Overview
The A8911-23 is designed for pulse ounting appli ations where large number of pulse output devi es need to be onne ted
to a Modbus network. The A8911-23 will ount onta t losures on 23 separate inputs and store the totalized pulse ount
internally using non-volatile memory. The pulse ount totals are then read using the RS485/Modbus proto ol. Appli ations
in lude reading gas/water/ele tri meters in ommon building areas for energy information and reporting purposes.
Features and Specifications
Pro essor Arm7, field upgradeable firmware.
LED 23 input status LEDs (red), 2 Modbus TX/RX (yellow), 1 power/alive status. (green)
Proto ols Modbus/RTU
Power Supply 9VDC to 30VDC, 200mA, Required (not in luded)
The unit is to be sour ed by a NEC Class 2 power supply, or Listed ITE power supply marked LPS and
rated from 9 to 30Vd , 200 mA minimum but not to ex eed 8A
Serial Port1RS-485 two wire, 19200 or 9600 baud. N81
Pulse Inputs123 independent pulse ount inputs.
Intended for use with isolated dry onta t outputs.
Pulse rate/width user sele table to 10hz, 50hz or 100hz.
Pulse rate option: 10hz, minimum pulse width 50ms
Pulse rate option: 50hz, minimum pulse width 10ms
Pulse rate option: 100hz, minimum pulse width 5ms
Conta t losure threshold 100Ω to 2.5kΩ user sele table
Pulse ount values are stored in non-volatile memory.
Isolation2: Pulse inputs, power input and RS485 are non-isolated.
Environmental Pollution Degree 2, Altitude up to 2000M.
For indoor and outdoor use when used in an appropriate en losure.
The A8911-23 must be mounted inside a NEMA rated ele tri al en losure for safety and isolation
requirements.
North Ameri a: Indoor, temperature -30º - +70º , 0 - 95% humidity, non- ondensing. 4
Safety UL61010 Re ognized4
File: E320540 (Model A8911-23)
EMC FCC CFR 47 Part 15, Class A
EN 61000, EN 61326
Size 4.13” x 3.39” x 1.18” (105mm x 86mm x 30mm)
Mass 3.7 oz (105 g)
1 inputs are intended for low voltage NEC Class 2 or equivalent outputs.
2 if the produ t is used in a manner not spe ified by the manufa ture, the prote tion provided by the equipment may be
impaired.
4 Devi es manufa tured before Nov 1, 2011 are rated to
0 ~ 50 , and are not UL re ognized.
Installation Checklist
The following omponents are required for a omplete A8911-23 I/O module installation:
●A8911-23 I/O module
●Modbus/RTU master devi e su h as an A quiSuite™ A8812 server
●Pulse output meter
●Power supply: 24VDC typi al. (9VDC to 30VDC ok)
●Wire. Typi ally 18 to 24 gauge 3 for pulse meter onne tion.
●2 wire, twisted pair with shield for Modbus/RS485 onne tion. (Belden 1120A or equivalent)3
●Optional: Termination resistor (120 ohm) for long RS485 runs over 200ft.
3 Wire onne ted to pulse meters inside high voltage panels should have an insulation rating in ex ess of the servi e voltage.
Consult a li ensed ele tri ian and lo al building odes for further requirements that may apply.
Page 4 A8911-23