olympia electronics OLY-1004 User manual

ATTENTION!!!
CAUTION : Do not view directly with bare eyes.
X16 0A F
G
OLY-1004
SELF TESTING
MAINTAINED/NON MAINTAINED
EMERGENCY LUMINAIRE
IP42
923100403_09_003 923100403_09_003
45
60: 1 hour duration
480: 8 hours duration
F: Automatic test gear complying with IEC 61347-2-7 denoted EL-T
1: Maintained operation (*)
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
A: Including test device
G: Internally illuminated safety sign
180: 3 hours duration
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not.
Non Maintained operation: The luminaire lights its illumination source, only in mains power supply’s
failure.
OLY-1004
Olympia Electronics S.A.
10-12V DC
1h: 2W 3h: 1.6W 8h: 0.6W
2701205
50 °C max. across the board
Non reversible connection between main pcb and led module
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed
to them in writing. Products that have been damaged can be returned to the premises of our company for
repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
NOTE!! The installer should fill in, on the specification label, the letter G if the luminaire is used as a
safety sign.
European
manufacturers
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
info@olympia-electronics.gr
Non
maintained
NM
Olympia Electronics - European manufacturer
Thank you for your trust in our products
25m
Maintained
Μ
Warranty
LED Characteristics
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
CONNECTIONS
NOMINAL POWER
TEMPERATURE (tc)
OLY-1004
220-240V AC / 50-60Hz
4.5W / 4.7VA
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
3.6V/3 Ah
0.95
BATTERY (Ni-Cd)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
MINIMUM POWER FACTOR
WIRE CROSS SECTION
MAX OPEN CIRCUIT VOLTAGE
Irated
Prated
U-OUT
SUPPLY CURRENT
Basic insulation
1h: 2W 3h: 1.6W 8h: 0.6W
1h: 174mA 3h: 145mA 8h: 47mA
22V
22V
19mA
2 2
0.5mm - 2.5mm
BATTERY PROTECTION
28 white LEDs
1 h, 3 h, 8 h
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
24 hours
LED Charge, Lamp Fault LED, Battery Fault LED
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
IP42
25m
VIEWING DISTANCE (as safety sign)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE o
5 to 40 C
ABS/PC, PC
755gr.
270 x 147 x 48 mm
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
Up to 95%
3 years (1 year for the battery)
INDICATIONS
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
1h: 510-885mA 3h: 410-715mA 8h: 138-220mA
190-210mA
100mA
MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT
MAX CHARGE VOLTAGE
3-4.5V
6V
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
300lm / 350lm (1 h), 295lm (3 h), 95lm (8 h)
CONTROL GEAR MAX. TEMPERATURE:tc
o
50 C at R18/R19
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
Manual Test
Lens Removal
22
1
3
1
350/295/95lm
Light output
1h/3h/8h
Duration
The light source contained in this luminaire shall only be replaced by the manufacturer, or
his agent, or a similar qualified person.
NOTE!! The light source is non-user replaceable.
22
11
It can be done only by a competent person and after the mains interruption.
1. Follow step 1 of the installation instructions and remove the diffusor.
2. Follow step 2 of the installation instructions and remove the reflector.
3. Remove the old battery and place a new one of the same type and characteristics.
4. Replace the removed parts (previous steps 1 and 2).
Battery Replacement

A
B
A
1
1
1
1
Luminaire
Set of Pictograms
Mounting accessories
Manual
1 2
Pictogram Installation
3
Mounting Methods
22
11
o
These devices are used indoors (ta 40 C) in places
where emergency light is needed. Each device must
be permanently connected to mains power supply.
In normal operation the battery is charging. The light
source can be either on or off, depending on user’s
choice. In case of a mains power supply failure, the
device enters emergency mode and the illumination
LED turns on. When the mains power supply is
restored the device turns to normal operation.
Autonomy Duration Selection
The user can select one of the 3 available minimum
autonomy durations 1 hour, 3 hours and 8 hours. The
selection must be done while the luminaire is
disconnected from AC and battery supplies. The
selection is achieved through Switches 2 & 3 of DS1
as shown below.
Remove the diffusor and then by pressing the test
button briefly an operation test is initiated. The light
source and the emergency circuit of the device are
tested. The manual test can be conducted only if the
mains power supply and the battery are connected.
During this test period the LAMP TEST LED will blink.
The battery must have adequate charge. This test
lasts for 3 seconds.
Technical Label Installation
Two additional labels are included in the package.
one for 3 hours duration (180) and one for 8 hour
duration (480). Depending on the selected duration,
the installer must cover the default 1 hour (60)
printing with one label that has the required
duration. Please take notice of the orientation of the
label.
Manual Operational Test
Manual Autonomy Test
A duration test can be conducted by pushing the
button steadily for 5 to 10 seconds. In order to be
performed, the mains power supply should be
connected and the battery should be fully charged.
The luminaire enters emergency mode, the CHARGE
LED is turned OFF and the BATTERY FAULT LED starts
blinking. Its duration is the stated autonomy duration
of the luminaire. If at the end of the test the autonomy
The Automatic Autonomy Test is conducted every 6
months and measures the device’s back up operation
and emergency duration. This test includes all
functions of the Manual Autonomy Test.
Automatic Operational Test
5. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
4. In case of battery replacement, it must be
replaced by the same type, by the manufacturer
or a competent person.
is lower than the nominal, the BATTERY FAULT LED will
lit and battery needs to be replaced. If the result of the
test is good then the luminaire enters charging mode
and the CHARGE LED starts blinking until the battery is
fully charged.
This test includes all the operations that are provided
in Manual Operational Test and is conducted
automatically every 15 days and lasts 3 seconds.
Automatic Autonomy Test
Lens Removal
When the luminaire is used without the pictograms
or the SP-1100 and you require more light output
then remove the lens that covers the LEDs.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. Always use in any case round mains cable, with a
diameter of 5-10mm (H05RN-F type 2x1mm² or
any other type, at least equal to it’s mechanical
and electrical properties). ATTENTION!! The cable
must not be deformed in any way (This
requirement is important to ensure the ΙΡ rating).
3. The device must be connected to the mains
power supply through a circuit breaker that is
depends on the total line’s power load.
6. I s not allowed to discard batteries into t i
common trash bins, they must be discarded
only in battery recycling points. Do not
incinerate.
Oly luminaires can be surface mounted on walls or ceilings. For these mounted installations, special
accessories are included.
Wall
bottom
view Wall installation Ceiling installation
Ceiling
* ATTENTION!!! The below mounting methods can be done after request of the necessary
mounting accessories!!
Extra Mounting Methods *
Suspended ceiling installation
with mounting accessory
A-3018
The luminary can be installed in a suspended
ceiling.
Suspended installation with A-3018 accessory
A marking panel (SP-1100) can be installed on the luminary pointing the desired direction.
Suspended ceiling installation
with mounting accessories
and marking panel
Ceiling installation
with marking panel
General
5
6 7
7
8
8 9
NOTE!!
After finishing the installation you must power the luminaire for at least 24 hours in order to
completely charge the battery. The rated autonomy duration can be achieved after that time.
Package Contents
2
923100403_09_003 923100403_09_003 923100403_09_003
Drill one of the available holes with a 16-18mm drill bit. Install the included rubber gasket and pass
through the power cables. Install the included tie (if needed) to fasten and securely the power cables.
34
a
b
1h
(default position) 3h 8h
Battery Connection
Attention!! The 6 plastic
latches (A) must be secured
(click sound). This
requirement is important to
ensure the IP rating. Power
on the luminary.
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
6) Autonomy Duration Selection
(Read on General Informations, Page 1) 7 a) Pernament Maintained Operation
7 b) Non-Maintained Operation 7 c) Controlled Maintained Operation of the lamp
ON
1 2 3 4
11
10
Ν for neutral, L for live wire
WARNING!! Isolate the mains power supply before making the connections.
Ν for neutral, L for live wire WARNING!! Isolate the mains power supply before making the connections.
Description
Indications LED Status
BATT.
FAULT
(yellow)
LAMP
FAULT
(red)
CHARGE
(green)
Fully charged
Charging
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
Note:
Permanently
ON
Blink
Indifferent
Off
N
L
Link
N
L
1
Installation Instructions
or
Switch number 4 of DS1
must be in ON position.
ON
1 2 3 4
Switch number 4 of DS1
must be in OFF position.
and
ON
1 2 3 4
Switch number 4 of DS1
must be in OFF position.
and
N
L
External
switch
Other olympia electronics Light Fixture manuals
Popular Light Fixture manuals by other brands

Larson Electronics
Larson Electronics EPL-EMG-HB-50LED-RT-WLM instruction manual

ProLights
ProLights ECLIPSEFRESNELJTW user manual

Lightolier
Lightolier Calculite ProSpec PB4H3870 specification

MaxLite
MaxLite PhotonMax Series operating instructions

TINTSKY
TINTSKY TD01 manual

EuroLite
EuroLite BSL-10 user manual