NXT Power NPTU 600-L-N User manual

Integrity Pro Medical / Non-Medical
User Manual
600 / 800 / 1100 / 1440 VA
NPTU 600-L-N
NPTU 800-L-N
NPTU 600-LM-N
NPTU 800-LM-N
NPTU 1100-L-N
NPTU 1500-L-N
NPTU 1100-LM-N
NPTU 1500-LM-N
NPTU 1100-L-i
NPTU 1500-L-i
NPTU 1100-LM-i
NPTU 1500-LM-i

Table of Contents
1. Safety Instructions and Storage / Battery Care .................................................... 1
2. UPS System Block Diagram .................................................................................... 1
3. Front Panel Display ................................................................................................. 1
4. Product Features...................................................................................................... 2
5. Button Function ....................................................................................................... 2
6. Installation and Start up .......................................................................................... 3
7. Alarms and Status Icons ......................................................................................... 3
8. Specifications ........................................................................................................... 3
9. Battery Replacement Procedure ............................................................................ 4
10. Warrenty information.............................................................................................5

1
1. Safety Instructions and Storage/ Battery Care
SAVE THESE INSTRUCTIONS. - This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
Read the instructions carefully to become familiar with the equipment before starting the instillation process.
Notify the carrier and dealer if there is any damage to the unit. Do not install if unit has signs of physical damage.
Adhere to all national and local electrical codes.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with liquids, or where there is excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. Keep rear panel a minimum of 8 inches
(20cm) from any obstructions.
For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or
extension cords. Use only the power cord supplied with the UPS.
The battery typically lasts for three to five years. Environmental factors will impact battery life. Elevated ambient temperatures, poor quality
utility power, and frequent short duration discharges will shorten battery life.
The equipment and batteries are heavy. Remove the batteries before lifting the UPS and practice safe lifting techniques adequate for the
weight of the equipment.
Before installing or servicing the equipment check that the Disconnecting from the AC mains and load. The UPS contains internal batteries
and may present a shock hazard even when disconnected from the branch circuit (mains).
Doing wiring, maintenance service and batteries replacement should be performed or supervised by personnel knowledgeable about
batteries and the required precautions.
When replacing batteries, replace with the same type and number of batteries or battery packs.
This UPS is intended for patient vicinity use only. Do not use this UPS for any life support applications or critical support.
CAUTION: Do not dispose of batteries into fire. The batteries may explode.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin, eyes, and may be toxic.
CAUTION: A battery can present a risk of electrical shock and high short-circuit current through conductive materials and could cause
severe burns. The following precautions should be observed when working on batteries:
Before installing or replacing the batteries, remove jewelry such as wristwatches and rings, or other metal objects.
When working on batteries should wear rubber gloves and boots. Also, must use tools with insulated handles. Do not lay tools or metal
parts on top of batteries.
Remove battery grounds during installation and maintenance to reduce likelihood of shock. Remove the connection from ground if any
part of the battery is determined to be grounded.
2. UPS System Block Diagram
3. Front Panel Display
LCD
Status
1. AC mains mode
2. Battery/inverter mode
3. Automatic Voltage Regulation (Buck or Boost)
4. Battery capacity
5. Load capacity
6. UPS status
7. Power ON/OFF button

2
4. Product Features
NPTU600-L-N/ PTU600-LM-N
NPTU800-L-N / PTU800-LM-N
NPTU1100-L-N / NPTU1100-LM-N
NPTU1500-L-N / NPTU1500-LM-N
NPTU1100-L-i/ PTU1100-LM-i
NPTU1500-L-i/ PTU1500-LM-i
A
:
RS
-
232
E
:
Input Breaker
B
:
USB port
F
:
AC Outlet
s (Program relay, PRY)
C: Fan / Ventilation hole G: Intelligent Slot
D
:
AC Inlet
5. Button Function
Status
Action
Description
LCD Display
Power ON
Press the on/off button for 5~8 seconds,
release the button when the alarm sounds
The UPS will now turn on.
The (2) icons highlighted in red will flash
Power OFF
Press the on/off button for 5~8 seconds,
release the button when the alarm sounds
The UPS will now turn off.
The (2) icons highlighted in red will flash
Alarm silence
When the UPS is in an abnormal state, the
alarm will sound. Press on/off button for ½
second (Do not hold the button longer that
1 second). This will silence the alarm
Self-Test
(With the UPS in AC mains operation)
press the on/off button for 1~2 seconds,
release the button when the alarm sounds
a short beep. The UPS will perform a self-
test.
The icon highlighted in red will flash
Outlet Status
(With the UPS ON) Press the on/off button
two times in 5 seconds to enter outlet
status mode. With no actions for 5 seconds,
the UPS will exit outlet status mode.
Group 1 Group 2
The highlighted icon in the above figure
shows:
Group 1 (1on/1oF): Output at
Group 2 (2on/2oF): Output at
Please use software tool for outlet status
setting

3
To clear the error icon
Hold down the on/off button for 5~8
seconds, release the button when the alarm
beeps. The error icon will be removed.
6. Installation and Power On
1. Installation:
Please read Section 1. Safety Instructions and Storage/ Battery Care before installing.
2. Connect equipment to the UPS. Avoid using extension cords.
Do NOT connect printers, heaters, or copiers to the UPS.
During a power outage or other AC problems, the outlets receive power for a limited time from the
UPS.
3. Press the ON/OFF button for 5~8 seconds to turn the unit on.
The UPS should charge the battery for at least 6 hours to ensure sufficient runtime.
Press ON/OFF button in 5~8 seconds. The alarm sounds to confirms that the UPS is on and provide
power to outlets.
4. Cold start the UPS.
Use cold start feature to supply power to connected equipment from the UPS batteries when there is
no utility power. To turn on the UPS see step 3 above.
5. Connect and install management software.
UPS is provided with management software for unattended operating system shutdown, UPS monitoring, and UPS settings.
7. Audible alarms and Status Icons
If the UPS
…
Possible cause...
In Battery Mode: Alarm sounds every 2 seconds.
(
alarm for
0.5 second and stop
s for
1.5 seconds)
UPS is running on battery. You should consider saving any work in
progress.
a. Low Battery: alarm sounds every 0.2 seconds
b. Low Battery power off: Continuous alarm
Low battery condition and battery run-time is very low. Promptly save
any work in progress, exit all open applications, and shut down the
operating system.
Continuous tone with flashing. UPS is overloaded.
Continuous tone with illuminated.
a. Press ON/OFF button one time to mute the alarm.
b. Continuous alarm will sound until battery runs low.
(<11Vdc each battery)
: Fan fault detected
: Inverter short
: Inverter over voltage
: Transformer over temperature
Battery Replacement Alarm: alarms every 4 seconds (alarms
for
1 second and stop
s for
3 seconds)
The battery is near the end of useful life or damaged. Replace battery
8. Specifications
Low Voltage Models (Domestic) High Voltage Models
(International)
Model NPTU600-L-N NPTU800-L-N NPTU1100-L-N NPTU1500-L-N NPTU1100-L-i NPTU1500-L-i
Medical Model NPTU600-LM-N
NPTU800-LM-N
NPTU1100-LM-N
NPTU1500-LM-N
NPTU1100-LM-i
NPTU1500-LM-i
Input
Voltage range 100VAC : 80-120 VAC
120VAC : 96-144 VAC
208VAC : 167-249 VAC
230VAC : 184-276 VAC
240VAC : 192-288 VAC
Connection IEC320 C-14
Frequency Range 50 / 60 Hz(Auto sensing)
Output
UPS Capacity (total) 600VA/540W 800VA/720W 1100VA/990W 1440VA/1296W 1100VA/990W 1440VA/1296W
Rated Voltage 100VAC / 120VAC 208VAC / 230VAC / 240VAC
Transfer time Typical 2-6 ms, 12ms max.
Waveform Pure Sine Wave
USBRS23 2
11AC OU TPU T
22
AC INPU T
INPU T BR EAK ER
L
INTE RF ACE
N

4
Battery Type & Number
(lead-acid battery) 12V/7Ah x 2 12V/9Ah x 2 12V/7Ah x 4 12V/9Ah x 4 12V/7Ah x 4 12V/9Ah x 4
Physical
Dimension
(D x W x H)
17.7 x 7 x 9.3 inch
450 x 180 x 236 mm
20.7 x 8.7 x 10 inch
525 x 220 x 254 mm
Net Weight 46.1 lb
20.9 kg
48.2 lb
21.9 kg
82.9 lb
37.6 kg
87.3 lb
39.6 kg
84 lb
38.1 kg
88.4 lb
40.1 kg
Packaging
Dimension
(D x W x H)
23 x 12.4 x 15.8 inch
584 x 314 x 401 mm
26 x 14 x 16.5 inch
659 x 354 x 419 mm
Gross Weight 52.7 lb
23.9 kg
54.9 lb
24.9 kg
88.8 lb
40.3 kg
93.3 lb
42.3 kg
90 lb
40.8 kg
94.4 lb
42.8 kg
Environm
ent
Operating
temperature &
Humidity
0-95 % RH @ 0-40°C (non-condensing)
Noise level
AC Line mode: 0-70% load < 43dB
AC Line mode: 70-100% load < 50dB
Backup mode: 0-100% load < 60dB
9. Battery Replacement Procedure
Qualified Service Personnel Only
PLEASE READ ALL OF THE CAUTIONS AND THE WARNINGS BEFORE ATTEMPING TO REPLACE THE BATTERY MODULE
Warning: Lead-acid battery could be drained and damaged by long-term self-discharge naturally without maintenance.
1
100VA / 1
4
4
0VA 48Vdc
Step1 Step2 Step3 Step4
600VA / 800VA 24Vdc
Step1 Step2 Step3
Recycling the Used battery
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
Right side battery safety assembly:
1. Please tear off the double-sided tape.
2. Please install the cover in battery negative
connector (black).

5
10. Warranty Information
Integrity Pro Series Products (hereafter referred to as “Product”) are warranted to be free from defects in material and workmanship for thirty
six (36) months from date of shipment from NXT POWER, on the chassis & electronic components and thirty six (36) months from date of
shipment from NXT POWER on the batteries. This warranty is limited to NXT POWER Product Exchange service. See full Warranty statement
for additional limitations & exclusions.
24 Hour Technical Support Call Center:
Phone: (877) NXT-POWR or (877) 698-7697
Email: [email protected]m

192321572001003
This manual suits for next models
11
Table of contents
Other NXT Power AC Power Distribution manuals
Popular AC Power Distribution manuals by other brands

Panamax
Panamax MIW-POWERKIT-PRO datasheet

Monster Power
Monster Power Reference PowerSource HTPS7000 owner's manual

Pacific Power Source
Pacific Power Source MS SERIES Operation manual

Pacific Power Source
Pacific Power Source ADF Series Operation manual

ETA Systems
ETA Systems ETA-S15 owner's manual

West Mountain Radio
West Mountain Radio RIGrunner 4005i user guide