This component is an electrical device that must
be installed correctly to ensure proper operation
and to prevent shock or fire. Read these important
warnings and carefully follow all of the installation
instructions.
•To minimize the danger of fire from sustained
electrical arcing if the heating cable is damaged
or improperly installed, and to comply with the
requirements of nVent, agency certifications, and
national electrical codes, ground-fault equipment
protection must be used. Arcing may not be
stopped by conventional circuit breakers.
•The power connection may be powered by more
than one circuit. Be sure all power sources are
de-energized before opening box.
•Component approvals and performance are
based on the use of nVent specified parts only.
Do not use substitute parts or vinyl electrical
tape.
•The black heating cable core and fibers are
conductive and can short. They must be properly
insulated and kept dry.
•Damaged bus wires can overheat or short. Do
not break bus wire strands when scoring the
jacket or core.
•Keep components and heating cable ends dry
before and during installation.
•Use only fire-resistant insulation materials, such
as fiberglass wrap or flame-retardant foam.
HEALTH HAZARD: Prolonged or repeated contact
with the sealant in the core sealer may cause skin
irritation. Wash hands thoroughly. Overheating or
burning the sealant will produce fumes that may
cause polymer fume fever. Avoid contamination of
cigarettes or tobacco. Consult MSDS VEN 0058 for
further information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300
Non-emergency health and safety information:
(800) 545-6258.
KIT CONTENTS
Item Qty Description
A 1 Stand assembly
B 2 Grommet plugs
C 1 Box plug, o-ring, and locknut
D 1 Cable lubricant
E 3 Core sealers
F 3 Green/yellow tubes
G 1 Box with terminal blocks
H 1 Lid
I 1 Spanner
J 1 Strain relief
APPROVALS
CLI, ZN1, AEx e II T* (1)
Ex e II T*
Hazardous Locations
(1) Except VPL
* For system Temperature Code, see heating cable or design documentation.
(2) Except KTV-CT
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups E, F, G
Class III
JBM-100-A is IECEx certified for use with:
BTV-CR/BTV-CT: IECEx BAS 06.0043X
QTVR-CT: IECEx BAS 06.0045X
XTV-CT: IECEx BAS 06.0044X
KTV-CT: IECEx BAS 06.0046X
VPL-CT: IECEx BAS 06.0048X
–WS
(JBM-100-A only) Ex e IIC T* Gb (2)
IECEx
A
D
C
B
H
G
F
E
I
J
®
RAYCHEM
Power Connection, Powered Splice, Powered Tee, Dual
Power Connection, Splice or Tee with Junction Box
DESCRIPTION
kits. They are
designed for use with nVent RAYCHEM BTV-CR, BTV-CT, QTVR-CT,
and VPL-CT industrial parallel heating cables. The kits can be used
to connect one, two, or three heating cables to power, to connect two separate
each heating cable should not exceed the maximum allowable circuit length
published in the Raychem self-regulating cables design guide and the total
current of all heating cables on the circuit should equal no more than 80% of the
circuit breaker current rating.
easier installation store above freezing until just before installation.
For technical support call nVent Industrial Heat Tracing Solutions
TOOLS REQUIRED
•Utility knife
ADDITIONAL MATERIALS REQUIRED
OPTIONAL MATERIALS
Installation Instructions