Ambient models
All slimline ambient air curtains require
230V, 1ph, 50Hz supply via a 3 core cable
for connection to the mains isolator.
ON/OFF and HIGH/LOW settings are
operated via a remote switchbox (See
Figure 13).
For details on interconnection between
heater and switchbox please refer to
section 12.
Electrically heated models
AS70SE04 models require 230V, 1ph,
50Hz supply via a 3 core cable for
connection to the mains isolator. ON/OFF
and HIGH/LOW settings are operated via
switches located on the front of the unit.
(See Figure 17).
AS80SE03 models require 230V, 1ph,
50Hz supply via a 3 core cable for
connection to the mains isolator. Heat
and fan settings are operated via a
remote switchbox. (See Section 6).
AS100SE06 - AS200HE18 models should
be connected to a 415V, 3ph, 50Hz supply
via a 5 core cable for connection to the
mains isolator and to the terminal block
on top of the unit. Heat and fan settings
are controlled via a remote switchbox.
(See Figure 14).
It is also possible for the 6kW model to be
connected to a single phase system by
linking the R, S,and T terminal blocks
together. (See Figure 15).
Electrical connections must always be
undertaken by a suitably qualified
electrician wired in accordance with this
installation manual.
For details on interconnection between
heater and switchbox. Please refer to
section 12.
Cabling should be 5 core 2.5mm dia for
heating capacity up to 9kW. For heaters
up to 18kW a 5 core 4mm dia cable
should be used.
Always use the ON/OFF switch on the
remote switch box to operate the unit.
DO NOT operate the air curtain by means
of the mains isolator switch. On the
AS70SE04 use ON/OFF switch on the air
curtain.
WARNING
Before installation carefully read the
instruction manual and labels on the
upper side of the air curtain and remote
switchbox connection box. Before final
connection check earthing of the supply.
Warning Warning
AIRBLOC AS AIRBLOC SLIMLINE ENERGY SAVING AIR CURTAINS
5. Wiring instructions
Figure 13 Electrical connection - (AS160A shown)
Figure 14 Open power supply plastic box - (AS160SE12 shown)
Figure 15 Open power supply plastic box - (AS100SE06R shown)