCTS AND ACCESSORIES
This symbol indicates accessories or product recommendations.
Instruction for use An arrow marks instructions.
Read and observe the instructions.
1 | If they are numbered, it is absolutely necessary to follow them in the cor-
rect order.
2 | Read and observe the instructions.

Introduction
User manual 59507_hdb_en_12 8 / 51
1.5.2 Trademarks
Trademarks of the following companies and institutions are used in this docu-
mentation:
1.5.3 Specifications
The features of the IO-Link Specification version 1.1.3 are supported as well.
IO-Link c/o PROFIBUS Nutzerorganisation e.V. (PNO)
Specification Link
IO-Link specification
Version 1.1.2 dated 07/2013
http://www.io-link.com

For your safety
User manual 59507_hdb_en_12 9 / 51
2 For your safety
2.1 General safety instructions
Qualified personnel Only qualified and safety-trained personnel may assemble, commission and
operate the product.
This document is intended for specialists in automation technology.
NOTE
Interventions in the hardware and software of the device dare, if they are not
described in this document, only be carried out by qualified personnel from
Murrelektronik GmbH.
NOTE
The operating instructions must always be available to the operator of the ma-
chine where the device is used.
2.2 Intended purpose
The product has been designed and manufactured for:
industrial use
operation within the specified environmental conditions
field use.
NOTE
Radio interference may occur if the module is used in a domestic or mixed en-
vironment.
Follow standards for domestic or mixed environments!
2.2.1 Foreseeable misuse
Foreseeable
misuse
The module:
must not be altered with regard to design, engineering, or electrical fea-
tures.
should only be used in the application fields described in this manual,
in the technical data or in the operating instructions.
must not be used as a safety-related device. It does not meet the relevant
standards. Safety functions of the system are not
ensured.
should only be used in the respective IP-protected environment.
should only be cleaned with oil-free compressed air and a leather cloth.
must not be used as a climbing aid.
2.2.2 Warranty and liability
Warranty and liability claims cannot be made if
the product is not used according to its intended use
damage is caused due to non-observance of the
operating instructions
the personnel was/is not qualified

Description
User manual 59507_hdb_en_12 10 / 51
3 Description
Art.-No. 59507, 59607
Art.-No. 59504, 59604
IO-Link hub in 30 mm plastic housing
1 x M12 IO-Link class A
8 x M8 I/O
8 configurable digital inputs/outputs
IO-Link hub in 30 mm plastic housing
1 x M12 IO-Link class B
8 x M8 I/O
8 configurable digital inputs/outputs
Galvanically isolated voltage groups

Description
User manual 59507_hdb_en_12 11 / 51
3.1 Product Designation Code
The product designation provides information on the module function.
Art.-No. 59507
Art.-No. 59607
Art.-No. 59504
Art.-No. 59604
MVP8-P3 DIO8 8xM8-3 IOLA12 B0
MVP8-P3 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM8-3 Number and size of ports + number
of pins
IOLA IOL = IO-Link
A = Class A
B0 Basic Firmware Features
MVP8-P3 DIO8 8xM8-3 IOLA12 E0
MVP8-P3 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM8-3 Number and size of ports + number
of pins
IOLA IOL = IO-Link
A = Class A
E0 Extended Firmware Features
MVP8-P3 DIO4 DIO4 8xM8-3 IOLB12 B0
MVP8-P3 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM8-3 Number and size of ports + number
of pins
IOLB IOL = IO-Link
B = Class B
B0 Basic Firmware Features
MVP8-P3 DIO4 DIO4 8xM8-3 IOLB12 E0
MVP8-P3 Product family + module size
DIO D = Digital
I = Input
O = Output
8xM8-3 Number and size of ports + number
of pins
IOLB IOL = IO-Link
B = Class B
E0 Extended Firmware Features

Description
User manual 59507_hdb_en_12 12 / 51
3.2 Module structure
Fig. 3-1: Module structure and port designations
Art. No. Port designation Explanation
59507, 59607 X0 ... X7 Digital inputs and outputs US
XZ1 Module supply, IO-Link Class A
59504, 59604 X0 ... X3 Digital inputs and outputs UA
X4 ... X7 Digital inputs and outputs US
XZ1 Module supply, IO-Link Class B

Description
User manual 59507_hdb_en_12 13 / 51
3.3 PIN assignment
3.3.1 IO-Link Class A
3.3.2 IO-Link Class B
IO-Link XZ1 (M12 male connectors)
Pin 1 24 V US (L+)
Pin 2 n.c.
Pin 3 0 V US (L-)
Pin 4 C/Q IO-Link
Pin 5 n.c.
DIO X0 ... X7 (M8 female connectors)
Pin 1 24 V US
Pin 3 0 V US
Pin 4 DIO US
IO-Link XZ1 (M12 male connectors)
Pin 1 24 V US (L+)
Pin 2 24 V UA (P24)
Pin 3 0 V US (L-)
Pin 4 C/Q IO-Link
Pin 5 0 V UA (N24)
DIO X0 ... X3 (M8 female connectors)
Pin 1 24 V UA
Pin 3 0 V UA
Pin 4 DIO UA
DIO X4 ... X7 (M8 female connectors)
Pin 1 24 V US
Pin 3 0 V US
Pin 4 DIO US

Technical Data
User manual 59507_hdb_en_12 14 / 51
4 Technical Data
4.1 Art.-No. 59507
4.1.1 Electrical data
Total current US
Fig. 4-1: Total current US
Module supply
Operating voltage US 24 V
Operating voltage range US 18 ... 30 V
Total current US ≤50 °C (see Derating) ≤4 A
Power consumption when idling ≤40 mA
Galvanic isolation No
0
0,5
I [A]
1
2,5
1,5
2
-30 0T [°C]
-10 2010
3
30
-20 40 50 60 70
IO-Link
Communication speed COM3
Transfer rate 230,400 bit/s
Bus protocol IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time ≥1 ms
VendorID 0x012F
DeviceID 0x0C0005
Process data 2 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector M8
Operating voltage 24 V
Power supply Per 2 ports (X0+X1, X2+X3, X4+X5, X6+X7) ≤1 A
Input (DI)
Connection/female connector M8
Cable cross section ≤0.75 mm²

Technical Data
User manual 59507_hdb_en_12 15 / 51
4.1.2 Environmental characteristics
Cable length ≤30 m
Input characteristic EN 61131-2 Type 1 + Type 3
Input filter 1ms
Input (DI)
Output (DO)
Connection/female connector M8
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Output current Per pin ≤0.5 A
Switching frequency Resistive load ≤25 Hz
Climatic
Operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Installation height Above sea level ≤3000 m
Relative humidity ≤95 %
Mechanical
Vibration test EN 60068 Parts 2-6 5 ... 500 Hz;
const. amplitude 1 mm;
acceleration 15 g
Shock test EN 60068 Parts 2-27 50 g @ 11 ms
Electrical safety
Degree of protection IP68
Protection class III
Degree of pollution 2
Emitted EMC interference
Radio interference field strength EN 61000-6-4 Emission QP: 40 dBμ V/m
@ 30 ... 230 MHzQP: 47
dBμ V/m
@ 230 ... 1000 MHz
EMC immunity
Electrostatic
discharge (housing)
EN 61000-4-2 ±4 kV @ contact
±8 kV @ air
Electromagnetic high-frequency fields
(housing)
EN 61000-4-3 RF field 10 V/m
Rapid transient electric disturbances
(burst)
DC inputs/outputs
EN 61000-4-4 ±2 kV I/O supply
±1 kV data line/
±1 kV I/O line
Magnetic field EN 61000-4-8 30 A/m @ 50 Hz
Conducted interferences,
high-frequency fields
EN 61000-4-6, asymmetric 10 V

Technical Data
User manual 59507_hdb_en_12 16 / 51
4.1.3 Protection
4.1.4 Product reliability
4.1.5 Mechanical data
4.1.6 Conformity, Approvals
Device protection
Overvoltage protection Yes
Overload protection of module supply To be ensured through load circuit monitoring Yes
Reverse polarity protection of module sup-
ply
Yes
Short-circuit protection, sensor supply Electronically
Short-circuit protection, output (DO) Electronically
Protective circuit for input Internal Suppressor diode
Product reliability
MTTF SN 29500 (at 40 °C and rated data) 94 years
Assembly data
Weight Net 129 g
Dimensions L x W x H 126 x 30 x 34.5 mm
Conformity, Approvals
Product standard EN 61131-2
Programmable logic controllers, Part 2
Compliant
CE 2014/30/EU
2011/65/EU
Compliant
UKCA Compliant
EMC 2014/30/EU Compliant
REACH No. 1907/2006 SVHC List
WEEE 2012/19/EU Compliant
ULus E201820
RoHS 2011/65/EU & 2015/863 Exception 6c&7a
China RoHS SJ/T 11364-2014 25 EPUP

Technical Data
User manual 59507_hdb_en_12 17 / 51
4.2 Art.-No. 59607
4.2.1 Electrical data
Total current US
Fig. 4-2: Total current US
Module supply
Operating voltage US 24 V
Operating voltage range US 18 ... 30 V
Total current US ≤50 °C (see Derating) ≤4 A
Power consumption when idling ≤40 mA
Galvanic isolation No
0
0,5
I [A]
1
2,5
1,5
2
-30 0T [°C]
-10 2010
3
30
-20 40 50 60 70
IO-Link
Communication speed COM3
Transfer rate 230,400 bit/s
Bus protocol IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time ≥1 ms
VendorID 0x012F
DeviceID 0x0C0006
Process data 4 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector M8
Operating voltage 24 V
Power supply Per 2 ports (X0+X1, X2+X3, X4+X5, X6+X7) ≤1 A
Input (DI)
Connection/female connector M8
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Input characteristic EN 61131-2 Type 1 + Type 3
Input filter 1 ... 10 ms, adjustable

Technical Data
User manual 59507_hdb_en_12 18 / 51
4.2.2 Environmental characteristics
4.2.3 Protection
Output (DO)
Connection/female connector M8
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Output current Per pin ≤0.5 A
Switching frequency Resistive load ≤25 Hz
Climatic
Operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Installation height Above sea level ≤3000 m
Relative humidity ≤95 %
Mechanical
Vibration test EN 60068 Parts 2-6 5 ... 500 Hz;
const. amplitude 1 mm;
acceleration 15 g
Shock test EN 60068 Parts 2-27 50 g @ 11 ms
Electrical safety
Degree of protection IP68
Protection class III
Degree of pollution 2
Emitted EMC interference
Radio interference field strength EN 61000-6-4 Emission QP: 40 dBμ V/m
@ 30 ... 230 MHzQP: 47
dBμ V/m
@ 230 ... 1000 MHz
EMC immunity
Electrostatic
discharge (housing)
EN 61000-4-2 ±4 kV @ contact
±8 kV @ air
Electromagnetic high-frequency fields
(housing)
EN 61000-4-3 RF field 10 V/m
Rapid transient electric disturbances
(burst)
DC inputs/outputs
EN 61000-4-4 ±2 kV I/O supply
±1 kV data line/
±1 kV I/O line
Magnetic field EN 61000-4-8 30 A/m @ 50 Hz
Conducted interferences,
high-frequency fields
EN 61000-4-6, asymmetric 10 V
Device protection
Overvoltage protection Yes
Overload protection of module supply To be ensured through load circuit monitoring Yes
Reverse polarity protection of module sup-
ply
Yes
Short-circuit protection, sensor supply Electronically
Short-circuit protection, output (DO) Electronically
Protective circuit for input Internal Suppressor diode

Technical Data
User manual 59507_hdb_en_12 19 / 51
4.2.4 Product reliability
4.2.5 Mechanical data
4.2.6 Conformity, Approvals
Product reliability
MTTF SN 29500 (at 40 °C and rated data) 94 years
Assembly data
Weight Net 129 g
Dimensions L x W x H 126 x 30 x 34.5 mm
Conformity, Approvals
Product standard EN 61131-2
Programmable logic controllers, Part 2
Compliant
CE 2014/30/EU
2011/65/EU
Compliant
UKCA Compliant
EMC 2014/30/EU Compliant
REACH No. 1907/2006 SVHC List
WEEE 2012/19/EU Compliant
ULus E201820
RoHS 2011/65/EU & 2015/863 Exception 6c&7a
China RoHS SJ/T 11364-2014 25 EPUP

Technical Data
User manual 59507_hdb_en_12 20 / 51
4.3 Art.-No. 59504
4.3.1 Electrical data
Total current US and
total current UA
Fig. 4-3: Total current US and total current UA
Module supply
Operating voltage US 24 V
Operating voltage UA 24 V
Operating voltage range US 18 ... 30 V
Operating voltage range UA 18 ... 30 V
Total current US ≤50 °C (see Derating) ≤4 A
Total current UA ≤50 °C (see Derating) ≤4 A
Power consumption when idling ≤50 mA
Galvanic isolation Yes
0
0,5
I [A]
1
2,5
1,5
2
-30 0T [°C]
-10 2010
3
30
-20 40 50 60 70
IO-Link
Communication speed COM3
Transfer rate 230,400 bit/s
Bus protocol IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time ≥1 ms
VendorID 0x012F
DeviceID 0x0C0007
Process data 2 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector M8
Operating voltage 24 V
Power supply Per 2 ports (X0+X1, X2+X3, X4+X5, X6+X7) ≤1 A
Input (DI)
Connection/female connector M8
Cable cross section ≤0.75 mm²
This manual suits for next models
8
Table of contents
Other Murrelektronik I/O System manuals

Murrelektronik
Murrelektronik MVP12 Series User manual

Murrelektronik
Murrelektronik MODLINK MSDD DBL COMBI INSERT User manual

Murrelektronik
Murrelektronik DATA PANEL xtremeDB DP-34044-3 User manual

Murrelektronik
Murrelektronik xtreme DB DP-34005-12 User manual

Murrelektronik
Murrelektronik CUBE20S User manual

Murrelektronik
Murrelektronik Data Panel xtremeDB xDB08-PVE User manual