Novatek RNPP-311M User manual

«NOVATEK-ELECTRO» Ltd
Intelligent industrial electronics
RNPP-311M
MULTIFUNCTIONAL
THREE PHASE
VOLTAGE MONITORING
RELAY
OPERATING MANUAL
Quality control system on the development and production complies with requirements ISO 9001:2015
Dear customer,
Company NOVATEK-ELECTRO Ltd. thanks you for purchasing our products.
You will be able to use properly the product after carefully studying the Operating Manual.
Keep the Operating Manual throughout the service life of the product.
Review the Operating manual before using the unit
This unit is safe for use in case of compliance with operating rules.
UKRAINE, Odessa, www.novatek-electro.com

~ 2 ~
RNPP-311M NOVATEK-ELECTRO
ATTENTION! ALL REQUIREMENTS OF THIS OPERATING MANUAL ARE COMPULSORY TO BE MET!
WARNING! –PRODUCT TERMINALS AND INTERNAL COMPONENTS ARE UNDER
POTENTIALLY LETHAL VOLTAGE
TO ENSURE THE PRODUCT SAFE OPERATION IT IS STRICTLY FORBIDDEN THE
FOLLOWING:
TO CARRY OUT MOUNTING WORKS AND MAINTENANCE WITHOUT DISCONNECTING THE
PRODUCT FROM THE MAINS;
TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY;
TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE.
IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE
PRODUCT.
During operation and maintenance the regulatory document requirements must be met, namely:
–Regulations for Operation of Consumer Electrical Installations;
–Safety Rules for Operation of Consumer Electrical Installations;
–Occupational Safety when in Operation of Electrical Installations;
ATTENTION! THE DEVICE IS NOT INTENDED TO BE USED FOR LOAD COMMUTATION IN CASE OF SHORT
CIRCUITS. THEREFORE OUTPUT CONTACTS OF LOAD RELAY SHOULD BE PROTECTED BY AUTOMATIC
CIRCUIT BREAKERS (FUSES) WITH TRIPPING CURRENT NOT EXCEEDING 6.3 A OF CLASS B.
To improve operational properties of the unit it is recommended to install the fuse (fuse element), or the
equivalent for current of 1A in power supply circuit (L1, L2, L3) for RNPP-311M.
Installation, adjustment and maintenance of the product must be performed by qualified personnel having
studied this Operating Manual.
In compliance with the requirements of this Operating Manual and regulations the product is safe for
use.
1 –Input terminals 400V/415V;
2 –Switch of voltage of controlled mains (400 V / 415 V);
3 –Switch of protection operation at phase sequence (SEQ) (in position “OFF” – the protection is disabled);
4 –Switch of protection operation at voltage imbalance (IMB) (in position “OFF» – the protection is disabled);
5 –Switch of protection operation at the minimum voltage (Umin)(in position “OFF» – the protection is disabled);
6 –Switch of protection operation at the maximum voltage (Umax) (in position “OFF» – the protection is disabled);
7 –Green LED indicators of voltage presence on each phase (LINE);
8 –Red LED “ALARM” indicator showing also the open state of the output contacts;
9 –Output terminals;
10 –Control of setting the protection operation time (Toff (sec));
11 –Control of setting the AR time (Ton(sec));
12 –Control of setting the threshold for maximum / minimum voltage (Unom±%);
Figure 1 - Control descriptions and dimensions diagram

~ 3 ~
NOVATEK-ELECTRO
RNPP-311M
This operation manual is intended for description, principle of work, construction, mode of work and
maintenance of the multifunctional three phase voltage monitoring relay (hereinafter RNPP-311M).
The product meets the requirements of the following:
EN 60947-1;
EN 60947-6-2; EN 55011;
IEC 61000-4-2.
Harmful substances, in more than allowed concentration, are not available.
Terms and abbreviations:
AR is automatic reclosing;
MS is magnetic starter;
The term "Normal voltage" means that the voltage value does not exceed the threshold limit values set by the
User.
1. APPLICATION
1.1. RNPP-311M is designed:
for monitoring the permissible voltage level;
for monitoring the correct alternation and absence of sticking of phases;
for monitoring the full-phase and symmetry of the mains voltage (phase imbalance);
to disconnect the load in case of improper mains voltage;
for monitoring the quality of the mains voltage after switching off the load and automatically turning it
on after restoring the voltage parameters;
to indicate the failure in the event of emergency situation and the presence of voltage in each phase.
RNPP-311M performs zero control, indirectly.
The device provides the possibility of adjusting the parameters (voltage threshold, time of automatic reclosing
and time delay of protection operation), selection of the voltage of the monitored mains (400 V or 415 V) and a set
of protective functions.
After restoring the voltage parameters of the mains, the device enables again the load after the reclosing
time.
Note - For networks with a high level of harmonics, we recommend using the modification of the
RNPP-311M-24 device with the connection to self-contained 24 V power supply.
1.2. Operation conditions
The product is designed for operation in the following conditions:
–Ambient temperature: from minus 35 to +55°C;
–Atmospheric pressure: from 84 to 106.7 kPa;
–Relative air humidity (at temperature of +25°C): 30 … 80%.
If the temperature of the product after transportation or storage differs from the environment temperature
at which it is expected to operate, then before connection to electric mains keep the product under the
operating conditions within two hours (because the product elements may have moisture condensation).
ATTENTION! The product is not intended for operation in the following conditions:
–Significant vibration and shocks;
–High humidity;
–Aggressive environment with content in the air of acids, alkalis, etc., as well as severe
contaminations (grease, oil, dust, etc.).
2. TECHNICAL CHARACTERISTICS
Table 1
Item
Value
Purpose of device
Control and distribution equipment.
Typical operation
Continued
Protection degree: - device
- terminal block
IP40
IP20
Protection class against electric shock
II
Permissible contamination level
II
Overvoltage category
II
Nominal voltage of insulation V
450
Rated impulse withstand voltage, kV
2.5

- 4 -
RNPP-311M
NOVATEK-ELECTRO
Table 2
Rated line/phase voltage, V
400/230,
415/240
Rated frequency, Hz
45 65
Harmonical configuration (nonsinusoidality) of power supply voltage
EN 50160
Adjustable range for Umax/Umin, % of nominal value Unom
5 50
Adjustable Tripping time delay (Toff), sec
0 10
Adjustable Autoreclosing time delay (Ton), sec
0 600
Fixed time delay for tripping in case MIN voltage fault detected (time delay for Umin), sec
12*
Reaction time in case of phase loss, sec (not more)
0.2
Readiness time on energizing the RNPP-311M, sec (not more)
0.2**
Phase imbalance value, V
60
Voltage hysteresis, V
5 - 6
Phase imbalance hysteresis, V
5 - 6
Accuracy for voltage tripping threshold measurement, V (not more)
3
Accuracy for phase imbalance measurement, % (not more)
2
Voltage when safe operating (effective value), V
- at one phase
- at three phase
140 –450
95 –450
Power consumption (under load), W, not more
1.2
Maximal current that output contacts may commutate, A
5
Commutation endurance for the output contacts:
- under 5Аpower load (cos φ = 1,0), not less than
- under 1Аpower load (cos φ = 1,0), not less than
100000 times
1000000 times
Cross-section area of connection terminals, mm²
0.5 –1.5
Torque of terminal fixing, N*m
0.4
Weight, kg (not more)
0.100
Overall Dimensions, H*B*L, mm
90.2*36*64.5
Standard 35 mm DIN rail mounting
Mounting position as per requirement (arbitrary)
Case material is self-extinguishing plastic
_______
* If the switch Umin is in the "ON" position, the fixed operation time of the device is 12 seconds.
** When working in "Maximum Voltage Control" mode, the ready time is 0.3 seconds.
3. INTENDED USE
3.1. Preparation for operation
3.1.1. Preparation for connection:
Unpack and check the product for damage after transportation; in case of such damages detection,
contact the supplier or manufacturer;
Carefully study the Operating Manual (pay special attention to the connection diagram to power the
product);
If you have any questions regarding the installation of the product, please contact the manufacturer by
telephone number indicated at the end of this Operating Manual.
3.1.2. Device connection
ATTENTION! ALL CONNECTIONS MUST BE PERFORMED WHEN THE PRODUCT IS DE-ENERGIZED.
Error when performing the installation works may damage the product and connected devices.
To ensure the reliability of electrical connections you should use flexible (stranded) wires with insulation
for voltage of no less than 450 V, the ends of which it is necessary to be striped of insulation for 5±0.5 mm
and tightened with bootlaces. Recommended cable cross section for connection is not less 1 mm2.
Wires fastening should exclude mechanical damage, twisting and abrasion of the wire insulation.
IT IS NOT ALLOWED TO LEAVE EXPOSED PORTIONS OF WIRE PROTRUDING BEYOND THE
TERMINAL BLOCK.
For a reliable contact, tighten the terminal screws with the force indicated in Table 1.
When reducing the tightening torque, the junction point is heated, the terminal block may be melted and
wire can burn. If you increase the tightening torque, it is possible to have thread failure of the terminal block
screws or the compression of the connected wire.
3.1.2.1. Connect the device according to the diagram shown in Fig. 2.

- 5 -
NOVATEK-ELECTRO RNPP-311M
Notes:
1) If on the first start up RNPP-311M
doesn’t allow to turn ON the power
load and indicates wrong phase
sequence alarm but the user is
absolutely sure that the phase
sequence is correct –then it is
necessary to exchange the wires
connected to terminals 10 and 11.
2) If RNPP-311M is being used as a
maximal voltage protection relay
then the break in the magnetic starter
coil power circuit should be connected
to terminals 1-2 (4-5) (the reverse logic
of switching-on).
The switch Umax (it. 6, Fig. 1) should
be set to ON position (enabled) and
the switches SEQ, IMB and Umin
should be set to the OFF position
(disabled).
Figure 2 - RNPP-311MConnection diagram
3.1.2.2. Using the Unom ±% control (it. 12, Fig. 1), set the required operation threshold for the maximum
and minimum voltage as a percentage of the rated supply voltage of the mains.
Attention! When setting the lower threshold for Umin, the release voltage of the MS must be taken
into account.
3.1.2.3. Using the Toff (sec) control (it. 10, Fig. 1), set the protection operation time at the maximum
voltage and phase imbalance.
3.1.2.4. Using Ton(sec) control (it. 11, Fig. 1) set the reclosing time AR.
Ton(sec) is the time of automatic reclosing after the device operation and restoration of the mains voltage
parameters; on-time is after the rated voltage supply to the device.
It is recommended to set the reclosing time AR for air conditioners, refrigerators and other compressor
equipment at least 180 - 240 seconds.
ATTENTION! In order not to break or turn the control, please do not use excessive force when
performing the setting operations.
3.1.2.5. Enable the necessary protections using protection switches (it. 3 –6, Fig. 1).
3.1.2.6. Set the type of mains used with switch of rated voltage of 400 V / 415 V (it. 2, Fig. 1).
3.1.2.7. Feed the supply voltage to the terminals of the device.
3.2. Operation
3.2.1. It is possible to adjust the RNPP-311M to operate in following modes:
–“Minimum / maximum voltage control";
–“Minimum voltage control";
–“Maximum voltage control";
–"Phases presence control";
–"Control of incorrect phase sequence and presence of phase sticking";
–"Phase imbalance control".
NOTE: The control of the phase presence is kept in any operating mode.
In “Minimum / maximum voltage control" mode, when the voltage value of the mains is exceeded for the
thresholds set by the User, the protected equipment will be disconnected from the mains and red ALARM
LED indicator will turn ON .

- 6 -
RNPP-311M
NOVATEK-ELECTRO
In “Minimum voltage control" mode, when the mains voltage drops below the threshold set by the User,
the protected equipment is disconnected from the mains and red ALARM LED indicator will turn ON.
In “Maximum voltage control" mode, when the mains voltage rises above the threshold set by the User,
the protected equipment is disconnected from the mains and red ALARM LED indicator will turn ON.
In "Phases presence control" mode, if one phase is broken, when one of the LINE LED indicators will turn
OFF, the protected equipment is disconnected from the mains. Red ALARM LED indicator will turn ON.
In "Control of incorrect phase sequence and presence of phase sticking" mode, if the connection is
incorrect or if one of the phases is sticking, one of the LINE LED indicators lights up on the front panel of the
device, the ALARM LED indicator will turn ON and the protected equipment disconnects from the mains.
In "Phase imbalance control" mode, in case of voltage imbalance, two LINE LED indicators flash
alternately on the front panel of the device, the ALARM LED indicator will turn ON and the protected
equipment disconnects from the mains.
3.2.2. The device at the output has two groups of independent output changeover contacts (1-2-3, 4-5-6).
If there is no voltage to the device, the contacts 1-2 (4-5) are closed, and the contacts 2-3 (5-6) are open.
When the RNPP-311M is operated, the load is disconnected by interrupting the power supply of the MS
coil through 1-2 (4-5) contacts, except for the "Maximum Voltage Control" mode in which the device is
operated with an inverse switching logic.
3.2.3. After the power is supplied to the terminals of the device, the indicators LINE turn ON. The device
goes into the AR delay time mode (set by the Ton(sec) control),while the ALARM indicator flashes. After the
reclosing time has finished, the ALARM indicator turns OFF and the device connects the protected
equipment to the mains.
In the event of the failure, the reclosing time AR begins immediately after the device disconnects the
protected equipment.
3.2.4. If the device is used in the “Maximum voltage control" mode, at normal voltage in the mains, the
device contacts 1-2 (4-5) are closed, and the contacts 2-3 (5-6) are open. This is done to ensure that the
device in the "Maximum voltage control" mode has never operated for reducing the voltage. In this mode,
when the device is turned on for the first time, the reclosing time value (Ton(sec)) is not taken into account.
Note: in all modes of operation RNPP-311M trips the power load with the fixed time of 0,2 sec in case of
phase loss or if the voltage on any of the phases get lower than 100V.
3.2.5. The options for the status of indicators LINE and ALARM are shown in Table 3
Table 3
Green LED
indicators
LINE
Indication status LINE
Red LED
ALARM
Indication status
ALARM
Functional state
of RNPP-311M
All LEDs are
permanently ON
Luminescence is absent
Voltage parameters
on each phase are
normal.
Blinking (reverse reading
of the autoreclosing time
delay)
Blinking of any (all)
LEDs
Continuous
luminescence
Voltage rise on the
corresponding phase
(phases) is detected
Any (all) LEDs are OFF
Continuous
luminescence
1) Voltage level on any
(all) of phases is lower
than the user adjusted
value;
2) Voltage level on
any (all) of phases is
lower than 100V or the
phase loss is detected.
Blinking of two LEDs
alternately. At first Mid-
dle and Right LEDs turn
ON and then Middle and
Left turn ON
Continuous
luminescence
Phase imbalance
failure
Left, Middle and then
Right LEDs turn ON one
by one
Continuous
luminescence
Wrong phase sequence
and phase coincidence
alarm situation

- 7 -
NOVATEK-ELECTRO RNPP-311M
NOTE - The failure is displayed in order of priority:
1 –Phase failure or voltage drop below 100 V (highest priority);
2 –Phase sequence;
3 –Minimum and maximum voltage;
4–Phase imbalance.
3.2.2. RNPP-311M usage examples
a) RNPP-311M in “Minimum voltage control" mode
- Switch Umin is in ON position.
- Switches Umax, IMB are in OFF position.
If the voltage drops below Umin, the device will operate after the Toff (sec) time set by the User, the red
ALARM indicator will turn ON, the corresponding LINE indicator (-s) will off. If the voltage drops below 100 V,
the device will be operated after 0.2 seconds.
b) RNPP-311M in "Minimum / maximum voltage control" and "Phases presence control" modes
- Switches Umin and Umax are in ON position.
RNPP-311M will operate if the voltage rises above the set threshold after the time Toff (sec), and when
it decreases - with the fixed delay of 12 seconds (setting the starting voltage slumps), the red ALARM
indicator will turn ON. If the phase breaks, the device will operate after 0.2 seconds.
c) Maximal voltage relay
- Switch Umax is in ON position.
- Switches Umin, SEQ, IMB are in OFF position.
- Red ALARM indicator is OFF.
If high voltage detected RNPP-311M will turn OFF the power load with time delay (Toff (sec) +0,4) sec
and the red ALARM indicator will turn ON.
d) Turn ON time delay relay
- Switches Umin, Umax are in OFF position.
The protected equipment will be connected after the AR time countdown set by the User with the help of
Ton(sec) control. In all modes of operation, the switching ON / OFF of protection due to the phase sequence
disturbance is carried out by the switch SEQ, and the switching ON / OFF due to the phase imbalance protection
- by the switch IMB. If the phase is broken or the voltage drops below 100 V in one or more phases, the device
will operate (turn OFF) the corresponding phase indicator will turn OFF.
If switches Umin, Umax,SEQ,IMB are in ON position and the voltage drop is less than Umin, the device
will operate with the fixed delay of 12 seconds (setting the starting voltage slumps).
4. MAINTENANCE
4.1. Safety precautions
THE TERMINALS AND THE PRODUCT INTERNAL ELEMENTS CONTAINS POTENTIALLY LETHAL
VOLTAGE.
DURING MAINTENANCE IT IS NECESSARY TO DISABLE THE PRODUCT AND CONNECTED
DEVICES FROM THE MAINS.
Maintenance of the unit should be performed by persons admitted to the operation and have the
appropriate permission.
The recommended frequency of maintenance is every six months.
4.2. Maintenance procedure:
1) check the wires connection reliability, if necessary –clamp with force as specified in Table 2;
2) check visually the housing integrity;
3) if necessary, wipe with cloth the front panel and the unit housing.
It is not allowed to clean the unit with abrasive materials or organic compounds (alcohol, gasoline, solvents,
etc.).
5. SERVICE LIFE AND WARRANTY
Service life –is 10 years. Contact manufacturer upon the expiry of the service life.
Guaranteed storage life –is 3 years.
Warranty period of the unit operation is 5 years from the date of sale.
During the warranty period the Manufacturer is responsible for free repair of the unit, if the Consumer has
complied with the requirements of this Operating Manual.
ATTENTION! IF THE UNIT HAS BEEN OPERATED WITH VIOLATION OF THE REQUIREMENTS OF
THIS OPERATION MANUAL, BUYER WILL FORFEIT THE RIGHT TO WARRANTY SERVICE.
Warranty service is performed at the place of purchase or by the Manufacturer of the product.

- 8 -
RNPP-311M
NOVATEK-ELECTRO
Post-warranty service is performed by the Manufacturer at current rates.
Before sending for repair, the unit should be packed in the original or other packaging excluding
mechanical damage.
6. TRANSPORTATION AND STORAGE
RNPP-311M in the shipping box should be stored indoors at a temperature of -45 to +60 C and relative
humidity of no more than 80% with no vapors available in the air.
7. ACCEPTANCE CERTIFICATE
RNPP-311M is manufactured and accepted in accordance with the applicable technical documentation
and considered as fit for use.
Stamp Head of quality division Date of manufacture
__________________ _________________
Sale date______________________
8. NOTICES OF CLAIMS
Earnest request: indicate the reason for return in the notice of faults field at the return of the device or in
case of submitting for warranty service or post-warranty service.
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
The Company is grateful to you for the information about the quality of the device and suggestions for its operation.
With questions and comments, please contact manufacturer at the following address:
"Novatek-Electro" Ltd.
59, Admiral Lazarev str.,
Odessa, Ukraine, 65007.
Tel: +38 048 738-00-28; +38 0482 37-48-27;
Fax: +38 0482 34 36 73.
www.novatek-electro.com
VN190404
Table of contents
Other Novatek Relay manuals
Popular Relay manuals by other brands

Pilz
Pilz PZE X4VP operating manual

Schweitzer Engineering Laboratories
Schweitzer Engineering Laboratories SEL-321-5 instruction manual

ABB
ABB REF 610 Operator's manual

FANOX
FANOX SIA-B Standard Series Installation & commissioning guide

GRUP ARGE
GRUP ARGE KKNT-2.5 Usage and maintenance

Circutor
Circutor WRU-10 RAL manual

ComAp
ComAp InteliPro Installation and operation guide

Schweitzer Engineering Laboratories
Schweitzer Engineering Laboratories SEL-321-2 instruction manual

Vemer
Vemer CLIP-485 user manual

Carrier
Carrier KAAWS0101AAA installation instructions

Rockwell Automation
Rockwell Automation Guardmaster MSR57P user manual

GMI
GMI D1092S-069 quick start guide