240322-01
3. Reinstall the thermostat
faceplate on to its backplate.
Check proper operation by
watching the LED blink
pattern as outlined in the LED
Status section. Repeat for
each sensor.
LED STATUS
The NT-DRS includes a Diagnostic LED that can help you
troubleshoot your installation and sensor operation.
LED Off:
LED OFF indicates no power to the NT-DRS or thermostat. Check
wiring of your sensor and the thermostat for problems. Fix as
necessary.
LED On Solid During Power-Up:
On power-up the LED will turn on solid until the NT-DRS
successfully communicates with the thermostat. If the connection
is successful, the LED will blink according to its conguration. If
the remains on, there is a communication problem. Check wiring
and x as necessary.
LED On Solid After Power Up:
If the NT-DRS loses connection with the thermostat for 60
seconds, the LED will turn on solid. Check the wiring and x as
necessary. Cycle power cycle power and recheck the LED status.
LED Triple Blink (Probe Operation)
The NT-DRS LED will blink three times when the thermostat
requests data. This occurs approximately every 16-20 seconds.
LED Fast Continuous Blink (Lost Probe)
If the NT-DRS loses communication with the probe, the LED will
continually blink fast. Check wiring and probe and x as
necessary.
ANOTE: In this condition, the NT-DRS will stop reporting until
the communication with the probe is xed.
ONE (1) YEAR LIMITED WARRANTY
Network Thermostat™ warrants to the original purchaser that
this product will be free from defects in workmanship and
materials for a period of ve years from the date of purchase
with proof of purchase.
Warranty Limitations
This warranty begins on the date of purchase.
Warranty is Void if:
●The date code or serial number is defaced or removed.
●The product has a defect or damage due to product
alteration, connection to an improper electrical supply,
shipping and handling, accident, re, ood, lightning or
other conditions beyond the control of the manufacturer.
●The product is not installed according to the manufacturers
instructions and specications.
Owner’s Responsibility
●Provide proof of purchase.
●Provide normal care and maintenance.
●Pay for freight, labor and travel.
●Return any defective product.
●In no event shall the manufacturer be liable for incidental
or consequential damages.
This warranty gives you specic legal rights and you may have
others which vary by state and/or province. For example,
some states and/or provinces do not allow the exclusion or
limitation of incidental or consequential damages, so this
exclusion may not apply to you. The manufacturer’s continuing
commitment to quality products may require a change in
specications without notice.
SPECIFICATIONS
Rated Voltage:
20V to 30VAC, 24VAC nominal
Auxiliary Temp Sensor Range:
AUX1, AUX2, AUX3: -40°F to +200°F (-40°C to +93°C)
Measurement Accuracy:
Temperature: ± 1.0°F (±0.5°C);
Terminations:
RS1 - Data, RS+V – Power, RS2 – Return, 1 & 2 – External
Temp Sensor Leads, 1-2, 3-5, 6+ Sensors
Dimensions:
Case: 3.0”H x 3.25”W x 2.05”D (76.2mm x 82.5mm x 52mm)
Probe: 8.0” (203.2mm)
Approved Cable Types:
CAT5 or CAT5e unshielded, or 1-Pair Twisted Shielded Cable
with Drain and nominal capacitance of 12pF/ft or less. Use
riser or plenum jacket as required by local code.
Maximum 300ft Total Sensor Cable Length per Thermostat
Page 3
X-SERIES
2. Connect wires to each additional sensor in the following
manner.
NT-DRS
Additional NT-DRS Sensors
Set as AUX 2 Sensor
NT-DRS
First NT-DRS in chain
Set as AUX 1 Sensor
Wiring To
Next Sensor
(If needed)