NetApp AAF A700 User manual

Chassis
ONTAP Systems
NetApp
November 23, 2021
This PDF was generated from https://docs.netapp.com/us-en/ontap-systems/fas9000/chassis-replace-
overview.html on November 23, 2021. Always check docs.netapp.com for the latest.

Table of Contents
Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê1
Replace the chassis - AFF A700 and FAS9000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê1
Shut down the controllers - AFF A700 and FAS9000. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê1
Move and replace hardware - AFF A700 and FAS9000. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ê4
Complete the restoration and replacement process - AFF A700 and FAS9000 . . . . . . . . . . . . . . . . . . . . . . Ê12

Chassis
Replace the chassis - AFF A700 and FAS9000
All other components in the system must be functioning properly; if not, you must contact
technical support.
•You can use this procedure with all versions of ONTAP supported by your system.
•This procedure is disruptive. For a two-node cluster, you will have a complete service outage and a partial
outage in a multi-node cluster.
Shut down the controllers - AFF A700 and FAS9000
Option 1: Shut down the controllers
You must shut down the node or nodes in the chassis prior to moving them to the new
chassis.
About this task
•If you have a cluster with more than two nodes, it must be in quorum. If the cluster is not in quorum or a
healthy node shows false for eligibility and health, you must correct the issue before shutting down the
impaired node; see the Administration overview with the CLI.
•If AutoSupport is enabled, suppress automatic case creation by invoking an AutoSupport message:
system node autosupport invoke -node * -type all -message
MAINT=number_of_hours_downh
The following AutoSupport message suppresses automatic case creation for two hours: cluster1:*>
system node autosupport invoke -node * -type all -message MAINT=2h
Steps
1. If your system has two controller modules, disable the HA pair.
If your system is running
clustered ONTAP with…
Then…
Two nodes in the cluster cluster ha modify -configured false storage failover
modify -node node0 -enabled false
More than two nodes in the
cluster
storage failover modify -node node0 -enabled false
2. Halt the node, pressing ywhen you are prompted to confirm the halt: system node halt -node
node_name
The confirmation message looks like the following:
1

Warning: Rebooting or halting node
"node_name" in an HA-enabled cluster may result in client disruption or
data access
failure. To ensure continuity of service, use the "storage
failover takeover" command. Are you sure you want to halt node
"node_name"? {y|n}:
You must perform a clean system shutdown before replacing the chassis to avoid losing
unwritten data in the nonvolatile memory (NVMEM). If the NVMEM LED is flashing, there is
content in the NVMEM that has not been saved to disk. You need to reboot the node and
start from the beginning of this procedure. If repeated attempts to cleanly shut down the
node fail, be aware that you might lose any data that was not saved to disk.
3. Where applicable, halt the second node to avoid a possible quorum error message in an HA pair
configuration: system node halt -node second_node_name -ignore-quorum-warnings true
Option 2: Shut down a node in a two-node MetroCluster configuration
To shut down the impaired node, you must determine the status of the node and, if
necessary, switch over the node so that the healthy node continues to serve data from
the impaired node storage.
About this task
•If you are using NetApp Storage Encryption, you must have reset the MSID using the instructions in the
"Returning SEDs to unprotected mode" section of Administration overview with the CLI.
•You must leave the power supplies turned on at the end of this procedure to provide power to the healthy
node.
Steps
1. Check the MetroCluster status to determine whether the impaired node has automatically switched over to
the healthy node: metrocluster show
2. Depending on whether an automatic switchover has occurred, proceed according to the following table:
If the impaired node… Then…
Has automatically switched over Proceed to the next step.
Has not automatically switched
over
Perform a planned switchover operation from the healthy node:
metrocluster switchover
Has not automatically switched
over, you attempted switchover
with the metrocluster
switchover command, and the
switchover was vetoed
Review the veto messages and, if possible, resolve the issue and try
again. If you are unable to resolve the issue, contact technical
support.
3. Resynchronize the data aggregates by running the metrocluster heal -phase aggregates
2

command from the surviving cluster.
controller_A_1::> metrocluster heal -phase aggregates
[Job 130] Job succeeded: Heal Aggregates is successful.
If the healing is vetoed, you have the option of reissuing the metrocluster heal command with the
-override-vetoes parameter. If you use this optional parameter, the system overrides any soft vetoes that
prevent the healing operation.
4. Verify that the operation has been completed by using the metrocluster operation show command.
controller_A_1::> metrocluster operation show
Ê Operation: heal-aggregates
Ê State: successful
Start Time: 7/25/2016 18:45:55
Ê End Time: 7/25/2016 18:45:56
Ê Errors: -
5. Check the state of the aggregates by using the storage aggregate show command.
controller_A_1::> storage aggregate show
Aggregate Size Available Used% State #Vols Nodes RAID
Status
--------- -------- --------- ----- ------- ------ ----------------
------------
...
aggr_b2 227.1GB 227.1GB 0% online 0 mcc1-a2
raid_dp, mirrored, normal...
6. Heal the root aggregates by using the metrocluster heal -phase root-aggregates command.
mcc1A::> metrocluster heal -phase root-aggregates
[Job 137] Job succeeded: Heal Root Aggregates is successful
If the healing is vetoed, you have the option of reissuing the metrocluster heal command with the
-override-vetoes parameter. If you use this optional parameter, the system overrides any soft vetoes that
prevent the healing operation.
7. Verify that the heal operation is complete by using the metrocluster operation show command on
the destination cluster:
3

mcc1A::> metrocluster operation show
Ê Operation: heal-root-aggregates
Ê State: successful
ÊStart Time: 7/29/2016 20:54:41
Ê End Time: 7/29/2016 20:54:42
Ê Errors: -
8. On the impaired controller module, disconnect the power supplies.
Move and replace hardware - AFF A700 and FAS9000
Step 1: Remove the power supplies
Steps
Removing the power supplies when replacing a chassis involves turning off, disconnecting, and then removing
the power supply from the old chassis.
1. If you are not already grounded, properly ground yourself.
2. Turn off the power supply and disconnect the power cables:
a. Turn off the power switch on the power supply.
b. Open the power cable retainer, and then unplug the power cable from the power supply.
c. Unplug the power cable from the power source.
3. Press and hold the orange button on the power supply handle, and then pull the power supply out of the
chassis.
When removing a power supply, always use two hands to support its weight.
4

Locking button
4. Repeat the preceding steps for any remaining power supplies.
Step 2: Remove the fans
To remove the fan modules when replacing the chassis, you must perform a specific
sequence of tasks.
Steps
1. Remove the bezel (if necessary) with two hands, by grasping the openings on each side of the bezel, and
then pulling it toward you until the bezel releases from the ball studs on the chassis frame.
2. Press the orange button on the fan module and pull the fan module straight out of the chassis, making sure
that you support it with your free hand.
The fan modules are short. Always support the bottom of the fan module with your free hand
so that it does not suddenly drop free from the chassis and injure you.
5

Orange release button
3. Set the fan module aside.
4. Repeat the preceding steps for any remaining fan modules.
Step 3: Remove the controller module
To replace the chassis, you must remove the controller module or modules from the old
chassis.
Steps
1. Unplug the cables from the impaired controller module, and keep track of where the cables were
connected.
2. Slide the orange button on the cam handle downward until it unlocks.
6

Cam handle release button
Cam handle
3. Rotate the cam handle so that it completely disengages the controller module from the chassis, and then
slide the controller module out of the chassis.
Make sure that you support the bottom of the controller module as you slide it out of the chassis.
4. Set the controller module aside in a safe place, and repeat these steps if you have another controller
module in the chassis.
Step 4: Remove the I/O modules
Steps
To remove I/O modules from the old chassis, including the NVRAM modules, follow the
specific sequence of steps. You do not have to remove the FlashCache module from the
7

NVRAM module when moving it to a new chassis.
1. Unplug any cabling associated with the target I/O module.
Make sure that you label the cables so that you know where they came from.
2. Remove the target I/O module from the chassis:
a. Depress the lettered and numbered cam button.
The cam button moves away from the chassis.
b. Rotate the cam latch down until it is in a horizontal position.
The I/O module disengages from the chassis and moves about 1/2 inch out of the I/O slot.
c. Remove the I/O module from the chassis by pulling on the pull tabs on the sides of the module face.
Make sure that you keep track of which slot the I/O module was in.
Lettered and numbered I/O cam latch
I/O cam latch completely unlocked
3. Set the I/O module aside.
4. Repeat the preceding step for the remaining I/O modules in the old chassis.
8

Step 5: Remove the De-stage Controller Power Module
Steps
You must remove the de-stage controller power modules from the old chassis in
preparation for installing the replacement chassis.
1. Press the orange locking button on the module handle, and then slide the DCPM module out of the
chassis.
DCPM module orange locking button
2. Set the DCPM module aside in a safe place and repeat this step for the remaining DCPM module.
Step 6: Replace a chassis from within the equipment rack or system cabinet
Steps
You must remove the existing chassis from the equipment rack or system cabinet before
you can install the replacement chassis.
1. Remove the screws from the chassis mount points.
If the system is in a system cabinet, you might need to remove the rear tie-down bracket.
2. With the help of two or three people, slide the old chassis off the rack rails in a system cabinet or L
brackets in an equipment rack, and then set it aside.
3. If you are not already grounded, properly ground yourself.
4. Using two or three people, install the replacement chassis into the equipment rack or system cabinet by
9

guiding the chassis onto the rack rails in a system cabinet or Lbrackets in an equipment rack.
5. Slide the chassis all the way into the equipment rack or system cabinet.
6. Secure the front of the chassis to the equipment rack or system cabinet, using the screws you removed
from the old chassis.
7. Secure the rear of the chassis to the equipment rack or system cabinet.
8. If you are using the cable management brackets, remove them from the old chassis, and then install them
on the replacement chassis.
9. If you have not already done so, install the bezel.
Step 7: Move the USB LED module to the new chassis
Steps
Once the new chassis is installed into the rack or cabinet, you must move the USB LED
module from the old chassis to the new chassis.
1. Locate the USB LED module on the front of the old chassis, directly under the power supply bays.
2. Press the black locking button on the right side of the module to release the module from the chassis, and
then slide it out of the old chassis.
3. Align the edges of the module with the USB LED bay at the bottom-front of the replacement chassis, and
gently push the module all the way into the chassis until it clicks into place.
Step 8: Install the de-stage controller power module when replacing the chassis
Steps
Once the replacement chassis is installed into the rack or system cabinet, you must
reinstall the de-stage controller power modules into it.
1. Align the end of the DCPM module with the chassis opening, and then gently slide it into the chassis until it
clicks into place.
The module and slot are keyed. Do not force the module into the opening. If the module
does not go in easily, realign the module and slide it into the chassis.
2. Repeat this step for the remaining DCPM module.
Step 9: Install fans into the chassis
Steps
To install the fan modules when replacing the chassis, you must perform a specific
sequence of tasks.
1. Align the edges of the replacement fan module with the opening in the chassis, and then slide it into the
chassis until it snaps into place.
When inserted into a live system, the amber Attention LED flashes four times when the fan module is
successfully inserted into the chassis.
2. Repeat these steps for the remaining fan modules.
10

3. Align the bezel with the ball studs, and then gently push the bezel onto the ball studs.
Step 10: Install I/O modules
Steps
To install I/O modules, including the NVRAM/FlashCache modules from the old chassis,
follow the specific sequence of steps.
You must have the chassis installed so that you can install the I/O modules into the corresponding slots in the
new chassis.
1. After the replacement chassis is installed in the rack or cabinet, install the I/O modules into their
corresponding slots in the replacement chassis by gently sliding the I/O module into the slot until the
lettered and numbered I/O cam latch begins to engage, and then push the I/O cam latch all the way up to
lock the module in place.
2. Recable the I/O module, as needed.
3. Repeat the preceding step for the remaining I/O modules that you set aside.
If the old chassis has blank I/O panels, move them to the replacement chassis at this time.
Step 11: Install the power supplies
Steps
Installing the power supplies when replacing a chassis involves installing the power
supplies into the replacement chassis, and connecting to the power source.
1. Using both hands, support and align the edges of the power supply with the opening in the system chassis,
and then gently push the power supply into the chassis until it locks into place.
The power supplies are keyed and can only be installed one way.
Do not use excessive force when sliding the power supply into the system. You can damage
the connector.
2. Reconnect the power cable and secure it to the power supply using the power cable locking mechanism.
Only connect the power cable to the power supply. Do not connect the power cable to a
power source at this time.
3. Repeat the preceding steps for any remaining power supplies.
Step 12: Install the controller
Steps
After you install the controller module and any other components into the new chassis,
boot it to a state where you can run the interconnect diagnostic test.
1. Align the end of the controller module with the opening in the chassis, and then gently push the controller
module halfway into the system.
11

Do not completely insert the controller module in the chassis until instructed to do so.
2. Recable the console to the controller module, and then reconnect the management port.
3. Connect the power supplies to different power sources, and then turn them on.
4. With the cam handle in the open position, slide the controller module into the chassis and firmly push the
controller module in until it meets the midplane and is fully seated, and then close the cam handle until it
clicks into the locked position.
Do not use excessive force when sliding the controller module into the chassis; you might
damage the connectors.
The controller module begins to boot as soon as it is fully seated in the chassis.
5. Repeat the preceding steps to install the second controller into the new chassis.
6. Boot each node to Maintenance mode:
a. As each node starts the booting, press Ctrl-C to interrupt the boot process when you see the
message Press Ctrl-C for Boot Menu.
If you miss the prompt and the controller modules boot to ONTAP, enter halt, and then
at the LOADER prompt enter boot_ontap, press Ctrl-C when prompted, and then
repeat this step.
b. From the boot menu, select the option for Maintenance mode.
Complete the restoration and replacement process - AFF
A700 and FAS9000
Step 1: Verify and set the HA state of the chassis
You must verify the HA state of the chassis, and, if necessary, update the state to match
your system configuration.
Steps
1. In Maintenance mode, from either controller module, display the HA state of the local controller module and
chassis: ha-config show
The HA state should be the same for all components.
2. If the displayed system state for the chassis does not match your system configuration:
a. Set the HA state for the chassis: ha-config modify chassis HA-state
The value for HA-state can be one of the following:
▪ha
▪mcc
▪mcc-2n
12

▪mccip
▪non-ha
b. Confirm that the setting has changed: ha-config show
3. If you have not already done so, recable the rest of your system.
4. Exit Maintenance mode: halt
The LOADER prompt appears.
Step 2: Running system-level diagnostics
After installing a new chassis, you should run interconnect diagnostics.
Your system must be at the LOADER prompt to start System Level Diagnostics.
All commands in the diagnostic procedures are issued from the node where the component is being replaced.
Steps
1. If the node to be serviced is not at the LOADER prompt, perform the following steps:
a. Select the Maintenance mode option from the displayed menu.
b. After the node boots to Maintenance mode, halt the node: halt
After you issue the command, you should wait until the system stops at the LOADER prompt.
During the boot process, you can safely respond yto prompts:
2. Repeat the previous step on the second node if you are in an HA configuration.
Both controllers must be in Maintenance mode to run the interconnect test.
3. At the LOADER prompt, access the special drivers specifically designed for system-level diagnostics to
function properly: boot_diags
During the boot process, you can safely respond yto the prompts until the Maintenance mode prompt (*>)
appears.
4. Enable the interconnect diagnostics tests from the Maintenance mode prompt: sldiag device modify
-dev interconnect -sel enable
The interconnect tests are disabled by default and must be enabled to run separately.
5. Run the interconnect diagnostics test from the Maintenance mode prompt: sldiag device run -dev
interconnect
You only need to run the interconnect test from one controller.
6. Verify that no hardware problems resulted from the replacement of the chassis: sldiag device status
-dev interconnect -long -state failed
System-level diagnostics returns you to the prompt if there are no test failures, or lists the full status of
13

failures resulting from testing the component.
7. Proceed based on the result of the preceding step.
If the system-level diagnostics
tests…
Then…
Were completed without any
failures
a. Clear the status logs: sldiag device clearstatus
b. Verify that the log was cleared: sldiag device status
The following default response is displayed:
SLDIAG: No log messages are present.
c. Exit Maintenance mode on both controllers: halt
The system displays the LOADER prompt.
You must exit Maintenance mode on both
controllers before proceeding any further.
d. Enter the following command on both controllers at the LOADER
prompt: bye
e. Return the node to normal operation:
With two nodes in the cluster Issue these commands: node::> cluster ha modify
-configured true
node::> storage failover modify -node node0
-enabled true
With more than two nodes in the
cluster
Issue this command:node::> storage failover modify
-node node0 -enabled true
In a two-node MetroCluster
configuration
Proceed to the next step.
The MetroCluster switchback procedure is done in the next task in the
replacement process.
In a stand-alone configuration You have no further steps in this particular task.
You have completed system-level diagnostics.
14

If the system-level diagnostics
tests…
Then…
Resulted in some test failures Determine the cause of the problem.
a. Exit Maintenance mode: halt
b. Perform a clean shutdown, and then disconnect the power
supplies.
c. Verify that you have observed all of the considerations identified
for running system-level diagnostics, that cables are securely
connected, and that hardware components are properly installed
in the storage system.
d. Reconnect the power supplies, and then power on the storage
system.
e. Rerun the system-level diagnostics test.
Step 3: Switch back aggregates in a two-node MetroCluster configuration
After you have completed the FRU replacement in a two-node MetroCluster
configuration, you can perform the MetroCluster switchback operation. This returns the
configuration to its normal operating state, with the sync-source storage virtual machines
(SVMs) on the formerly impaired site now active and serving data from the local disk
pools.
This task only applies to two-node MetroCluster configurations.
Steps
1. Verify that all nodes are in the enabled state: metrocluster node show
cluster_B::> metrocluster node show
DR Configuration DR
Group Cluster Node State Mirroring Mode
----- ------- -------------- -------------- ---------
--------------------
1 cluster_A
Ê controller_A_1 configured enabled heal roots
completed
Ê cluster_B
Ê controller_B_1 configured enabled waiting for
switchback recovery
2 entries were displayed.
2. Verify that resynchronization is complete on all SVMs: metrocluster vserver show
3. Verify that any automatic LIF migrations being performed by the healing operations were completed
15

successfully: metrocluster check lif show
4. Perform the switchback by using the metrocluster switchback command from any node in the
surviving cluster.
5. Verify that the switchback operation has completed: metrocluster show
The switchback operation is still running when a cluster is in the waiting-for-switchback state:
cluster_B::> metrocluster show
Cluster Configuration State Mode
-------------------- ------------------- ---------
ÊLocal: cluster_B configured switchover
Remote: cluster_A configured waiting-for-switchback
The switchback operation is complete when the clusters are in the normal state.:
cluster_B::> metrocluster show
Cluster Configuration State Mode
-------------------- ------------------- ---------
ÊLocal: cluster_B configured normal
Remote: cluster_A configured normal
If a switchback is taking a long time to finish, you can check on the status of in-progress baselines by using
the metrocluster config-replication resync-status show command.
6. Reestablish any SnapMirror or SnapVault configurations.
Step 4: Return the failed part to NetApp
After you replace the part, you can return the failed part to NetApp, as described in the
RMA instructions shipped with the kit. Contact technical support at NetApp Support, 888-
463-8277 (North America), 00-800-44-638277 (Europe), or +800-800-80-800
(Asia/Pacific) if you need the RMA number or additional help with the replacement
procedure.
16

Copyright Information
Copyright © 2021 NetApp, Inc. All rights reserved. Printed in the U.S. No part of this document covered by
copyright may be reproduced in any form or by any means-graphic, electronic, or mechanical, including
photocopying, recording, taping, or storage in an electronic retrieval system- without prior written permission of
the copyright owner.
Software derived from copyrighted NetApp material is subject to the following license and disclaimer:
THIS SOFTWARE IS PROVIDED BY NETAPP “AS IS” AND WITHOUT ANY EXPRESS OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE HEREBY DISCLAIMED. IN NO EVENT SHALL
NETAPP BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR
CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE
GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER
CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT
(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS
SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
NetApp reserves the right to change any products described herein at any time, and without notice. NetApp
assumes no responsibility or liability arising from the use of products described herein, except as expressly
agreed to in writing by NetApp. The use or purchase of this product does not convey a license under any
patent rights, trademark rights, or any other intellectual property rights of NetApp.
The product described in this manual may be protected by one or more U.S. patents, foreign patents, or
pending applications.
RESTRICTED RIGHTS LEGEND: Use, duplication, or disclosure by the government is subject to restrictions
as set forth in subparagraph (c)(1)(ii) of the Rights in Technical Data and Computer Software clause at DFARS
252.277-7103 (October 1988) and FAR 52-227-19 (June 1987).
Trademark Information
NETAPP, the NETAPP logo, and the marks listed at http://www.netapp.com/TM are trademarks of NetApp, Inc.
Other company and product names may be trademarks of their respective owners.
17
This manual suits for next models
2
Table of contents
Popular Chassis manuals by other brands

iStarUSA
iStarUSA D-200L-PFS Product Quick Guide

Transition Networks
Transition Networks PointSystem CPSMC0200-221 user guide

Accuride
Accuride AL4160-12 manual

Overland Storage
Overland Storage SnapExpansion DX Series Replacement instructions

Transition Networks
Transition Networks PointSystem CPSMC1900-100 user guide

Cisco
Cisco Nexus 7018 manual