Caution For Division 2 and Zone 2 applications,
connected voltage sources must be within 60 VDC to
earth ground.
Caution For Division 2 and Zone 2 applications,
install a protection device between the input signal and
the NI 9238 input terminal. The device must clamp all
voltage sources to no more than 40% above their rated
value or within 84 VDC to earth ground if there is a
transient overvoltage condition.
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9238 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO Certificate No. 12 ATEX 1202658X and is
IECEx UL 14.0089X certified. Each NI 9238 is marked II 3G
and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI 9238
in Gas Group IIC hazardous locations, you must use the device in
an NI chassis that has been evaluated as Ex nC IIC T4, Ex IIC
T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Caution You must make sure that transient
disturbances do not exceed 140% of the rated voltage.
8| ni.com | NI 9238 Getting Started Guide