NetMan 204 User manual


INTRODUCTION
Thank you for choosing our product.
The accessories described in this manual are of the highest quality, carefully designed and built in
order to ensure excellent performance.
This manual contains detailed instructions on how to install and use the product.
This manual must be stored in a safe place and CONSULTED BEFORE USING THE DEVICE
for proper usage instructions as well as maximum performance from the device itself.
NOTE: Some images contained in this document are for informational purposes only and may not
faithfully demonstrate the parts of the product they represent.
Symbols used in this manual:
Warning Indicates important information that must not be ignored.
Information Provides notes and useful suggestions for the User.
SAFETY
This part of the manual contains SAFETY precautions that must be followed scrupulously.
The device has been designed for professional use and is therefore not suitable for use in
the home.
The device has been designed to operate only in closed environments. It should be
installed in rooms where there are no inflammable liquids, gas or other harmful substances.
Take care that no water or liquids and/or foreign bodies fall into the device.
In the event of a fault and/or impaired operation of the device, do not attempt to repair it but
contact the authorized service centre.
The device must be used exclusively for the purpose for which it was designed. Any other
use is to be considered improper and as such dangerous. The manufacturer declines all
responsibility for damage caused by improper, wrong and unreasonable use.
- 2 -

ENVIRONMENTAL PROTECTION
Our company devotes abundant resources to analyzing environmental aspects in the development
of its products. All our products pursue the objectives defined in the environmental management
system developed by the company in compliance with applicable standards.
Hazardous materials such as CFCs, HCFCs or asbestos have not been used in this product.
When evaluating packaging, the choice of material has been made favoring recyclable materials.
Please separate the different material of which the packaging is made and dispose of all material in
compliance with applicable standards in the country in which the product is used.
DISPOSING OF THE PRODUCT
The device contains internal material which (in case of dismantling/disposal) are considered
TOXIC, such as electronic circuit boards. Treat these materials according to the laws in force,
contacting qualified centers. Proper disposal contributes to respect for the environment and human
health.
© The reproduction of any part of this manual, even in part, is prohibited unless authorized by the
manufacturer.
The manufacturer reserves the right to change the product described at any time without prior notice for
improvement purposes.
- 3 -

CONTENTS
DESCRIPTION ____________________________________________________ 6
OVERVIEW ____________________________________________________________6
PACKAGE CONTENTS _____________________________________________________6
FRONT PANEL __________________________________________________________7
Network port _____________________________________________________________ 7
Micro-USB port ___________________________________________________________ 7
Serial port _______________________________________________________________ 7
Led _____________________________________________________________________ 7
Reset button _____________________________________________________________ 8
USERS _______________________________________________________________8
NETWORK SERVICES _____________________________________________________9
SSH_____________________________________________________________________ 9
Serial network ____________________________________________________________ 9
Wake-on-LAN_____________________________________________________________ 9
HTTP____________________________________________________________________ 9
SNMP ___________________________________________________________________ 9
UDP_____________________________________________________________________ 9
Modbus TCP/IP __________________________________________________________ 10
BACnet/IP_______________________________________________________________ 10
FTP ____________________________________________________________________ 10
Email___________________________________________________________________ 10
Reports_________________________________________________________________ 10
UPS VALUES AND EVENTS HISTORY LOG ARCHIVE _______________________________11
Eventlog ________________________________________________________________ 11
Datalog _________________________________________________________________ 11
ENVIRONMENTAL SENSORS (OPTIONAL)_______________________________________12
Available sensors ________________________________________________________ 12
INSTALLATION __________________________________________________ 12
CONFIGURATION ________________________________________________ 13
OVERVIEW ___________________________________________________________13
Configuration via HTTP/HTTPS _____________________________________________ 13
Configuration via USB ____________________________________________________ 14
Configuration via SSH ____________________________________________________ 14
CONFIGURATION MENU DESCRIPTION ________________________________________15
Start menu ______________________________________________________________ 15
Setup __________________________________________________________________ 16
- 4 -

IP config________________________________________________________________ 18
Time setting_____________________________________________________________ 19
Scheduled NTP __________________________________________________________ 20
UPS config______________________________________________________________ 20
Services 1 ______________________________________________________________ 21
SNMPv1 config __________________________________________________________ 22
SNMPv1 community ______________________________________________________ 22
Email config_____________________________________________________________ 23
Email logic ______________________________________________________________ 24
Miscellaneous ___________________________________________________________ 25
Activation 1 _____________________________________________________________ 26
Services 2 ______________________________________________________________ 26
Wake-On-LAN address ____________________________________________________ 27
Wake-On-LAN delay ______________________________________________________ 27
Activation 2 _____________________________________________________________ 28
Sensors Config __________________________________________________________ 28
I/O Sensors _____________________________________________________________ 30
Security ________________________________________________________________ 31
Save and load ___________________________________________________________ 33
Password recovery _______________________________________________________ 33
Wi-Fi setup (optional card required) _________________________________________ 34
Expert mode ____________________________________________________________ 35
CONFIGURATION OF SEVERAL DEVICES _______________________________________35
FIRMWARE UPGRADE ____________________________________________ 36
FIRMWARE UPGRADE VIA HTTP ____________________________________________36
FIRMWARE UPGRADE VIA FTP _____________________________________________36
SNMPV3 CONFIGURATION ________________________________________ 37
MODBUS TCP/IP PROTOCOL_______________________________________ 39
BACNET/IP CONFIGURATION ______________________________________ 43
MODEM CONFIGURATION _________________________________________ 45
TECHNICAL DATA ________________________________________________ 47
NETWORK CABLE ______________________________________________________47
OPERATING AND STORAGE CONDITIONS_______________________________________47
- 5 -

DESCRIPTION
OVERVIEW
NetMan 204is a device that allows UPS management through a LAN (Local Area Network); the
accessory supports all the main network protocols (SNMP v1 and v3, TCP/IP, HTTP and so on)
and is compatible with Ethernet 10/100Mbps IPv4/6 networks. The UPS can therefore be
integrated easily into medium and large-sized networks.
The device also records UPS values and events in the history log archive and can manage
optional environmental sensors (not supplied with the device, but provided separately)
PACKAGE CONTENTS
NetMan 204
USB cable
CD-Rom (User manual)
Quick start
- 6 -

FRONT PANEL
A: Network port
B: Led
C: Reset button
D: Micro-USB port
E: Serial port
Network port
NetMan 204 connects to 10/100 Mbps Ethernet networks by means of connector RJ45. The LEDs
built into the connector describe the status of the network:
•Left LED:
SOLID YELLOW: NetMan204 has detected a valid link.
FLASHING YELLOW: NetMan204 is receiving or transmitting data packets.
•Right LED
SOLID GREEN: NetMan204 is connected to a network operating at 100 Megabits per second.
Micro-USB port
NetMan 204 makes available an USB communication port through which it is possible to configure
it (see paragraph “Configuration via USB”).
Serial port
NetMan 204 makes available a serial communication port to which you can connect environmental
sensors (not supplied with the device, but provided separately) or a modem (not supplied with the
device) for UPS teleservice.
Led
This led describes the status of NetMan 204:
•SOLID RED: NetMan 204 is not communicating with the UPS (verify PRTK Code).
•FLASHING RED: the DHCP server does not have assigned a valid IP address to NetMan 204.
•OFF: regular working.
- 7 -

Reset button
The reset button allows to restart the NetMan204 or to load a default configuration with a
predefined static IP address.
To reset NetMan204: keep press the reset button until the red led start flashing (ca. 2 seconds)
and then release it.
To load a configuration with predefined static IP address: keep press the reset button; first the
led starts flashing, then turns to solid red (ca. 10 seconds). When the led is solid red, release the
reset button and the NetMan 204 will reboot with:
•IP address: 192.168.0.204
•Netmask: 255.255.0.0
•SSH service enabled
•HTTP service enabled
HTTP and SSH service are enabled temporarily without changing the configuration saved
in non-volatile memory.
USERS
It is possible to access to NetMan 204 with three different users (admin / fwupgrade / user).
Username Default password Privileges
admin admin user with right to modify the configuration
fwupgrade fwupgrade user with right to upgrade the firmware
user user user with right to read and download the log files
- 8 -

NETWORK SERVICES
NetMan 204 implements a series of services based on the main network protocols. These services
can be activated or deactivated according to requirements (see paragraph “Configuration”). A brief
description for each of these is given below.
SSH
By means of a SSH client (available on all the main operating systems) a remote connection with
NetMan 204 can be established to change its configuration (see paragraph “Configuration via
SSH”).
Serial network
To emulate a point-to-point serial connection through the network (TCP/IP protocol) in order to use
special function service software.
Wake-on-LAN
NetMan 204 can send “Wake-on-LAN” command for remote computers boot.
HTTP
Using the HTTP (Hyper Text Transfer Protocol), is possible to configure the NetMan 204 and the
status of the UPS can be monitored by means of a web browser without having to install additional
software. All the most popular web browsers are supported.
SNMP
SNMP (Simple Network Management Protocol) is a communication protocol that allows a client
(manager) to make requests to a server (agent). NetMan 204 is an SNMP agent.
To exchange information, manager and agent use an addressing technique called MIB
(Management Information Base). There is a MIB file for each agent, defining which variables can
be requested and the respective access rights. The agent can also send messages (TRAP) without
a prior request from the manager, to inform the latter of particularly important events. SNMPv3 is
the evolution of SNMP and introduces new important features related to security. (See paragraph
“SNMPv3”).
UDP
UDP (User Datagram Protocol) is a low level network protocol that guarantees speed in the
exchange of data and low network congestion. It is the protocol used by the UPSMon software for
monitoring and control of the UPS.
The UDP connection uses the UDP 33000 port by default but can be configured on other ports
according to requirements.
- 9 -

Modbus TCP/IP
The UPS status can be monitored by means of the standard network protocol MODBUS TCP/IP.
Modbus TCP/IP is simply the Modbus RTU protocol with a TCP interface that runs on Ethernet.
BACnet/IP
The UPS status can be monitored by means of the standard network protocol BACnet/IP.
BACnet (Building Automation and Control networks) is a data communication protocol mainly used
in the building automation and HVAC industry (Heating Ventilation and Air-Conditioning).
FTP
FTP (File Transfer Protocol) is a network protocol used for file exchange. NetMan 204 uses this
protocol for:
1. download of files of the UPS values and events history log archive (Datalog and Eventlog);
2. download and upload of configuration files;
3. firmware upgrade.
In both cases a client FTP is required, configured with these parameters:
•Host: hostname or NetMan 204 IP address;
•User: see chapter “Users”;
•Password: current password.
The connection can also be established using a web browser (all the most popular web browsers
are supported), by inserting the hostname or IP address of the NetMan 204.
Email
NetMan 204 can send a notification e-mail if one or more alarm conditions occur. The e-mails can
be sent to up to three recipients and they can be sent for seven different kinds of alarm.
SMTP (Simple Mail Transfer Protocol) is the protocol used to send the e-mails. They are sent to an
SMTP server on port 25. For more details, see paragraph “Configuration”
Reports
NetMan 204 can send periodic e-mails with an attachment containing the files of the UPS values
and events history log archive.
This service can be used to periodically save the history log archives.
The “Email” service must be enabled in order to send reports; the reports are sent to all the
addresses configured for this service (for more details see paragraph “Configuration”).
- 10 -

UPS VALUES AND EVENTS HISTORY LOG ARCHIVE
NetMan 204 records the UPS values (Datalog) and events (Eventlog) in a history log archive. The
data are saved to file in text format.
The format used to record the date and time is of the type: YY/MM/DD HH:MM:SS
Eventlog
The Eventlog service is always active and records all relevant UPS events in the ‘event.log’ file.
The file can be downloaded via FTP or sent by e-mail using the “Email report” service. The data
are saved in circular list mode, thus the most recent data are saved by overwriting the oldest data.
Datalog
The Datalog service records the main data of the UPS in the ‘data.log’ file. The file can be
downloaded via FTP or can be sent by e-mail using the “Email report” service. The following data
are monitored:
•Input voltage phase 1
•Input voltage phase 2
•Input voltage phase 3
•Input frequency
•Output voltage phase 1
•Output voltage phase 2
•Output voltage phase 3
•Load on phase 1
•Load on phase 2
•Load on phase 3
The interval of time between one recording and the next (Log frequency) can be configured by the
user (see paragraph “Miscellaneous Menu”). The data are saved in circular list mode, thus the
most recent data are saved by overwriting the oldest data. Data for up to 256 different points of
time can be recorded.
- 11 -

ENVIRONMENTAL SENSORS (OPTIONAL)
It is possibile to connect to NetMan 204 the environmental sensors for monitoring temperature,
humidity and digital input/output.
The information provided by these sensors can be showed with the UPS monitoring and control
software or with a web browser (the HTTP service must be active).
The values provided by the sensors may also be requested with SNMP according to the RFC 3433
standard (MIB files in the bundled CD).
Available sensors
•Temperature: detects the environmental temperature in °C.
•Humidity & Temperature: detects the relative humidity in % and the environmental
temperature in °C.
•Digital I/O & Temperature: detects the environmental temperature in °C and features a
digital input and a digital output.
It is possible to connect up to 3 environmental sensor to a NetMan 204 (for sensor
installation please see the sensors’ manual).
INSTALLATION
1. Remove the cover of the UPS expansion slot by removing the two retaining screws.
2. Insert NetMan 204 in the slot.
3. Secure Netman 204 in the slot using the two screws removed previously.
4. Connect the device to the network by means of connector RJ-45 (see “Specifications for the
cabling of the network cable”)
- 12 -

CONFIGURATION
OVERVIEW
NetMan 204 can be configured via USB, via SSH or via HTTPS.
NetMan 204 comes provided as factory default with DHCP enabled and with the following
services active: SSH, HTTP, SNMP, UDP and FTP.
In order to change the configuration of NetMan 204, you have to log in as admin (default
password “admin”).
5
NetMan 204 needs approx. 2 minutes to become operational from when it is powered up
or after a reboot; before this time the device may not respond to commands that are sent
to it.
Configuration via HTTP/HTTPS
In order to change the configuration via http/https, you have to insert in your web browser the
hostname or IP address of the NetMan 204 and then log in as admin (default password: "admin").
The HTTPS service uses TLS (transport layer security) in order to provide cryptographic
security. However, the certificate used is self-signed and therefore the web browser may
prompt a security alert; in this case you can ignore the alert and proceed with the
configuration of NetMan 204.
Once login has been effected, you can browse through the menus to configure the NetMan 204.
In order to make a new configuration effective, it is necessary to confirm it (OK button for
each configuration page changed) and then reboot the NetMan 204 (as required with a
pop-up by your web browser).
- 13 -

Configuration via USB
To configure NetMan 204 via USB it is necessary to:
•Connect, with the USB cable provided, the micro-USB port with the USB port of a PC with
Windows operating system.
•If not previously installed, install the USB driver (after driver installation, a virtual COM
named “NetMan 204 Serial” will be present in device manager).
•Execute a terminal emulation program with the following settings:
COMn (1), 115200 baud, no parity, 8 databits, 1 stop bit, no flow control.
(1) COMn = COM port assigned to “NetMan 204 Serial” by device manager.
•Press the “Enter” key of the PC.
•At the login prompt, enter “admin”.
•At the password prompt, enter the current password (default password: "admin").
During password’s typing, no character is shown.
Once login has been effected, the screen of the start menu is displayed. From this screen it is
possible to access the various menus to change NetMan 204 settings (see paragraph “Start menu”
and following paragraphs).
Configuration via SSH
To configure NetMan 204 via SSH it is necessary to:
•Execute a SSH client on a PC connected in a network to NetMan 204 set with the IP
address of the device to be configured.
•At the login prompt, enter “admin”.
•At the password prompt, enter the current password (default password: "admin").
During password’s typing, no character is shown.
For proper configuration of NetMan 204, you must configure the SSH client so that
the backspace key sends "Control-H".
Please verify the keyboard options of your SSH client.
Once login has been effected, the screen of the start menu is displayed. From this screen it is
possible to access the various menus to change NetMan 204 settings (see paragraph “Start menu”
and following paragraphs).
- 14 -

CONFIGURATION MENU DESCRIPTION
In order to make a new configuration effective, it is necessary to save it in the flash
memory; this action automatically reboot the NetMan 204 (refer to “Menu Save and load”).
Start menu
Once login has been effected via SSH or USB, a screen like the following is displayed:
/------------------------/
/ Netman 204 /
/------------------------/
Setup..........:<--
View status....:
Change password:
Service log....:
Wi-Fi setup....:no card installed
Expert mode....:
Press [ESC] for logout
SysVer. S15-1 - AppVer. 01.04.000
Function Description
Setup To enter main configuration menu
View status To see the status of the device
Change password To modify the password (see also Password recovery)
Service log To generate a log file of the card (when requested by the service)
Wi-Fi setup
To configure Wi-Fi connection
For Wi-Fi connection, an optional card is required. The Wi-Fi card is not
provided with NetMan 204 but it has to be purchased separately.
Expert mode To enter Expert mode (more information at paragraph “Expert mode”)
To move within this menu and the following menus, use the keys as described in the following
table; the arrow or the cursor shows the current selection.
Key Function
Direction keys (Arrow up, down, right, left) To move the cursor within the menus
Tab Goes on to next option
Enter (1) Choice of submenu
Confirmation of characters entered
Esc (1) Exit main menu (2)
Return to previous menu
(1) Some keys can have a different function depending on the menu.
(2) To exit from a menu a confirmation (‘Y’ or ‘N’) is required after pressing the ESC key.
- 15 -

Setup
The main configuration menu displays a screen like the following:
/------------------------/
/ Setup /
/------------------------/
IP config......:<--
Time setting...:
UPS config.....:
Services 1.....:
Services 2.....:
Security.......:
Save and load..:
Press [Esc] to quit
SysVer. S15-1 - AppVer. 01.04.000
From this main menu it is possible to access the various submenus, the function of each of which
is shown in the table below.
Menu Function
IP config To configure the network parameters
Time setting To configure the internal clock
UPS config To configure the type of UPS connected
Services 1
To activate and/or deactivate device services
Services 2
Security To configure the password and access to the network
Save and load To save a configuration: this action will reboot automatically the device.
The screen also displays some messages describing the kind of configuration data displayed and
the status of the UPS. The meaning of these messages is described below.
•Data from flash: means that the configuration has been loaded from the flash memory
•Default data: means that the configuration has been reset to the default values
- 16 -

Here is a graphical representation of the setup menu and submenus:
- 17 -

IP config
/------------------------/
/ IP config /
/------------------------/
Hostname.......:ups-server
IP address/DHCP:DHCP
Netmask........:
Gateway........:
Primary DNS....:
Secondary DNS..:
Mailhost.......:
With this menu the main network parameters can be set as described in the following table.
Field Parameters to be inserted
Hostname Enter the NetMan 204 host name
IP address/DHCP Enter the IP address for a static IP; enter “DHCP” for a dynamic IP
Netmask Enter the netmask to be used together with the static IP address
Gateway Enter the name or the address of the network gateway
Primary DNS Enter the name or the address of the preferred DNS to be used
Secondary DNS Enter the name or the address of the alternative DNS to be used
If a static IP address is assigned to the device, all the fields must be configured with the
network parameters. If a dynamic IP address is assigned, just enter ‘dhcp’ in the “IP
Address/DHCP” field and provide a hostname; all the other options should be ignored
because these are automatically configured with DHCP
After pressing “ESC” and “Y” to confirm exit from the menu, a screen similar to the image below is
displayed. Press the “ENTER” key to return to the main menu. The configuration must however be
saved to make it effective after restart of the device (see “Save and load” menu).
eth0 Link encap:Ethernet HWaddr 00:02:63:04:07:b1
inet addr:10.1.11.19 Bcast:10.1.255.255 Mask:255.255.0.0
inet6 addr: fe80::202:63ff:fe04:7b1/64 Scope:Link
UP BROADCAST RUNNING MULTICAST MTU:1500 Metric:1
RX packets:145877 errors:0 dropped:0 overruns:0 frame:1
TX packets:4899 errors:0 dropped:0 overruns:0 carrier:0
collisions:0 txqueuelen:1000
RX bytes:12740380 (12.1 MiB) TX bytes:2115614 (2.0 MiB)
NOTE: The new settings will become effective on next reboot.
- 18 -

Time setting
/------------------------/
/ Time setting /
/------------------------/
Set time.......:<--
Set timezone...:
Sync with NTP..:
Scheduled NTP..:
From this menu the time and date of the device can be set as described in the following table.
Command Description
Set time To configure the time and date manually
Set timezone To configure the time zone
Sync with NTP To synchronize the clock with an NTP server
Scheduled NTP To configure the scheduled NTP
Pressing the “ENTER” key corresponding to the “Set time” command displays a screen like the one
shown below.
Current date is Wed Jan 01 07:45:50 GMT 2014
Insert new date and clock time in this form:
MMDDYYYYHHMMSS
06152014080100
Current date is Sun Jun 15 08:01:00 GMT 2014
Enter the date and time in the format shown, then press the ENTER key and then “ESC” to exit.
Pressing the “ENTER” key corresponding to the “Set timezone” command displays a screen where
is possible to modify the time zone.
Pressing the “ENTER” key corresponding to the “Sync with NTP” command displays a screen like
the one shown below.
Current date is Thu Jun 16 14:17:06 ECT 2005
Insert IP Address or host name of the NTP server to synchronize time:
Enter the name or the address of the NTP server with which the device is to be synchronized. In
this case the time has to be within the GMT time zone, thus it may be necessary to correct the
current time zone with the “Set timezone” command.
- 19 -

Scheduled NTP
/------------------------/
/ Scheduled NTP /
/------------------------/
NTP server.....:time_server
Sync only at...:13 hour (0 - 23)
Sync only at...:* day of week (0 - 6) (Sunday=0 or 7) OR sun,mon,tue ...
Sync only at...:1 day of month (1 - 31)
Insert * where the value is not needed.
With this menu is possible to schedule the NTP synchronization. Is possible to specify the time and
frequency for performing a synchronization. For each field is possible to enter the precise condition
or leaving ‘*’ which means always. On the example above, synchronization will be performed every
1st day of month at 13:00, regardless of the day of week.
Field Parameters to be inserted
NTP server Enter the name or address of the NTP server
Sync only at (h) Enter the hour when the synchronization should occur, or ‘*’
Sync only at (w) Enter the day of week when the synchronization should occur, or ‘*’
Sync only at (m) Enter the day of month when the synchronization should occur, or ‘*’
Only for UPS with PRTK code SENTR.., if a valid NTP server is configured, NetMan 204
will synchronize the clock of the UPS every day with its clock.
UPS config
/------------------------/
/ UPS config /
/------------------------/
PRTK Code......:GPSER11201XX
Name...........:ups3
UPS Address....:1
Serial number..:324321
With this menu the UPS parameters must be set as described in the following table, for the UPS to
be able to communicate correctly with the device.
Field Parameters to be inserted
PRTK Code Enter the PRTK code indicated at the back of the UPS(1)
Name Enter the identifying name of the UPS
UPS Address Insert 1
Serial number Enter the UPS identification code
(1) The PRTK code is formed of 12 alphanumeric characters.
- 20 -
Other manuals for 204