Nauxus NX-19IL-30 Assembly instructions

Professional Insert Liner
Installation Guide
and Users Manual
IMPORTANT:
Read and save these instructions.
NOTICE:
Installer: Leave this guide with the homeowner
Homeowner: Keep this guide for future reference
4XHVWLRQVSUREOHPVPLVVLQJSDUWV"%HIRUHUHWXUQLQJWRWKHVWRUH
FDOO1$8;86&XVWRPHU6HUYLFH
DPSP(670RQGD\)ULGD\
1$8;86&20
02'(/ 1;19IL/36/42/48/54/60


Important Safety Notice
Read all Instructions before Installing and operating this appliance
The installation in this manual is intended for qualied installers, service technicians or persons with•
similar qualied background. Installation and electrical wiring must be done by qualied profession-
als and in accordance with all applicable codes and standards, including re-rated construction.
DO NOT• attempt to install this appliance yourself. Injury could result from installing the unit due to
lack of appropriate electrical and technical background.
Range hood may have very sharp edges; please wear protective gloves if it is necessary to remove any•
parts for installing, cleaning or servicing.
Activating any switch ON before completing installation may cause ignition or an explosion.•
Due to the size and weight of this range hood, two people installation is recommended.•
To reduce the risk of re, electric shock, or injury to persons:
For general ventilating use only. • DO NOT use to exhaust hazardous or explosive materials and va-
pors.
The combustion air ow needed for safe operation of fuel-burning equipment may be affected by this•
unit’s operation. Follow the heating equipment manufacturer’s guideline and safety standards such
as those published by the National Fire Protection Association (NFPA), and the American Society of
Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
Before servicing or cleaning unit, switch power OFF at service panel and lock service panel to pre-•
vent power from being switched ON accidentally.
Clean grease laden surfaces frequently. To reduce the risk of re and to disperse air properly, make•
sure to vent air outside. DO NOT vent exhaust into spaces between walls, crawl spaces, ceiling, attics
or garages.
Ducted fans MUST always be vented to the outdoors.•
Use only metal ductwork and this unit MUST be grounded.•
Sufcient air is needed for proper combustion and exhausting of gases through the duct to prevent•
back drafting.
When cutting or drilling into wall or ceiling, be careful not to damage electrical wiring or other hid-•
den utilities.
All electrical wiring must be properly installed, insulated and grounded.•
Old duct work should be cleaned or replaced if necessary to avoid the possibility of a grease re.•
Check all joints on duct work to insure proper connection and all joints should be properly taped.•
Use this unit only in the manner intended by the manufacturer. If you have questions, contact the•
vendor.
To reduce the risk of a stove top grease re:
Keep all fan, bafe, spaces, lter, grease tunnel, oil container and grease-laden surfaces clean. Grease•
should not be allowed to accumulate on fan, bafe, spaces, lter, grease tunnel and oil container.
Always turn range hood ON when cooking at high heat or when cooking aming foods.•
Use high settings on cooking range only when necessary.•
Never leave surface units unattended at high settings. Boil overs cause smoking and greasy spillovers•
that may ignite. Heat oils slowly on low or medium settings. Page 1

$OOVDIHW\PHVVDJHVZLOOIROORZWKHVDIHW\DOHUWV\PERODQGWKHZRUG³:$51,1*´
The manufacturer and/or distributor/reseller declines all responsibility in the event of failure to ob-
serve the instructions given here for installation, maintenance and suitable use of the product.
The manufacturer and/or distributor/reseller further declines all responsibility for injury due to neg-
ligence and the warranty of the unit automatically expires due to improper maintenance.
The manufacturer and/or distributor/reseller will not be held responsible for any damages to personal
property or real estate or any bodily injuries whether caused directly or indirectly by the range hood.
,PSRUWDQW6DIHW\1RWLFH
5HDGDOO,QVWUXFWLRQVEHIRUH,QVWDOOLQJDQGRSHUDWLQJWKLVDSSOLDQFH
:$51,1*
<RXUVDIHW\DQGWKHVDIHW\RIRWKHUVLVYHU\LPSRUWDQW:HKDYHSURYLGHGPDQ\LPSRUWDQWVDIHW\PHV-
VDJHVLQWKLVPDQXDODQGRQ\RXUDSSOLDQFH$OZD\VUHDGDQGREH\DOOVDIHW\PHVVDJHV$OOVDIHW\PHV-
VDJHVZLOOWHOO\RXZKDWWKHSRWHQWLDOKD]DUGLVWHOO\RXKRZWRUHGXFHWKHFKDQFHRILQMXU\DQGWHOO\RX
what can happen if the instructions are not followed.
7KLVLVWKHVDIHW\DOHUWV\PERO7KLVV\PERODOHUWV\RXWRSRWHQWLDOKD]DUGVWKDWFDQKXUW\RXDQGRWKHUV
•&OHDQYHQWLODWLQJIDQIUHTXHQWO\
•$OZD\VXVHDSSURSULDWHFRRNZDUHDQGXWHQVLOVVL]H
•$OZD\VXVHFRRNZDUHDSSURSULDWHIRUWKHVL]HRIWKHVXUIDFHHOHPHQW
7RUHGXFHWKHULVNRILQMXU\WRSHUVRQVLQWKHHYHQWRIDVWRYHWRSJUHDVH¿UH
•6027+(5)/$0(6ZLWKDFORVH¿WWLQJOLGFRRNLHVKHHWRUPHWDOWUD\WKHQWXUQ2))WKHEXUQHU
%(&$5()8/7235(9(17%85161(9(53,&.83$)/$0,1*3$1²\RXPD\EHEXUQHG
.((3)/$00$%/(25&20%867,%/(0$7(5,$/$:$<)520)/$0(6,IWKHÀDPHV'2
127JRRXWLPPHGLDWHO\(9$&8$7($1'&$//7+(),5('(3$570(17RUGLDO\RXUORFDO
HPHUJHQF\VHUYLFHLPPHGLDWHO\
•'212786(:$7(5LQFOXGLQJZHWGLVKFORWKVRUWRZHOV²DYLROHQWVWHDPH[SORVLRQZLOOUHVXOW
•8VHDQH[WLQJXLVKHU21/<LI
•<RXNQRZ\RXKDYHD&ODVV$%&H[WLQJXLVKHUDQG\RXDOUHDG\NQRZKRZWRRSHUDWHLW
•7KH¿UHLVVPDOODQGFRQWDLQHGLQWKHDUHDZKHUHLWLVVWDUWHG
•7KH¿UHGHSDUWPHQWLVEHLQJFDOOHG
•<RXFDQ¿JKWWKH¿UHZLWK\RXUEDFNWRDQH[LW
7RUHGXFHWKHULVNRILQMXU\WRSHUVRQVLQWKHHYHQWRIDJDVOHDNV
•([WLQJXLVKDQ\RSHQÀDPH
•'2127WXUQRQWKHUDQJHKRRGIDQRUDQ\W\SHRIYHQWLODWRU
•'2127WXUQRQWKHOLJKWVRUDQ\W\SHRIDSSOLDQFH
•2SHQDOOGRRUVDQGZLQGRZVWRGLVSHUVHWKHJDV,I\RXVWLOOVPHOOJDVFDOOWKHJDVFRPSDQ\DQG¿UH
GHSDUWPHQWRUGLDO\RXUORFDOHPHUJHQF\VHUYLFHLPPHGLDWHO\
3DJH

Table of Contents
INSTALLATION
Tools needed....................................................3
Parts supplied...................................................4
Mount heights & clearance...............................5
Venting requirements.......................................6
Calculating vent system length.......................6
Venting methods..............................................7
Electrical requirements....................................8
Preparation......................................................9
Installation................................................10-11
Range hood operations..................................12
USE AND CARE
Troubleshooting...........................................13
Use and care information...............................14
Specications..............................................14
Measurement & wiring diagram...............15-19
MAINTENANCE Cleaning.........................20
Replacing the lter & light bulb.............20-21
WARRANTY Coverage & exception............22
Disclaimer & Contact Us...............................23
Tools needed:
Page 3
Level
Flat-blade
and Phillips
screwdrivers
Powered
screwdriver
or drill
Measuring
tape
Utility knife
Marker or
pencil

Parts supplied:
30"& 36": 2PCS 2PCS 6PCS 6PCS 6PCS
42"& 48": 4PCS 4PCS 9PCS 8PCS 6PCS
54" & 60":
Baffle Filter Baffle Filter Filler Grease Tunnel
Professional Insert Liner
Range Hood Mounting Bracket
(For 42"/ 48"/54"/60" use)
Range Hood Mounting Bracket
(For 30"&36" use)
Page 4

Page 5
IMPORTANT:
Vent system must terminate to the outside (roof or side wall).•
DO NOT terminate the vent system in an attic or other enclosed area.•
DO NOT use 4” (10.2 cm) laundry-type wall caps.•
Use metal/aluminum vent only. Rigid metal/aluminum vent is recommended.•
DO NOT use plastic vent.•
Always keep the duct clean to ensure proper airow.•
Calculate the following gures before installation:•
Distance between the oor to the countertop/stove.1.
Distance between the countertop/stove to the range hood (recommend* 30” to 36”).2.
Height of hood and duct cover/cabinet.3.
For the most efcient & quiet operation:
A distance of 30” to 36” is recommended* between stove top and the bottom of range hood.•
It is important to install the hood at the proper mounting height. Hoods mounted too low could result•
in heat damage and re hazard; while hoods mounted too high will be hard to reach and will loose its
performance and efciency.
It is recommended that the range hood be vented vertically through the roof through 8” (20.3 cm) or bigger round•
metal/aluminum vent work.
Always use rigid type metal/aluminum ducts if available to maximize airow when connecting to pro-•
vided duct.
The size of the vent should be uniform.•
Insert Liners Typical Installation:
Insert Liner
Width
30” to 36”
Hood to
Cooking Surface
Wood Hood Insert Liner
Round Duct
Wood Hood
Insert Liner
Transition
Mounting
Bracket
Grease
Tunnel Filter
Mount Heights & Clearance

For the most efcient & quiet operation:
ALWAYS, when possible, reduce the number or transitions and turns. If long duct run is required, increase•
duct size from 8” to 10” or bigger size duct. If a reducer is used, install a long reducer instead of a pancake
reducer. Reducing duct size will restrict airow and decrease airow, thus reduce duct size as far away from
opening as possible.
Use no more than three 90° elbows.•
Make sure there is a minimum of 24” (61 cm) of straight vent between the elbows if more than one elbow is used.•
DO NOT install two elbows together.•
The length of vent system and number of elbows should be kept to a minimum to provide efcient performance.•
The vent system must have a damper. If roof or wall cap has a damper, DO NOT use damper (if supplied) on top of the•
range hood.
Use silver tape or duct tape to seal all joints in the vent system.•
Use caulking to seal exterior wall or roof opening around the cap. • Please use Duct Run Calculation below to com-
pute total available duct run when using elbows, transitions and caps.
If turns or transitions are required: Install as far away from opening and as far apart, between 2, as possible.•
If available, also refer to stove top manufacturer’s height clearance requirements and recommended hood•
mounting height above range.
* Due to different ceiling height congurations, recommended height may not be applicable.
Minimum Duct Size:
Round - 6” or 8”•
Duct Run Calculation:
Recommended maximum run
8” or 3-1/4 x 10” duct 50 ft
Vent piece deduction
Each 90º elbow used 9 ft
Each 45º elbow used 5 ft
Each 8” to 3 1/4 x 10” transition used 7 ft
Side wall cap with damper 0 ft
Roof cap 0 ft
Duct Run Calcuation example:
One roof cap, two 90º elbow, and one 45º elbow used:
0ft + 9ft + 9ft + 5ft = 23ft used.
Deduct 23ft from 50ft, 27ft maximum available for
straight duct run.
Calculating Vent System Length
To calculate the length of the system you need, deduct the equivalent feet for each vent piece used in the system
from the recommended maximum duct run.
Venting Requirements
Page 6

Page 7
Venting Methods
This range hood is factory set for venting through the roof or wall.•
Vent work can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.•
IMPORTANT:
NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or•
garages. All exhaust must be ducted to the outside.
Use metal/aluminum duct work only.•
Fasten all connections with sheet metal screws and tape all joints with certied Silver Tape or Duct Tape.•
Use caulking to seal exterior wall or roof opening around the cap.•
Vertical roof venting
Roof cap
Option 2:
Side wall cap
Horizontal wall venting
Option 1:

Electrical Requirements
IMPORTANT: Observe all governing codes and ordinances.
(Please consult with a qualied electrician for 220-Volt 50 Hz voltage)
It is the customer’s responsibility:
To contact a qualied electrical installer.•
To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/•
NFPA 70 — latest edition*, or CSA Standards C22. 1-94, Canadian Electrical Code, Part 1 and C22. 2 No.
0-M91 - latest edition** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician determine that
the ground path is adequate.
A 120-Volt, 60 Hz, AC-only (USA & Canada standard), fused electrical supply is required on a separate 15-amp
circuit, fused on both sides of the line.
DO NOT ground to a gas pipe.
Check with a qualied electrician if you are not sure that the range hood is properly grounded.
DO NOT have a fuse in the neutral or ground circuit.
IMPORTANT: Save this Installation Guide for electrical inspector’s use.
The range hood must be connected with copper wire/plug only.
The range hood should be connected directly to the fused disconnect (or circuit breaker) box through exible
armored or non-metallic sheathed copper cable. A U.L. - or C.S.A. - listed strain relief must be provided at each
end of the power supply cable.
Wire sizes (copper wire only) and connections must conform with the rating of the appliance as specied on
the model/serial rating label. Wire sizes must conform to the requirements of the National Electrical Code
ANSI/NFPA 70 — latest edition*, or CSA Standards C22. 1-94, Canadian Electrical Code Part 1 and C22.
2 No. 0-M91 - latest edition** and all local codes and ordinances. A U.L. - or C.S.A. - listed conduit con-
nector must be provided at each end of the power supply cable (at the range hood and at the junction box).
Copies of the standards listed may be obtained from:
* National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
** CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
Page 8

Page 9
Preparation
WARNING
Severe Injury
Rotating fan can cause severe
injury. Stay clear of fan when
motor is running.
WARNING
Excessive Weight
Require three or more person to move and
install this range hood. Spinal or other bodi-
ly injuries could occur if it is not followed.
Advanced Preparations:
Be familiar with the controls of the range hood by reading1.
through Range Hood Operations,Page 12.
Place the range hood on a at, stable surface. Connect the2.
range hood to a designated standard outlet (please refer the
product label for the suitable voltage of this unit) and turn on
the range hood. Verify all operations of the range hood by
referring to Range Hood Operations, Page 12.
Place all supplied parts and required hardware on a at, stable surface and3.
verify the existence of all supplied parts listed on Page 4.
Carefully remove the white plastic protective coat from the chimney covers4.
and range hood.
Preparations:
NOTE: To avoid damage to your hood, prevent debris from entering the vent opening.
Decide the location of the venting pipe from the hood to the outside. Refer to1. Venting Methods on Page 7.
Due to the weight and size of this unit, please make sure that the wood hood or framework being used is stable2.
and secure in the wall. A straight, short vent run will allow the hood to perform more efciently.
Try to avoid as many transitions, elbows, and long run as possible. This may reduce the performance of the3.
hood.
IMPORTANT: Peel white plastic protective coat off the hood, if any.4.
Use silver tape or duct tape to seal joints between pipe sections.5.
Put a thick, protective covering over counter top, cook top or range to protect from damage or dirt. Remove6.
any hazardous objects around the area when installing.
CAUTION: If moving the cooking range is necessary to install the hood, turn OFF the power on an elec-
tric range at the main electrical box. SHUT OFF THE GAS BEFORE MOVING A GAS RANGE.
The hood assembly is equipped with the standard 8” round vent.7.
If venting to the outside install vent system (see 8. Venting Requirements, Page 6). Use caulking to seal exterior
wall or roof openings.
Disconnect main electrical supply, prepare and run electrical wiring through ceiling or wall. Leave approxi-9.
mately 12” of electrical cord hanging from the ceiling. Do not restore power until wiring is completed.
Disconnect power cord, remove the bufe lters and the grease tunnel. Refer to installation step 9 & 10.10.
Reinstall the bafe lters and the grease tunnel after the range hood is properly installed.11.

Installations (refer to Page 4 for parts):
Measure the distance between stove top and the bottom of
range hood. A distance of 30” to 36” is recommended*.
*Due to different ceiling height congurations, recommend-
ed height may not be applicable.
Installation of Metal Liner Inserts
If the optional trim kit is used it must be installed prior to mounting the Metal Hood Liner into the wood deco-1.
rative hood. Use the provided #8 Phillips head screws. See Figure 1.
Lift the Metal Hood Liner into the decorative hood structure. Due to the weight of the assembly three people2.
may be required for proper installation.
Install #6 x 1/2” screws through the pre-drilled EZ mount holes into the decorative hood structure. Tap chrome3.
cap into EZ mount holes for ush appearance See Figure 2.
Additional mounting fasteners may be used to secure to the back wall and top (from inside).4.
CAUTION: Make certain the range hood is secure before releasing!
For safety purpose, pre-drilled mounting holes are provided through the back of the hood. For a more secure5.
installation, use as many mounting holes as needed to secure from the inside of hood.
Use 8” round steel pipe (follow building codes in your area) to connect the exhaust on the hood to the duct-6.
work above. Use silver tape or duct tape to make all joints secure and air tight. Refer to Figure 3.
SAFETY WARNING: Risk of electrical shock. this range hood must be properly grounded. Make sure this
is done by qualied electrician in accordance with all applicable national and local electrical codes. Before
connecting wires, switch power off at service panel and lock service panel to prevent power from being
switched on accidentally.
Connect the range hood to a designated standard outlet or cut off the plug and connect three wires (black,7.
white and green) to house wires and cap with wire connectors. Connect according to colors (i.e. black to
black, white to white, and green to green) as shown in Figure 4.
Store excess wires in the wiring box.8.
Drop oil tunnel into recess support near rear of hood. Refer to Figure 5.9.
Installation
Figure 2
Wood Hood
Mounting Holes
Figure 1
Screew
Trim Kit
Page 10

Installation (Continued)
To install bafe lters and stainless spacer(s), refer to 10. Bafe Filters and Stainless Steel Spacers on Page 23 for bafe
lter and stainless spacer placement. Refer to Figure 6 for the following ve steps:
Angle bafe lter toward back of hood.
Push bafe lter up until almost level.
Slide forward into recess behind the front of hood.
Lower bafe lter.
Slide back until it ts into resting positions.
Repeat Step 8 to install all bafe lters and stainless spacers.11.
OPTIONAL: Install heating lamps (not included) last. 220V or 120V (for USA & Canada), 250-Watt12.
maximum per lamp.
Turn powe ON in control panel. Check all lights and fan operations.13.
Make sure to leave this Installation Guide for the homeowner.14.
Figure 3
Figure 4
Figure 5
Page 11
Figure 6

This range hood is designed to remove smoke, cooking vapors and odors from the cook top area. For best results,
start the range hood before cooking and allow it to operate several minutes after the cooking is completed to clear
all smoke and odors from the kitchen.
Button functions:•
Power: Power ON/OFF the range hood and activate power-off delay timer.
Decrease Value: Blower (motor) speed decrease, timer value decrease, and enter timer mode.
Increase Value: Blower (motor) speed increase, timer value increase, and cleaning reminder reset.
Light: Turns ON/OFF and dim halogen lights.
Power-Off Delay Digital Timer: Indicates the length of time left for delay off function.
•
•
•
• Blower Speed Indicator: Shows current blower (motor) speed (1-4).
•
•
Controls:•
Automatic cleaning reminder:•
This range hood is equipped with a cleaning reminder that will activate following 30 hours of use.•
When blower (motor) starts to rotate, cumulative running time reached 30 hours then the Cleaning
Reminder Indicator “C” flashes and reminds user to clean the aluminum filter.
After cleaning the filter and when the motor is not in use, press and hold •Increase Value button over 3
seconds to reset the timer. Please note that turning off the system will not reset the Power-On Elapsed
Timer.
Adjusting the blower (motor) speed:•
• Press Power button once to turn on the system. The Blower Speed Indicator shows the blower (mo-
tor) speed level. Decrease Value button will decrease the speed of the blower (motor) from 4to 1
(strongest to quietest). Increase Value button will increase the speed of the blower (motor) from 1 to
4(quietest to strongest).
5DQJH+RRG2SHUDWLRQV
4Speed Electronic Touch Control
Power
Power-Off Delay
Decrease Value
Light
Increase Value
Blower Speed Indicator
Power-Off Delay Digital Timer
Cleaning Reminder Indicator
• Press Power button once to turn off the system.
Note: The system saves user configurations, settings such as light, timer and blower (motor) speed will re-
main the same the next time it is turned on.
Page 12

Page 13
Controls:•
Adjusting the timer function:•
While the blower (motor) is not running, press and hold• Decrease Value button over 3 seconds to
enter timer mode. Adjust to desired period of delay off timer by pressing Increase Value or Decrease
Value button (minimum 1 minute to maximum 9 minutes). This setting will be saved immediately.
Activating the timer function:•
While the blower (motor) is running, press and hold• Power button for over 3 seconds to activate
delay off timer. Power-Off Delay Digital Timer begin to countdown, when it reaches zero, the blower
(motor) will shut down.
Adjusting the light:•
Press• Light button once to turn on the lights, and once again to turn off the lights.
CAUTION: DO NOT touch the lights until switched OFF and cooled.
• While the lights are on, press and hold Light button for over 3 seconds to dim the lights from high to
low. Level of brightness will be stored in system’s memory.
Note: Light settings are independent from other settings (including power-off delay) and lights has to be
manually turned on or off.
Note: The system saves user configurations, settings such as light, timer and blower (motor) speed will re-
main the same the next time it is turned on.
5DQJH+RRG2SHUDWLRQV&RQWLQXHG
4Speed Electronic Touch Control
Power
Power-Off Delay
Decrease Value
Light
Increase Value
Blower Speed Indicator
Power-Off Delay Digital Timer
Cleaning Reminder Indicator

Troubleshooting
If the range hood or halogen light does not operate1.
after installation:
Check if the range hood has been plugged in, make•
sure that all power has been turned back ON, fused
not blown and all electrical wiring are properly con-
nected.
The range hood vibrates when the blower is on:
• Swap out light assembly to working ones to deter-
mine whether it is caused by defective bulbs. See
Replacing the light bulbs on Page 22.
2. The range hood might not have been secured prop-•
erly on to the ceiling or wall.
The blower or fan seems weak:3. Check that the duct sized used is at least 8” or 3-1/4•
x 10”. Range hood WILL NOT function efciently
with insufcient duct size. For example: 10” duct
over 8” hole and loosely secured.
Check if duct is clogged or if damper unit (half-cir-•
cular apper) is not installed correctly or opening
properly. A tight mesh on a side wall cap unit might
also cause restriction to the air ow.
The lights work but the blower is not spinning at all,4.
is stuck or is rattling.
The blower might be jammed or scraping the bot-•
tom due to shipping damage. Please contact us im-
mediately.
The hood is not venting out properly:5. Make sure the distance between the stove top and•
the bottom of the hood is within* 30” and 36” in
distance. *Due to different ceiling height congura-
tions, recommended height may not be applicable.
Reduce the number of elbows and length of duct•
work. Check if all joints are properly connected,
sealed, and taped.
Make sure the power is on high speed for heavy•
cooking.
NOTE: For all other inquiries, please contact us. Our contact information can be found on the back cover page.
Page 14

Page 15
Use and Care Information
Operations:
Read and understand all instructions and warnings in this manual before operating the appliance. Save these•
instructions for future reference.
Always leave safety grills and filters in place. Without these components, operating blowers could catch on to•
hair, fingers and loose clothing.
NEVER dispose cigarette ashes, ignitable substances, or any foreign objects into blowers.•
NEVER leave cooking unattended. When frying, oil in the pan can easily overheat and catch fire. The risk of•
self combustion is higher when the oil has been used several times.
NEVER cook on “open” flames under the range hood. Check deep-fryers during use: Superheated oil may be•
flammable.
Cleaning:
The saturation of greasy residue in the blower and filters may cause increased inflammability. Keep unit clean•
and free of grease and residue build-up at all times to prevent possible fires.
Filters must be cleaned periodically and free from accumulation of cooking residue (see• cleaning instructions
on Page 18). Old and worn filters must be replaced immediately.
DO NOT operate blowers when filters are removed. Never disassemble parts to clean without proper instruc-•
tions. Disassembly is recommended to be performed by qualified personnel only. Read and understand all
instructions and warnings in this manual before proceeding.
Specifications
1. In House Test Static Pressure “0”.
2. One sone is roughly equivalent to the sound of a refrigerator (1kHz) at 40 decibels.
3. Subject to change without notice, please contact your local reseller for details.
Specifications :
Body Design Seamless Stainless Steel, Satin Finish
Power Rating 120V/60Hz (USA & Canada standard)
General Input Power
30"&36":126W / 42” & 48”: 249W/ 54"&60": 252W
Motor Input Power
30"&36": 120W / 42", 48",54"&60": 240W (120W + 120W)
Ampere 3 A
Levels Of Speed Control 4 Levels
Max. Airflow
30"& 36": 600CFM / 42", 48",54"& 60": 1000CFM
Max. Noise Level
30"& 36": 6.5Sone(67dB)/ 42", 48",54"& 60": 7.5Sone(69dB)
Number Of Motors
Motor T
30"& 36": Single Motor / 42", 48",54"& 60": Dual Motors
ype
Fan T
Single Chamber Ultra Quiet
ype Centrifugal Squirrel Cage
Control Type Electronic Control Panel
Filtration Type Stainless Steel Baffle Filter
Illumination LED 3W 12V
Venting Size
Top, 30"& 36" 6 Inches Round; 42"-60” 8 inches Round
Interference Protection Radio Frequency Interference Protected

All measurements in parenthesis are in millimeter.•
All inch measurements are converted from millimeters, thus inch measurements are estimated.•
Professional Insert Liner
Measurements & Wiring Diagram
Page 16
NX-19IL-42/48
NX-19IL-30/36

Page 17
Measurements & Wiring Diagram (Continued)
Wiring Diagram (4 Speed)
NX-19IL-30/36
NX-19IL-54/60

Range Hood Assembly:
No. Description Quantity
1Hood-Mounting Bracket 2
2Hood Body 1
3 Light Vary with size
4Control Switch 1
5 Oil Tunnel 1
6 Blower Assembly (Motor, Fan Blade, Protective Grill and Squirrel Cage) 1
7 Electrical Assembly 1
8 Stainless Steel Spacer Vary with size
9Bafe Filter Vary with size
10 Power Cord 1
Measurements & Wiring Diagram (Continued)
11 Ducting Transition 1(Only 30"&36" use)
Page 18
NX-19IL-42/48/54/60
This manual suits for next models
5
Table of contents
Other Nauxus Ventilation Hood manuals