ParameterReferenceGuide
Unidrive M700
RegenerationMode
Issue: 01.16.01 (Eth 01.07.00)

About Parameter Reference Guide
The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional
operating parameters of the equipment or from mismatching the variable speed drive with the motor.
The contents of this guide are believed to be correct at the time of printing. In the interests of a commitment to a policy of continuous development and
improvement, the manufacturer reserves the right to change the specification of the product or its performance, or the contents of the guide, without
notice.
All rights reserved. No parts of this guide may be reproduced or transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by an information storage or retrieval system, without permission in writing from the publisher.
Copyright © July 2017 Control Techniques Ltd
Issue Number: 01.16.01 (Eth 01.07.00)
Unidrive M700 Firmware Version: V01.16.01.00
Slot 4 (Ethernet) Firmware Version: V01.07.00.24
Unidrive M700 Project Last Modified: 21-Jul-2017 10:57:25
Slot 4 (Ethernet) Project Last Modified: 29-Feb-2016 13:34:17
HTML Generator Version: 3.4.2.24481
2Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

Parameter mm.000
Parametermm.000 (mm.000) is one parameter that can be accessed from every drive menu so that the user can initiate various actions by setting a
value in this parameter and then performing a drive reset. If the action is completed successfully parameter mm.000 is cleared when the action is
complete. If the action is not started because the value does not correspond to an action, or because the action is not allowed (i.e. an attempt is made
to load defaults and the drive is enabled), parameter mm.000 is not cleared. If the action is started and then fails a trip is produced and parameter
mm.000 is not cleared.
There could be some conflict between the actions of Parametermm.000 (mm.000) and ParameterCloning (11.042) when the drive is reset. If
ParameterCloning (11.042) has a value of 1 or 2 and a valid action is required from the value of parameter mm.000 then only the action required by
parameter mm.000 is performed, but on successful completion of the action both parameters are cleared. If ParameterCloning (11.042) has any other
value it is not affected.
The table below shows the possible actions that can be initiated with Parametermm.000 (mm.000).
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 3

Parameter
mm.000
(mm.000)
value
Action Possible failures
1000 Save drive user save parameters to non-volatile memory.
Power-down save parameters are saved when the drive enters
the under voltage state.
No action if the drive is in the under voltage state (i.e.
UnderVoltageActive (10.016)), or LowUnderVoltageThresholdSelect
(06.067) =1 or BackupSupplyModeEnable (06.068) = 1 or
UserSupplySelect (06.072).
1001
Save drive parameters to non-volatile memory. It should be
noted that power-down save parameters are also saved which
will result in one background task scan being extended to
100ms.
1070 Reset all option modules
1233 Load 50Hz defaults No action if the drive is enabled
1234 Load 50Hz defaults to all menus except option module menus
(i.e 15 to 20 and 24 to 28) No action if the drive is enabled
1244 Load 60Hz defaults No action if the drive is enabled
1245 Load 60Hz defaults to all menus except option module menus
(i.e 15 to 20 and 24 to 28) No action if the drive is enabled
1253 Change drive mode and load 50Hz defaults No action if the drive is enabled
1254 Change drive mode and load 60Hz defaults No action if the drive is enabled
1255 Change drive mode and load 50Hz defaults except for menus
15 to 20 and 24 to 28 No action if the drive is enabled
1256 Change drive mode and load 60Hz defaults except for menus
15 to 20 and 24 to 28 No action if the drive is enabled
1299 Reset StoredHF trip.
2001 Create a boot file on a non-volatile media card based on the
present drive parameters including all Menu 20 parameters Non-volatile media card trips
4xxx NV media card: Transfer the drive parameters to parameter file
xxx Non-volatile media card trips
5xxx NV media card: Transfer the onboard user program to onboard
user program file xxx Non-volatile media card trips
6xxx NV media card: Load the drive parameters from parameter file
xxx or the onboard user program from onboard user program
file xxx
No action if the drive is enabled
Non-volatile media card trips
7xxx NV media card: Erase file xxx Non-volatile media card trips
8xxx NV Media card: Compare the data in the drive with file xxx Non-volatile media card trips
9555 NV media card: Clear the warning suppression flag Non-volatile media card trips
9666 NV media card: Set the warning suppression flag Non-volatile media card trips
9777 NV media card: Clear the read-only flag Non-volatile media card trips
9888 NV media card: Set the read-only flag Non-volatile media card trips
9999 NV media card: Erase and format the NV media card Non-volatile media card trips
110S0
Transfer electronic nameplate motor object parameters from
the drive to an encoder connected to the drive or an option
module.
The data is stored in the extended format. S defines the target
encoder as follows:
0=Drive P1
1=Option slot 1 P1
2=Option slot 2 P1
3=Option slot 3 P1
4=Option slot 4 P1
5=Drive P2
6=Option slot 1 P2
7=Option slot 2 P2
8=Option slot 3 P2
9=Option slot 4 P2
P1 is position interface 1 and P2 is position interface 2.
No action if the position feedback device is not suitable for electronic
nameplate storage, or the drive is enabled and the position feedback
device does not support data transfer and position feedback
simultaneously.
NamePlate.003 trip if there is insufficient storage space in the position
feedback device to hold the extended format tables.
110S1 Transfer electronic nameplate motor object parameters from an
encoder connected to the drive or option module to the drive
parameters. S defines the source as given above.
No action if the drive is enabled.
NamePlate.001 trip if the position feedback devices does not support
this feature
NamePlate.002 if there is an error in the data read from the encoder.
110S2 As 110S0, but for performance object 1 See 110S0
110S3 As 110S1, but for performance object 1 See 110S1
110S4 As 110S0, but for performance object 2 See 110S0
110S5 As 110S1, but for performance object2 See 110S1
110S6 Transfer electronic nameplate motor object parameters from
the drive to an encoder connected to the drive or an option
module in the Unidrive SP format.
12000 Only display parameters that are different from their default
value. This action does not require a drive reset.
12001 Only display parameters that are used to set-up destinations
(i.e. DE format bit is 1). This action does not require a drive
reset.
4Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

15xxx Transfer the user program in an option module fitted in slot 1 to
a non-volatile media card file xxx Non-volatile media card trips
16xxx As 15xxx, but for option slot 2 See 15xxx
17xxx As 15xxx, but for option slot 3 See 15xxx
18xxx Transfer the user program from file xxx in a non-volatile media
card to an option module fitted in slot 1. No action if the drive is enabled
Non-volatile media card trips
19xxx As 18xxx, but for option slot 2 See 18xxx
20xxx As 18xxx, but for option slot 3 See 18xxx
21xxx As 15xxx, but for option slot 4 See 15xxx
22xxx As 18xxx, but for option slot 4 See 18xxx
59999
Deletes an onboard user program if a program is present.
Note: Any parameter changes that have not been saved will be
lost during this action.
No action if the drive is enabled.
No action if there is no program present.
No action if the user program is enabled (i.e.
OnboardUserProgram:Enable (11.047) = 1)
Parametermm.000 (mm.000) values from 1 to 14 are equivalent to other values as shown in the table below to allow easy access to some commonly
used functions. For 0 and each of these values the keypad provides a string as shown.
Value String Equivalent value Action
0[No Action] 0
1 [Save parameters] 1001 Save drive parameters to non-volatile memory
2 [Load file 1] 6001 Load the data from file 1 on a non-volatile media card into the drive provided it is a parameter file
3 [Save to file 1] 4001 Store the drive parameters in file 1 on a non-volatile media card
4 [Load file 2] 6002 Load the data from file 2 on a non-volatile media card into the drive provided it is a parameter file
5 [Save to file 2] 4002 Store the drive parameters in file 2 on a non-volatile media card
6 [Load file 3] 6003 Load the data from file 3 on a non-volatile media card into the drive provided it is a parameter file
7 [Save to file 3] 4003 Store the drive parameters in file 3 on a non-volatile media card
8 [Show non-default] 12000 Only display parameters that are different from their default value
9[Destinations] 12001 Only display parameters that are used to set-up destinations
10 [Reset 50Hz defs] 1233 Load 50Hz defaults
11 [Reset 60Hz defs] 1244 Load 60Hz defaults
12 [Reset modules] 1070 Reset all option modules
13 [Read Enc. NP P1] 11001 Encoder electronic nameplate transfer from the encoder connected to drive P1 interface to the drive.
14 [Read Enc. NP P2] 11051 Encoder electronic nameplate transfer from the encoder connected to drive P2 interface to the drive.
Saving drive parameters
User-save and power-down save drive parameters are stored in non-volatile memory within the drive. Any values that have changed are copied to this
memory under the following conditions.
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 5

Parameter type Conditions for copy to non-volatile memory
User-save parameter
not visible in menu 0
Drive reset with 1000 in Parametermm.000 (mm.000) if the drive is not in the under voltage state and the standard under
voltage threshold is being used (i.e. LowUnderVoltageThresholdSelect (06.067) = 0).
OR
A drive reset with 1001 in Parametermm.000 (mm.000).
OR
After parameters are transferred from a non-volatile media card.
OR
After the drive mode is changed.
OR
After default parameters are loaded.
OR
After parameters are transferred from an electronic nameplate.
User save parameter
visible in menu 0
Under the conditions given above for user save parameters not visible in Menu 0.
OR
If the keypad is in edit mode for a user-save parameter in Menu 0, the parameter is saved when the keypad mode is
changed from edit mode.
Power-down save
parameter
A drive reset with 1000 in Parametermm.000 (mm.000) if the drive is not in the under voltage state and the standard under
voltage threshold is being used (i.e. LowUnderVoltageThresholdSelect (06.067) = 0).
OR
A drive reset with 1001 in Parametermm.000 (mm.000).
OR
On the transition into the under voltage state when the standard under voltage threshold is being used (i.e.
LowUnderVoltageThresholdSelect (06.067) is zero).
OR
After the drive mode is changed.
OR
After parameters are transferred from a non-volatile media card which results in the drive mode changing.
It can take some time for parameter data to be copied to non-volatile memory, especially if there are a large number of differences between the
parameter values in the drive and the values stored in the memory. Saving Power-down save parameters takes a maximum of 300ms, but saving user-
save parameters can take several seconds. If the drive is powered from a 24V control supply, or from a low voltage supply, the power down time of the
control system can be very short and there is a risk that either the stored values of the power-down save or user-save parameters could be corrupted.
This would result in an EEPROMFail trip at the next power-up. To reduce this risk, the power-down save and user-save parameters are each stored in
two banks. The banks are alternated each time a save is performed and the bank pointer is only updated once the save is complete. If the new bank is
corrupted a UserSave or PowerDownSave is initiated at the next power-up indicating an error in the user-save or power-down save data respectively,
and the data from the old bank is used. The following points should be noted:
1. If a UserSave or PowerDownSave trip occur at power-up then parameter changes made before power down will be lost. To clear these trips a
parameter save must be performed. If both the user-save and power-down save data is corrupted then a PowerDownSave trip is produced.
2. When a Menu 0 parameter is changed its value is saved immediately to the active bank and the bank pointer is not changed. Therefore
changes made via Menu 0 are not lost if a UserSave trip occurs at power-up.
3. When the drive mode changes all the data in both banks in the non-volatile memory is cleared and the default parameters are saved in both
banks. Therefore there is an extended parameter saving period immediately after a drive mode change.
4. Two banks are not provided in non-volatile media cards therefore the card could be corrupted if the power is removed when the drive is writing
data to the card.
Loading defaults
A drive reset with 1233 in Parametermm.000 (mm.000) loads the defaults defined for each parameter. If defaults are loaded with 1244 in Parameter
mm.000 (mm.000) then the parameters in the table below have different defaults that are intended for the 60Hz regions.
Parameter Default Drive modes Drive voltage rating
Maximumreferenceclamp (01.006) 60.0Hz Open-loop All
Maximumreferenceclamp (01.006) 1800rpm RFC-A All
StandardRampVoltage (02.008) 775V Open-loop, RFC-A, RFC-S 400V
RatedFrequency (05.006) 60.0Hz Open-loop, RFC-A All
RatedLoadrpm (05.008) 1800rpm Open-loop All
RatedLoadrpm (05.008) 1770rpm RFC-A All
RatedVoltage (05.009) 460V Open-loop, RFC-A, RFC-S 400V
M2MaximumReferenceClamp (21.001) 60.0Hz Open-loop All
M2MaximumReferenceClamp (21.001) 1800rpm RFC-A All
M2RatedFrequency (21.006) 60.0Hz Open-loop, RFC-A All
M2RatedLoadrpm (21.008) 1800rpm Open-loop All
M2RatedLoadrpm (21.008) 1770rpm RFC-A All
M2RatedVoltage (21.009) 460V Open-loop, RFC-A, RFC-S All
6Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

Non-volatile media card data transfer
Details of the data that can be stored on a non-volatile media card and the methods to transfer/access this data are given in Menu 11.
Stored HF trips
When the drive is subsequently powered up a StoredHF trip is initiated where the sub-trip number is the number of the HF trip that last occurred. This
trip will occur at every power-up until it is reset. The trip can only be reset by first entering 1299 into Parametermm.000 (mm.000). If the drive is
powered up and a StoredHF trip occurs, OnboardUserProgram:Enable (Pr 11.047) is reset to zero to prevent the on-board user program from
running. This ensures that the user program can be changed or erased in case it causes an HF trip at every power-up. Once the StoredHF is cleared, it
is necessary to power cycle the drive or to re-download the user program to allow the program to restart.
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 7

Current Ratings
The tables below give the maximum output current ratings, peak current ratings and power ratings for all drive sizes and voltage ratings.
200V Rated Drives
Model
Heavy Duty Normal Duty
Kc
Rated
Current Motor Shaft Power
Peak
Current
Open Loop
Peak
Current RFC
Rated
Current Motor Shaft Power Peak
Current
A kW hp A A A kW hp A A
03200050 5 0.75 1 7.5 10 6.6 1.1 1.5 7.26 11.111
03200066 6.6 1.1 1.5 9.9 13.2 8 1.5 2 8.8 14.667
03200080 8 1.5 2 12 16 11 2.2 3 12.1 17.778
03200106 10.6 2.2 3 15.9 21.2 12.7 3 3 13.97 23.556
04200137 13.7 3 3 20.55 27.4 18 4 5 19.8 30.444
04200185 18.5 4 5 27.75 37 25 5.5 7.5 27.5 41.111
05200250 25 5.5 7.5 37.5 50 30 7.5 10 33 55.556
06200330 33 7.5 10 49.5 66 50 11 15 55 73.333
06200440 44 11 15 66 88 58 15 20 63.8 97.778
07200610 61 15 20 91.5 122 75 18.5 25 82.5 135.556
07200750 75 18.5 25 112.5 150 94 22 30 103.4 166.667
07200830 83 22 30 124.5 166 117 30 40 128.7 184.444
08201160 116 30 40 174 232 149 37 50 163.9 257.778
08201320 132 37 50 198 264 180 45 60 198 293.333
09201760 176 45 60 264 308 216 55 75 237.6 342.222
09202190 219 55 75 328.5 383.25 266 75 100 292.6 425.833
10202830 283 75 100 424.5 495.25 325 90 125 357.5 550.278
10203000 300 90 125 450 525 360 110 150 396 583.333
400V Rated Drives
Model
Heavy Duty Normal Duty
Kc
Rated
Current Motor Shaft Power
Peak
Current
Open Loop
Peak
Current RFC
Rated
Current Motor Shaft Power Peak
Current
A kW hp A A A kW hp A A
03400025 2.5 0.75 1 3.75 5 3.4 1.1 1.5 3.74 5.556
03400031 3.1 1.1 1.5 4.65 6.2 4.5 1.5 2 4.95 6.889
03400045 4.5 1.5 2 6.75 9 6.2 2.2 3 6.82 10
03400062 6.2 2.2 3 9.3 12.4 7.7 3 5 8.47 13.778
03400078 7.8 3 5 11.7 15.6 10.4 4 5 11.44 17.333
03400100 10 4 5 15 20 12.3 5.5 7.5 13.53 22.222
04400150 15 5.5 10 22.5 30 18.5 7.5 10 20.35 33.333
04400172 17.2 7.5 10 25.8 34.4 24 11 15 26.4 38.222
05400270 27 11 20 40.5 54 30 15 20 33 60
05400300 30 15 20 45 60 31 15 20 34.1 66.667
06400350 35 15 25 52.5 70 38 18.5 25 41.8 77.778
06400420 42 18.5 30 63 84 48 22 30 52.8 93.333
06400470 47 22 30 70.5 94 63 30 40 69.3 104.444
07400660 66 30 50 99 132 79 37 50 86.9 146.667
07400770 77 37 60 115.5 154 94 45 60 103.4 171.111
07401000 100 45 75 150 200 112 55 75 123.2 222.222
08401340 134 55 100 201 268 155 75 100 170.5 297.778
08401570 157 75 125 235.5 314 184 90 125 202.4 348.889
09402000 200 90 150 300 350 221 110 150 243.1 388.889
09402240 224 110 150 336 392 266 132 200 292.6 435.556
10402700 270 132 200 405 472.5 320 160 250 352 525
10403200 320 160 250 480 560 361 200 300 397.1 622.222
11403770 377 185 300 565.5 659.75 437 225 350 480.7 733.056
11404170 417 200 350 625.5 729.75 487 250 400 535.7 810.833
11404640 464 250 400 696 812 507 315 450 557.7 902.222
575V Rated Drives
8Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

Model
Heavy Duty Normal Duty
Kc
Rated
Current Motor Shaft Power
Peak
Current
Open Loop
Peak
Current RFC
Rated
Current Motor Shaft Power Peak
Current
A kW hp A A A kW hp A A
05500030 3 1.5 2 4.5 6 3.9 2.2 3 4.29 6.667
05500040 4 2.2 3 6 8 6.1 4 5 6.71 8.889
05500069 6.9 4 5 10.35 13.8 10 5.5 7.5 11 15.333
06500100 10 5.5 7.5 15 20 12 7.5 10 13.2 22.222
06500150 15 7.5 10 22.5 30 17 11 15 18.7 33.333
06500190 19 11 15 28.5 38 22 15 20 24.2 42.222
06500230 23 15 20 34.5 46 27 18.5 25 29.7 51.111
06500290 29 18.5 25 43.5 58 34 22 30 37.4 64.444
06500350 35 22 30 52.5 70 43 30 40 47.3 77.778
07500440 44 30 40 66 88 53 45 50 58.3 97.778
07500550 55 37 50 82.5 110 73 55 60 80.3 122.222
08500630 63 45 60 94.5 126 86 75 75 94.6 140
08500860 86 55 75 129 172 108 90 100 118.8 191.111
09501040 104 75 100 156 182 125 110 125 137.5 202.222
09501310 131 90 125 196.5 229.25 150 110 150 165 254.722
10501520 152 110 150 228 266 200 130 200 220 295.556
10501900 190 132 200 285 332.5 200 150 200 220 369.444
11502000 200 150 200 300 350 248 175 250 272.8 388.889
11502540 254 185 250 381 444.5 288 225 300 316.8 493.889
11502850 285 225 300 427.5 498.75 315 250 350 346.5 554.167
690V Rated Drives
Model
Heavy Duty Normal Duty
Kc
Rated
Current Motor Shaft Power
Peak
Current
Open Loop
Peak
Current RFC
Rated
Current Motor Shaft Power Peak
Current
A kW hp A A A kW hp A A
07600190 19 15 20 28.5 38 23 18.5 25 25.3 42.222
07600240 24 18.5 25 36 48 30 22 30 33 53.333
07600290 29 22 30 43.5 58 36 30 40 39.6 64.444
07600380 38 30 40 57 76 46 37 50 50.6 84.444
07600440 44 37 50 66 88 52 45 60 57.2 97.778
07600540 54 45 60 81 108 73 55 75 80.3 120
08600630 63 55 75 94.5 126 86 75 100 94.6 140
08600860 86 75 100 129 172 108 90 125 118.8 191.111
09601040 104 90 125 156 182 125 110 150 137.5 202.222
09601310 131 110 150 196.5 229.25 155 132 175 170.5 254.722
10601500 150 132 175 225 262.5 172 160 200 189.2 291.667
10601780 178 160 200 267 311.5 197 185 250 216.7 346.111
11602100 210 185 250 315 367.5 225 200 250 247.5 408.333
11602380 238 200 250 357 416.5 275 250 300 302.5 462.778
11602630 263 250 300 394.5 460.25 305 315 400 335.5 511.389
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 9

Variable Minimum / Maximum Pairs
The descriptions below define the variable minimum/maximum pairs that can be used with parameters when the VM format bit is set. The variable
minimum and maximum themselves can be dependent on other parameters, or the drive rating or other conditions as defined. The variable minimum
and the variable maximum have a limited range and this is defined for each minimum/maximum pair.
Identifier VM_AC_VOLTAGE
Description Range applied to parameters showing a.c. voltage
Units V
Range of [MIN] 0
Range of [MAX] 0 to 930
VM_AC_VOLTAGE[MAX] in drive voltage rating dependent. See the table below.
Voltage level 200V 400V 575V 690V
VM_AC_VOLTAGE[MAX] 325 650 780 930
VM_AC_VOLTAGE[MIN] = 0
Identifier VM_AC_VOLTAGE_SET
Description Range applied to a.c. voltage set-up parameters
Units V
Range of [MIN] 0
Range of [MAX] 0 to 765
VM_AC_VOLTAGE_SET[MAX] is drive voltage rating dependent. See the table below.
Voltage level 200V 400V 575V 690V
VM_AC_VOLTAGE_SET[MAX] 265 530 635 765
VM_AC_VOLTAGE_SET[MIN] = 0
Identifier VM_ACCEL_RATE
Description Maximum applied to the ramp rate parameters
Units s/100Hz, s/1000rpm, s/1000mm/s
Range of [MIN] Open-loop: 0.0
RFC-A, RFC-S: 0.000
Range of [MAX] Open-loop: 0.0 to 3200.0
RFC-A, RFC-S: 0.000 to 3200.000
A maximum needs to be applied to the ramp rate parameters because the units are a time for a change of speed from zero to a defined level or to
maximum speed. The defined level is 100Hz for Open-loop mode and 1000rpm or 1000mm/s for RFC-A and RFC-S modes. If the change of speed is to
the maximum speed then changing the maximum speed changes the actual ramp rate for a given ramp rate parameter value. The variable maximum
calculation ensures that longest ramp rate (parameter at its maximum value) is not slower than the rate with the defined level, i.e. 3200.00 s / Hz for
Open-loop mode, and 3200.000 s / 1000rpm or 3200.000 s / 1000mm/s for RFC-A and RFC-S modes.
The maximum frequency/speed is taken from MaximumReferenceClamp (01.006) if SelectMotor2Parameters (11.045) = 0, or M2Maximum
ReferenceClamp (21.001) if SelectMotor2Parameters (11.045) = 1.
Open-loop mode
VM_ACCEL_RATE[MIN] = 0.0
If RampRateUnits (02.039) = 0:
VM_ACCEL_RATE[MAX] = 3200.0
Otherwise:
VM_ACCEL_RATE[MAX] = 3200.0 x Maximum frequency / 100.0
RFC-A, RFC-S modes
VM_ACCEL_RATE[MIN] = 0.000
If RampRateUnits (02.039) = 0:
VM_ACCEL_RATE[MAX] = 3200.000
Otherwise:
VM_ACCEL_RATE[MAX] = 3200.000 x Maximum speed / 1000.0
Identifier VM_AMC_JERK_UNIPOLAR
Description Range applied to the parameters showing the AMC jerk
Units User units / ms / ms / ms
Range of [MIN] 0
Range of [MAX] 107374.1823
VM_AMC_JERK_UNIPOLAR[MAX] = 107374.1823 / AMCAutoResolutionScaling(31.016)
VM_AMC_JERK_UNIPOLAR[MIN] = 0
10 Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

AMC Roll Over Limit (31.010) = 0 > 0
VM_AMC_POSITION[MAX] 2147483647 / AMCAutoResolutionScaling(31.016) AMCRollOverLimit (31.010) - 1
VM_AMC_POSITION[MIN] -2147483648 / AMCAutoResolutionScaling(31.016) 0
AMC Roll Over Limit (31.010) = 0 > 0
VM_AMC_POSITION_CAM[MAX] 1073741823 / AMCAutoResolutionScaling(31.016) AMCRollOverLimit (31.010) - 1
VM_AMC_POSITION_CAM[MIN] -1073741824 / AMCAutoResolutionScaling(31.016) -AMCRollOverLimit (31.010) + 1
AMC Roll Over Limit (31.010) = 0 > 0
VM_AMC_POSITION_CAM_UNIPOLAR[MAX] 1073741823 / AMCAutoResolutionScaling(31.016) AMCRollOverLimit (31.010) - 1
VM_AMC_POSITION_CAM_UNIPOLAR[MIN] 0 0
AMC Roll Over Limit (31.010) = 0 > 0 > 0
AMC Rotary Mode (34.005) Not active < 4 = 4
VM_AMC_POSITION_REF[MAX] 2147483647 / AMCAutoResolution
Scaling(31.016) AMCRollOverLimit
(31.010) - 1 1073741823 / AMCAutoResolutionScaling
(31.016)
VM_AMC_POSITION_REF[MIN] -2147483648 / AMCAutoResolution
Scaling(31.016) 0-1073741824 / AMCAutoResolution
Scaling(31.016)
Identifier VM_AMC_POSITION
Description Range applied to the parameters showing the AMC position
Units User units
Range of [MIN] -2147483648
Range of [MAX] 2147483647
VM_AMC_POSITION is modified by AMCAutoResolutionScaling(31.016) and AMCRollOverLimit (31.010). See the table below.
Identifier VM_AMC_POSITION_CAM
Description Range applied to the parameters showing the AMC cam position
Units User units
Range of [MIN] -1073741824
Range of [MAX] 1073741823
VM_AMC_POSITION_CAM is modified by AMCAutoResolutionScaling(31.016) and AMCRollOverLimit (31.010). See the table below.
Identifier VM_AMC_POSITION_CAM_UNIPOLAR
Description Unipolar version of VM_AMC_POSITION_CAM
Units User units
Range of [MIN] 0
Range of [MAX] 1073741823
VM_AMC_POSITION_CAM_UNIPOLAR is modified by AMCAutoResolutionScaling(31.016) and AMCRollOverLimit (31.010). See the table below.
Identifier VM_AMC_POSITION_REF
Description Range applied to the AMC position reference
Units User units
Range of [MIN] -2147483648
Range of [MAX] 2147483647
VM_AMC_POSITION_REF is modified by AMCAutoResolutionScaling(31.016), AMCRollOverLimit (31.010) and AMCRotaryMode (34.005). See
the table below.
Identifier VM_AMC_POSITION_UNIPOLAR
Description Unipolar version of VM_AMC_POSITION
Units User units
Range of [MIN] 0
Range of [MAX] 2147483647
VM_AMC_POSITION_UNIPOLAR is modified by AMCAutoResolutionScaling(31.016) and AMCRollOverLimit (31.010). See the table below.
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 11

AMC Roll Over Limit (31.010) = 0 > 0
VM_AMC_POSITION_UNIPOLAR[MAX] 2147483647 / AMCAutoResolutionScaling(31.016) AMCRollOverLimit (31.010) - 1
VM_AMC_POSITION_UNIPOLAR[MIN] 0 0
Identifier VM_AMC_RATE
Description Range applied to the parameters showing the AMC acceleration
Units User units / ms / ms
Range of [MIN] 1073742.824
Range of [MAX] 1073741.823
VM_AMC_RATE_UNIPOLAR[MAX] = 1073741.823 / AMCAutoResolutionScaling(31.016)
VM_AMC_RATE_UNIPOLAR[MIN] = 1073741.824 / AMCAutoResolutionScaling(31.016)
Identifier VM_AMC_RATE_UNIPOLAR
Description Unipolar version of VM_AMC_RATE
Units User units / ms / ms
Range of [MIN] 0
Range of [MAX] 1073741.823
VM_AMC_RATE_UNIPOLAR[MAX] = 1073741.823 / AMCAutoResolutionScaling(31.016)
VM_AMC_RATE_UNIPOLAR[MIN] = 0
Identifier VM_AMC_ROLLOVER
Description Maximum applied to the AMC Rollover parameter
Units User units
Range of [MIN] 0
Range of [MAX] 1073741823
VM_AMC_ROLLOVER[MAX] = 1073741823 / AMCAutoResolutionScaling(31.016)
VM_AMC_ROLLOVER[MIN] = 0
Identifier VM_AMC_SPEED
Description Range applied to the parameters showing the AMC speed
Units User units / ms
Range of [MIN] -21474836.48
Range of [MAX] 21474836.47
VM_AMC_SPEED[MAX] = 21474836.47 / AMCAutoResolutionScaling(31.016)
VM_AMC_SPEED[MIN] = -21474836.48 / AMCAutoResolutionScaling(31.016)
Identifier VM_AMC_SPEED_UNIPOLAR
Description Unipolar version of VM_AMC_SPEED
Units User units / ms
Range of [MIN] 0
Range of [MAX] 21474836.47
VM_SPEED_UNIPOLAR[MAX] = 21474836.47 / AMCAutoResolutionScaling(31.016)
VM_SPEED_UNIPOLAR[MIN] = 0
Identifier VM_DC_VOLTAGE
Description Range applied to d.c. voltage reference parameters
Units V
Range of [MIN] 0
Range of [MAX] 0 to 1190
VM_DC_VOLTAGE[MAX] is the full scale d.c. link voltage feedback (over voltage trip level) for the drive. This level is drive voltage rating dependent.
See the table below.
Voltage level 200V 400V 575V 690V
VM_DC_VOLTAGE[MAX] 415 830 990 1190
VM_DC_VOLTAGE[MIN] = 0
12 Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

Identifier VM_DC_VOLTAGE_SET
Description Range applied to d.c. voltage reference parameters
Units V
Range of [MIN] 0
Range of [MAX] 0.0 to 1150.0
VM_DC_VOLTAGE_SET[MAX] is drive voltage rating dependent. All values are shown in the table below.
Voltage level 200V 400V 575V 690V
VM_DC_VOLTAGE_SET[MAX] 400 800 955 1150
VM_DC_VOLTAGE_SET[MIN] = 0
Identifier VM_DRIVE_CURRENT
Description Range applied to parameters showing current in A
Units A
Range of [MIN] -99999.999 to 0.000
Range of [MAX] 0.000 to 99999.999
VM_DRIVE_CURRENT[MAX] is equivalent to the full scale (over current trip level) for the drive and is given by FullScaleCurrentKc (11.061).
VM_DRIVE_CURRENT[MIN] = - VM_DRIVE_CURRENT[MAX]
Identifier VM_DRIVE_CURRENT_UNIPOLAR
Description Unipolar version of VM_DRIVE_CURRENT
Units A
Range of [MIN] 0.000
Range of [MAX] 0.000 to 99999.999
VM_DRIVE_CURRENT_UNIPOLAR[MAX] = VM_DRIVE_CURRENT[MAX]
VM_DRIVE_CURRENT_UNIPOLAR[MIN] = 0.000
Identifier VM_HIGH_DC_VOLTAGE
Description Range applied to the parameters showing high d.c. voltage
Units V
Range of [MIN] 0
Range of [MAX] 0 to 1500
VM_HIGH_DC_VOLTAGE[MAX] = 1500. This is the full scale d.c. link voltage feedback for the high d.c. link voltage measurement which can measure
the voltage if it goes above the normal full scale value.
VM_HIGH_DC_VOLTAGE[MIN] = 0
Identifier VM_LOW_UNDER_VOLTS
Description Range applied to the low under voltage threshold
Units V
Range of [MIN] 24
Range of [MAX] 24 to 1150
If Back-upModeEnable (06.068) = 0
VM_LOW_UNDER_VOLTS[MAX] = VM_STD_UNDER_VOLTS[MIN]
Otherwise
VM_LOW_UNDER_VOLTS[MAX] = VM_STD_UNDER_VOLTS[MIN] / 1.1.
VM_LOW_UNDER_VOLTS[MIN] = 0.
Identifier VM_MIN_SWITCHING_FREQUENCY
Description Range applied to the minimum switching frequency parameter
Units User units
Range of [MIN] 0
Range of [MAX] 0 to 6
VM_MIN_SWITCHING_FREQUENCY[MAX] = MaximumSwitchingFrequency (05.018)
VM_MIN_SWITCHING_FREQUENCY[MIN] = 0 for motor control modes, or 1 for Regen mode (subject to the maximum)
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 13

Identifier VM_MOTOR1_CURRENT_LIMIT
Description Range applied to current limit parameters (motor 1)
Units %
Range of [MIN] 0.0
Range of [MAX] 0.0 to 1000.0
VM_MOTOR1_CURRENT_LIMIT[MAX] is dependent on the drive rating and motor set-up parameters.
VM_MOTOR1_CURRENT_LIMIT[MIN] = 0.00
Identifier VM_MOTOR2_CURRENT_LIMIT
Description Range applied to current limit parameters (motor 2)
Units %
Range of [MIN] 0.0
Range of [MAX] 0.0 to 1000.0
VM_MOTOR2_CURRENT_LIMIT[MAX] is dependent on the drive rating and motor set-up parameters.
VM_MOTOR2_CURRENT_LIMIT[MIN] = 0.0
Identifier VM_NEGATIVE_REF_CLAMP1
Description Limits applied to the negative frequency or speed clamp (motor 1)
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: -550.0 to 0.0
RFC-A, RFC-S: -50000.0 to 0.0
Range of [MAX] Open-loop: 0.0 to 550.0
RFC-A, RFC-S: 0.0 to 50000.0
This variable maximum/minimum defines the range of the negative frequency or speed clamp associated with motor map 1 (MinimumReferenceClamp
(01.007)). The minimum and maximum are affected by the settings of the NegativeReferenceClampEnable (01.008), BipolarReferenceEnable
(01.010) and MaximumReferenceClamp (01.006) as shown in the table below.
Negative
Reference
Clamp Enable
(01.008)
Bipolar
Reference
Enable
(01.010)
VM_NEGATIVE_REF_CLAMP1[MIN] VM_NEGATIVE_REF_CLAMP1[MAX]
0 0 0.0 Pr 01.006
0 1 0.0 0.0
1 X -VM_POSITIVE_REF_CLAMP[MAX] 0.0
Identifier VM_NEGATIVE_REF_CLAMP2
Description Limits applied to the negative frequency or speed clamp (motor 2)
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: -550.0 to 0.0
RFC-A, RFC-S: -50000.0 to 0.0
Range of [MAX] Open-loop: 0.0 to 550.0
RFC-A, RFC-S: 0.0 to 50000.0
This variable maximum/minimum defines the range of the negative frequency or speed clamp associated with motor map 2 (M2MinimumReference
Clamp (21.002)). It is defined in the same way as VM_NEGATIVE_REF_CLAMP1 except that the M2MaximumReferenceClamp (21.001) is used
instead of MaximumReferenceClamp (01.006).
Identifier VM_POSITIVE_REF_CLAMP1
Description Limits applied to the positive frequency or speed reference clamp
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: 0.0
RFC-A, RFC-S: 0.0
Range of [MAX] Open-loop: 550.0
RFC-A, RFC-S: 0.0 to 50000.0
VM_POSITIVE_REF_CLAMP1[MAX] defines the range of the positive reference clamp, MaximumReferenceClamp (01.006), which in turn limit the
references. In RFC-A and RFC-S modes a limit is applied so that the position feedback does not exceed the speed where the drive can no longer
interpret the feedback signal correctly as given in the table below. The limit is based on the position feedback device selected with MotorControl
FeedbackSelect (03.026). It is possible to disable this limit if the RFCFeedbackMode (03.024) ≥ 1 (i.e. VM_POSITIVE_REF_CLAMP = 50000.0), so
that the motor can be operated at a speed above the level where the drive can interpret the feedback in sensorless mode. It should be noted that the
position feedback device itself may have a maximum speed limit that is lower than those given in the table. Care should be taken not to exceed a speed
that would cause damage to the position feedback device.
14 Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

Feedback device VM_POSITIVE_REF_CLAMP1[MAX]
AB, AB Servo (500kHz x 60 / rotary lines per revolution) rpm
(500kHz x linear line pitch in mm) mm/s
FD, FR, FD Servo, FR Servo (500kHz x 60 / rotary lines per revolution)/2 rpm
(500kHz x linear line pitch in mm)/2 mm/s
SC, SC Hiper, SC EnDat, SC SSI, SC Servo (500kHz x 60 / sine waves per revolution) rpm
(500kHz x linear line pitch in mm) mm/s
Resolver 30000 rpm
(250Hz x pole pitch in mm) mm/s
Any other device 50000.0 rpm or mm/s
The limit ensures that the frequency of incremental digital or sine wave signals from the encoder do not exceed 500kHz and the modulation frequency
for a resolver does not exceed 1kHz, neglecting any speed controller overshoot. The position feedback resolution remains fixed over the whole
frequency for digital signals, but reduces with increased frequency or reduced voltage with sine wave signals. The position resolution with sine wave
signals is given by the equations below.
Position resolution for a rotary device = K x sine waves per revolution
Position resolution for a linear device = K x sine waves per pole pitch
The value of K varies with the frequency and magnitude of the sine wave signals. The nominal value of K is 1024, and the drive interface provides at
least this resolution with 1.0Vp-p sine waves up to a frequency of 50kHz. The table below shows the variation of K with sine wave peak to peak voltage
and frequency.
1kHz 5kHz 50kHz 100kHz 200kHz 500kHz
1.2Vp-p 2048 2048 1024 1024 512 512
1.0Vp-p 2048 2048 1024 512 512 128
0.8Vp-p 1024 1024 1024 512 256 128
0.6Vp-p 1024 1024 512 512 256 128
0.4Vp-p 512 512 512 256 128 64
VM_POSITIVE_REF_CLAMP[MAX] in Open-loop mode is fixed at 3000.0 as position feedback cannot be used for motor control.
VM_POSITIVE_REF_CLAMP[MIN] = 0.0
(Note: An additional limit is applied to ensure that the drive output frequency cannot exceed 550Hz. For Open-loop mode an additional limit of 550Hz is
applied directly. For RFC modes the variable maximum is applied to the speed reference, and an additional limit of 550 x 60 / Motor pole pairs is
applied.)
VM_POSITIVE_REF_CLAMP2[MAX] defines the range of the positive reference clamp, M2MaximumReferenceClamp (21.001), which in turn limit the
references. See VM_POSITIVE_REF_CLAMP1 for more details.
Identifier VM_POWER
Description Range applied to parameters that either set or display power
Units kW
Range of [MIN] -99999.999 to 0.000
Range of [MAX] 0.000 to 99999.999
VM_POWER[MAX] is rating dependent and is chosen to allow for the maximum power that can be output by the drive with maximum a.c. output
voltage, at maximum controlled current and unity power factor.
VM_POWER[MAX] = √3 x VM_AC_VOLTAGE[MAX] x VM_DRIVE_CURRENT[MAX] / 1000
VM_POWER[MIN] = -VM_POWER[MAX]
Identifier VM_RATED_CURRENT
Description Range applied to rated current parameters
Units A
Range of [MIN] 0.000
Range of [MAX] 0.000 to 99999.999
VM_RATED_CURRENT [MAX] = MaximumRatedCurrent (11.060) and is dependent on the drive rating.
VM_RATED_CURRENT [MIN] = 0.000
Identifier VM_REGEN_REACTIVE
Description Range applied to the reactive current reference in Regen mode
Units %
Range of [MIN] -1000.0 to 0.0
Range of [MAX] 0.0 to 1000.0
VM_REGEN_REACTIVE[MAX] applies a limit to the reactive current reference in Regen mode so that the total current reference does not exceed its
maximum allowed level.
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 15

VM_REGEN_REACTIVE[MIN] = - VM_REGEN_REACTIVE[MAX]
Identifier VM_SPEED
Description Range applied to parameters showing speed
Units Open-loop, RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop, RFC-A, RFC-S: -50000.0 to 0.0
Range of [MAX] Open-loop, RFC-A, RFC-S: 0.0 to 50000.0
This variable minimum/maximum defines the range of speed monitoring parameters. To allow headroom for overshoot the range is set to twice the
range of the speed references.
VM_SPEED[MIN] = 2 x VM_SPEED_FREQ_REF[MIN]
VM_SPEED[MAX] = 2 x VM_SPEED_FREQ_REF[MAX]
Identifier VM_SPEED_FREQ_KEYPAD_REF
Description Range applied to the keypad reference
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: -550.0 to 550.0
RFC-A, RFC-S: -50000.0 to 50000.0
Range of [MAX] Open-loop: 0.0 to 550.0
RFC-A, RFC-S: 0.0 to 50000.0
This variable maximum is applied to KeypadControlModeReference (01.017). The maximum applied to these parameters is the same as other
frequency reference parameters.
VM_SPEED_FREQ_USER_REFS [MAX] = VM_SPEED_FREQ_REF[MAX]
However the minimum is dependent on NegativeReferenceClampEnable (01.008) and BipolarReferenceEnable (01.010).
Negative Reference
Clamp Enable
(01.008)
Bipolar
Reference
Enable (01.010)
VM_SPEED_FREQ_USER_REFS[MIN]
0 0 If SelectMotor2Parameters (11.045) = 0 MinimumReference
Clamp (01.007), otherwise M2MinimumReferenceClamp (21.002)
0 1 -VM_SPEED_FREQ_REF[MAX]
1 0 0.0
1 1 -VM_SPEED_FREQ_REF[MAX]
Identifier VM_SPEED_FREQ_REF
Description Range applied to the frequency or speed reference parameters
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: -550.0 to 0.0
RFC-A, RFC-S: -50000.0 to 0.0
Range of [MAX] Open-loop: 0.0 to 550.0
RFC-A, RFC-S: 0.0 to 50000.0
This variable minimum/maximum is applied throughout the frequency and speed reference system so that the references can vary in the range from the
minimum to maximum clamps.
Negative
Reference Clamp
Enable (01.008)
VM_SPEED_FREQ_REF[MAX] if Select
Motor 2 Parameters (11.045) = 0
VM_SPEED_FREQ_REF[MAX] if Select
Motor 2 Parameters (11.045) = 1
0MaximumReferenceClamp (01.006) M2MaximumReferenceClamp (21.001)
1MaximumReferenceClamp (01.006) or
|MinimumReferenceClamp (01.007)|
whichever the larger
M2MaximumReferenceClamp (21.001) or
|M2 MinimumReferenceClamp (21.002)|
whichever the larger
VM_SPEED_FREQ_REF[MIN] = -VM_SPEED_FREQ_REF[MAX].
Identifier VM_SPEED_FREQ_REF_UNIPOLAR
Description Unipolar version of VM_SPEED_FREQ_REF
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: 0.0
RFC-A, RFC-S: 0.0
Range of [MAX] Open-loop: 0.0 to 550.0
RFC-A, RFC-S: 0.0 to 50000.0
VM_SPEED_FREQ_REF_UNIPOLAR[MAX] = VM_SPEED_FREQ_REF[MAX]
16 Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

VM_SPEED_FREQ_REF_UNIPOLAR[MIN] = 0.0
Identifier VM_SPEED_FREQ_USER_REFS
Description Range applied to analogue reference parameters
Units Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN] Open-loop: -550.00 to 550.00
RFC-A, RFC-S: -50000.0 to 50000.0
Range of [MAX] Open-loop: 0.0 to 550.00
RFC-A, RFC-S: 0.0 to 50000.0
This variable maximum is applied to AnalogueReference1 (01.036) and AnalogueReference2 (01.037). It should be noted that in Open-loop mode the
analogue reference parameters have two decimal places.
The maximum applied to these parameters is the same as other frequency reference parameters.
VM_SPEED_FREQ_USER_REFS [MAX] = VM_SPEED_FREQ_REF[MAX]
However the minimum is dependent on NegativeReferenceClampEnable (01.008) and BipolarReferenceEnable (01.010).
Negative Reference
Clamp Enable
(01.008)
Bipolar
Reference
Enable (01.010)
VM_SPEED_FREQ_USER_REFS[MIN]
0 0 If SelectMotor2Parameters (11.045) = 0 MinimumReference
Clamp (01.007), otherwise M2MinimumReferenceClamp (21.002)
0 1 -VM_SPEED_FREQ_REF[MAX]
1 0 0.0
1 1 -VM_SPEED_FREQ_REF[MAX]
Identifier VM_STD_UNDER_VOLTS
Description Range applied to the standard under voltage threshold
Units V
Range of [MIN] 0 to 1150
Range of [MAX] 0 to 1150
VM_STD_UNDER_VOLTS[MAX] = VM_DC_VOLTAGE_SET / 1.1
VM_STD_UNDER_VOLTS[MIN] is voltage rating dependent. See the table below.
Voltage level 200V 400V 575V 690V
VM_STD_UNDER_VOLTS[MIN] 175 330 435 435
Identifier VM_SUPPLY_LOSS_LEVEL
Description Range applied to the supply loss threshold
Units V
Range of [MIN] 0 to 1150
Range of [MAX] 0 to 1150
VM_SUPPLY_LOSS_LEVEL[MAX] = VM_DC_VOLTAGE_SET[MAX]
VM_SUPPLY_LOSS_LEVEL[MIN] is drive voltage rating dependent. See the table below.
Voltage level 200V 400V 575V 690V
VM_SUPPLY_LOSS_LEVEL[MIN] 205 410 540 540
Identifier VM_SWITCHING_FREQUENCY
Description Range applied to the maximum switching frequency parameters
Units User units
Range of [MIN] 0
Range of [MAX] 0 to 6
VM_SWITCHING_FREQUENCY[MAX] = Power stage dependent
VM_SWITCHING_FREQUENCY[MIN] = 0 for motor control modes, or 1 for Regen mode (subject to the maximum)
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 17

Identifier VM_TORQUE_CURRENT
Description Range applied to torque and torque producing current parameters. (Where this is used in Regen
mode it refers to the active current.)
Units %
Range of
[MIN] -1000.0 to 0.0
Range of
[MAX] 0.0 to 1000.0
Select Motor 2 Parameters
(11.045) VM_TORQUE_CURRENT[MAX]
0 VM_MOTOR1_CURRENT_LIMIT[MAX]
1 VM_MOTOR2_CURRENT_LIMIT[MAX]
VM_TORQUE_CURRENT[MIN] = -VM_TORQUE_CURRENT[MAX]
Identifier VM_TORQUE_CURRENT_UNIPOLAR
Description Unipolar version of VM_TORQUE_CURRENT
Units %
Range of [MIN] 0.0
Range of [MAX] 0.0 to 1000.0
VM_TORQUE_CURRENT_UNIPOLAR[MAX] = VM_TORQUE_CURRENT[MAX]
VM_TORQUE_CURRENT_UNIPOLAR[MIN] =0.0
Identifier VM_USER_CURRENT
Description Range applied to torque reference and percentage load parameters with one decimal place
Units %
Range of [MIN] -1000.0 to 0.0
Range of [MAX] 0.0 to 1000.0
VM_USER_CURRENT[MAX] = UserCurrentMaximumScaling (04.024)
VM_USER_CURRENT[MIN] = -VM_USER_CURRENT[MAX]
Identifier VM_USER_CURRENT_HIGH_RES
Description Range applied to torque reference and percentage load parameters with two decimal places
Units %
Range of [MIN] -1000.00 to 0.00
Range of [MAX] 0.00 to 1000.00
VM_USER_CURRENT_HIGH_RES[MAX] = UserCurrentMaximumScaling (04.024) with an additional decimal place
VM_USER_CURRENT_HIGH_RES[MIN] = -VM_USER_CURRENT_HIGH_RES[MAX]
18 Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)

Menu 1 Single Line Descriptions − Regen References
Mode: Regeneration
Parameter Range Default Type
01.054 Fire Mode Activate Off (0) or On (1) Off (0) RO Bit NC
RW Read / Write RO Read-only Bit Bit parameter Txt Text string Date Date parameter Time Time parameter
Chr Character parameter Bin Binary parameter IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter
Num Number parameter DE Destination ND No
default value RA Rating dependent NC Non-copyable PT Protected
FI Filtered US User save PS Power-
down save
Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00) 19

Menu 1 − Regen References
Mode: Regeneration
Parameter 01.054 Fire Mode Activate
Short description Set to 1 to activate fire mode
Mode Regeneration
Minimum 0Maximum 1
Default 0Units
Type 1 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RO, NC
FireModeActivate (01.054) cannot be written directly, but it can be controlled from a digital input. This prevents fire mode from being enabled from the
keypad, comms or an option module.
Fire mode is intended for purging air from a ventilation system in the event of a fire. All trips are either disabled or are automatically reset after 1s. The
use of fire mode can result in damage to the drive, and so if fire mode is enabled and any trip is initiated an indication that cannot be reset by the user is
stored in PotentialDriveDamageConditions (10.106). For Open-loop, RFC-A or RFC-S modes fire mode is activated and if FireModeReference
(01.053) has a non-zero value and FireModeActivate (01.054) = 1. When fire mode is activated normal drive operation is overridden as follows.
1. Pre-rampReference (01.003) is forced to the value in FireModeReference (01.053).
2. The Final drive enable is forced to be active provided the safe torque off hardware input will allow the drive to be enabled. The Final drive run is
forced to be active.
3. ForwardLimitSwitch (06.035) and ReverseLimitSwitch (06.036) are disabled.
4. HardSpeedReference (03.022) is forced to 0 (RFC-A and RFC-S modes). The hard speed reference should not be used when fire mode can
be activated as this could cause an abrupt change in speed.
5. The hand/off/auto system is disabled. If this system is in the hand state when fire mode is activated it will be forced to the off state, so that hand
state is not active when fire mode is de-activated.
6. Keypad control mode is disabled.
7. All latched states in the sequencer (Menu 6) are reset.
For Regen mode fire mode is activated if FireModeActivate (01.054) = 1. When fire mode is activated the Final drive enable is forced to be active
provided the safe torque off hardware input will allow the drive to be enabled.
If the drive is in the tripped state when fire mode is activated the trip is reset and then only the trips listed in the table below can be initiated whilst fire
mode is active. If any of the trips shown as resettable occur, the drive will attempt to automatically reset the trip after 1s.
Trip number Trip Resettable
2OverVolts Yes
3OIac Yes
4OIBrake Yes
5PSU Yes
9PSU24V Yes
21 OHtInverter Yes
31 EEPROMFail No
36 UserSave No
37 PowerDownSave No
109 OIdc Yes
200 Slot1HF No
205 Slot2HF No
210 Slot3HF No
217-249 No
250 Slot4HF No
20 Unidrive M700 Parameter Reference Guide
Issue: 01.16.01 (Eth 01.07.00)
Other manuals for Unidrive M700
2
Other Nidec Servo Drive manuals
Popular Servo Drive manuals by other brands

Mitsubishi Electric
Mitsubishi Electric MELSERVO HG-MR instruction manual

Autonics
Autonics AiCA-EC Series user manual

SEW-Eurodrive
SEW-Eurodrive CM3C Series operating instructions

Kollmorgen
Kollmorgen S700 Series Safety guide

turck
turck IM72-11Ex/L manual

Mitsubishi Electric
Mitsubishi Electric MR-J2S-60A4 Instructions and Cautions for Safe Use