Introduction
The ACE-VAF110 provides accurate digital metering for AC Volts, Amps, Frequency and Kilowatts. Low/High Voltage,
Low/High Frequency and High KW alarms are easily set. When activated, the built-in 85 dB alarm will sound and the
display will flash the out-of-limit condition.
Volts can be displayed from 90 to 300 VACRMS. Amps can be displayed from 0 to 150 amps. Killowatts are displayed
from 0.0 to 45.0 kW in tenths.
The ACE-VAF110 outputs standard NMEA 0183 serial data sentences of AC volts, amps, frequency and kW. If the NMEA
0183 serial data is
not required, then this output line can be programmed to turn off a faulty generator.
Five levels of backlighting can be selected and the backlights can be remotely turned ON/OFF. All set-up, calibration and
alarm values are saved to non-volatile memory. The ACE-VAF110 comes complete with voltage and current transformers
and is factory calibrated to read within 1%. The large LCD display draws only .035 amps and only .055 amps with full
backlighting.
The ACE-VAF110 is powered with a power source of 9.5 to 33.0 VDC and transient protected.
Model: ACE-VAF110
AC Energy Monitor
INSTALLATION/OPERATION MANUAL
ELECTRONIC POWER PRODUCTS
COMMUNICATION • NAVIGATION
P.O. Box 1306, Newport Beach, California 92663 • Phone: 714-751-0488 • Fax: 714-957-1621 • E-Mail: sales@newmarpower.com
www.newmarpower.com
RED #1
BLUE #2
BLUE #1
GREEN #1
YELLOW #1
WHITE #2 NMEA 0183 Out
BLACK #1
Volts Xfmr
Volts Xfmr
LIGHTS On/Off
Current Xfmr
Current Xfmr
5 Amp Fuse
Power Ground
12 VAC 90-300 VAC
(C) +9.5 to
+33 VDC
Installation
Before starting the installation, please read this entire section first.
Finger tighten the screws that mount the instrument bracket - It is not necessary or recommended to use tools.
Drill a 2-1/8” (55mm) mounting hole where you desire to mount the instrument (Figure 1).
Connect the various wires from Cable 1 and Cable 2 as shown in Figures 2 and Figure 3.
Carefully check all your wiring against figures 2 and 3 and then mount the instrument in the hole. Use only finger tension to tighten the bracket
hold-down nuts
Figure 3
Bulkhead Gasket
Mounting Bracket
2 1/8" (55mm) Hole
Finger Tighten Only - Do Not Use Tools
Figure 1
Cable #1
Cable #2
RED #1 - Battery
BLUE #1 - AC Volts (from VT)
BLUE #2 - LIGHTS On/Off
WHITE #2 - NMEA 0183 out
GREEN #1 - Signal Ground
YELLOW #1 - Amps (fromCT)
BLACK #1 - Power Ground
Figure 2
ELECTRONIC POWER PRODUCTS
COMMUNICATION • NAVIGATION
P.O. Box 1306, Newport Beach, California 92663 • Phone: 714-751-0488 • Fax: 714-957-1621 • E-Mail: sales@newmarpower.com
www.newmarpower.com
Operation
Key Functions
The
6
,
+
,
5
(V, A, F) and * keys are used to select what to
display, set backlight levels, calibrate volts/amps/frequency,
turn alarms on/off, set alarms and set/change constants. New
information is automatically saved to non-volatile memory.
Turning Alarms ON/OFF
Press the
5
key 1/2 second to turn alarms ON. In Voltage mode,
the alarm icon will light. Press the
6
key 1/2 second to turn the
alarms OFF.
Backlight Intensity
Press
+
the key 1/2 second to adjust the backlight level for night
viewing. Each time you press the
+
key 1/2 second, the level will
get brighter 1, 2, 3, 4, OFF, 1, 2, ... etc. The blue backlight ON/
OFF control wire in cable #2 must be switched to +12/24V for the
backlights to work.
Display Volts/Amps/Frequency/kW
Quick press the V, A, or F key to select Voltage, Amps or Frequency
display. To display Killowats, press the V and A keys simultaneously.
Setting High Volts Alarm
While viewing Volts, press and hold the s key for ten (10) seconds until you
hear a long beep. The High Volts alarm value will be displayed. Use the 6
and 5 keys to set the desired alarm value. Press the + key to save the
High Volts alarm value to memory.
Setting Low Volts Alarm
While viewing Volts, press and hold the q key for ten (10) seconds until you
hear a long beep. The Low Volts alarm value will be displayed. Use the 6
and 5 keys to set the desired alarm value. Press the + key to save the
Low Volts alarm value to memory.
Setting High Frequency Alarm
While viewing Frequency, press and hold the p key for ten (10) seconds
until you hear a long beep. The High Frequency alarm value will be
displayed. Use the 6 and s keys to set the desired alarm value. Press the
+ key to save the High Frequency alarm value to memory.
Setting Low Frequency Alarm
While viewing Frequency, press and hold the q key for ten (10) seconds
until you hear a long beep. The Low Frequency alarm value will be
displayed. Use the 6 and 5 keys to set the desired alarm value. Press
the + key to save the Low Frequency alarm value to memory.
Setting High Killowatts Alarm
Press the V and A keys simultaneously to view the kW display. While
viewing kW, press and hold the s key for ten (10) seconds. You will hear a
beep and the High kW alarm value will be displayed. Use the q and p keys
to set the desired alarm value. Press the Ì key to save the High kW alarm
value to memory.
Calibrating the Voltmeter
The VAF110 is calibrated at time of manufacture, but can be calibrated
using the front panel keys. To calibrate the voltmeter, press and hold the V
and * keys for 10 seconds (until you hear a long beep) to enter into voltage
calibration mode. Use the q and p keys to make the displayed value read
correctly. Press the + key to save the calibration data to memory.
Auto-Zeroing the Ammeter
Press the A key to display amps. Then press and hold the A key for 10
seconds (until you hear a long beep) to auto-zero the ammeter.
Calibrating the Ammeter
To calibrate amps, press and hold the A and * keys for 10 seconds (until
you hear a long beep) to enter into amps calibration mode. Pass a known
amount of current through the current transformer (CT) and use the 6
and 5 keys to make the displayed value read correctly. Press the + key
to save the calibration data to memory. A reasonably high value of current
should be used (30 amps minimum) to obtain an accurate calibration.
Calibrating Frequency
To calibrate frequency, press and hold the F and * keys for 10 seconds
(until you hear a long beep) to enter into frequency calibration mode. Using
a known frequency, press the 6 and 5 keys to make the displayed value
read correctly. Press the + key to save the calibration data to memory.
NMEA 0183 Sentences
The VAF110 outputs serial data of voltage, amps, frequency and kW in
NMEA 0183 format. The sentences are output in the following formats:
Volts: $IIXDR,U,xxx,V,VAF30,*CS
Amps: $IIXDR,I,yyy,A,VAF30,*CS
Frequency: $IIXDR,F,zz.z,H,VAF30,*CS
kW: $IIXDR,G,aa.a,,VAF30,*CS
*CS = Check Sum
Selecting NMEA 0183 or External Alarm Output
The NMEA 0183 serial data line can be programmed to function as an
external generator cut-off switch. In this way the generator can be shut
down automatically if the voltage or frequency falls outside the alarm
ranges set by the user.
To toggle the data line between NMEA 0183 and Generator Shut-Off, press
and hold down both the 6 and 5 keys for 10 seconds (until you hear
a long beep). The new output mode is automatically saved to memory. A
5V signal in series with 270 ohms (10 mA Max.) is output to the generator
shut-down circuitry whenever an alarm condition exists and the alarms are
enabled (armed).
Notes and Warnings
a) During calibration or setting of alarm values, pressing and holding down
the 6 or 5 keys will cause the values to scroll faster the longer you hold
down the keys.
Specifications
Power supply: 9.50 to 33.00 VDC, .037 amps nominal
Operating temperature: 32 to 122 F ( 0 to 50 C)
Size: 4.3” x 4.3” x 3.5” deep (110 x 110 x 89 mm).
Display Data: AC Volts, AC Amps, Frequency, Kilowatts
Resolution: 1 VAC, 1 amp, 0.1 kW
Accuracy: Better than 1% for volts and 2% +/-1 digit for amps, .05% for
frequency. Volts, amps, frequency all front panel adjustable.
Ranges: 90 to 300 VAC
0 - 150 Amps AC
30 - 100 Hz
0 - 45.0 kW
Supplied Transducers: Voltage and Current transformers
Alarms: High/Low Voltage, High & Low Frequency, High kW
Display: 4 digit LCD, 5 levels of backlighting.
NMEA 0183: $IIXDR,U,xxx,V,VAF30,*CS for Volts
$IIXDR,I,yyy,A,VAF30,*CS for Amps
$IIXDR,F,zz.z,H,VAF30,*CS for Frequency
$IIXDR,G,aa.a,,VAF30,*CS for Kw
Generator Control: NMEA 0183 line programmable as automatic
generator shut-down control if generator volts/frequency/kW out of range.

Other NewMar Measuring Instrument manuals

NewMar DCV User manual

NewMar

NewMar DCV User manual

NewMar SPM-200 User manual

NewMar

NewMar SPM-200 User manual

NewMar DCE User manual

NewMar

NewMar DCE User manual

Popular Measuring Instrument manuals by other brands

AutoTest Battery Analyzer user manual

AutoTest

AutoTest Battery Analyzer user manual

Sensor Therm METIS M311 user manual

Sensor Therm

Sensor Therm METIS M311 user manual

Isotech SLM 52N instruction manual

Isotech

Isotech SLM 52N instruction manual

AU Tool X90 user manual

AU Tool

AU Tool X90 user manual

Check-line TI-25DL user manual

Check-line

Check-line TI-25DL user manual

Alarmcom Aeon Labs HEM installation guide

Alarmcom

Alarmcom Aeon Labs HEM installation guide

Check-line MKM user manual

Check-line

Check-line MKM user manual

Aquametro CONTOIL Series Spare Parts - Repair - Maintenance

Aquametro

Aquametro CONTOIL Series Spare Parts - Repair - Maintenance

MPFiltri CML4 Operation manual

MPFiltri

MPFiltri CML4 Operation manual

AutoMeter Spek Pro Programming instructions

AutoMeter

AutoMeter Spek Pro Programming instructions

Challenger Optics CO-OPM-10 operating manual

Challenger Optics

Challenger Optics CO-OPM-10 operating manual

Tek-Trol TEK-DP1620A instruction manual

Tek-Trol

Tek-Trol TEK-DP1620A instruction manual

Unit UTE9802+ user manual

Unit

Unit UTE9802+ user manual

i-PRO WJ-NX310K Series Important information

i-PRO

i-PRO WJ-NX310K Series Important information

Electronics International Inc SR-8A Operating and installation instructions

Electronics International Inc

Electronics International Inc SR-8A Operating and installation instructions

Bin Master SMARTBOB TS1 Installation and operating instructions

Bin Master

Bin Master SMARTBOB TS1 Installation and operating instructions

AimTTi RM420 instructions

AimTTi

AimTTi RM420 instructions

MPFiltri DEH Series Operator's guide

MPFiltri

MPFiltri DEH Series Operator's guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.