Omron K8AB-PM Series User manual

Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay K8AB-PM 1
Three-phase Phase-sequence Phase-loss Relay
K8AB-PM
Ideal for monitoring 3-phase power supplies
for industrial facilities and equipment.
• Monitor overvoltages, undervoltages, phase sequence, and
phase loss for three-phase 3-wire or 4-wire power supplies with
just one Unit.
Switch setting for 3-phase 3-wire or 3-phase 4-wire power
supply.
• Two SPDT output relays, 6 A at 250 VAC (resistive load).
Output overvoltages and undervoltages using separate relays.
• World-wide power specifications supported by one Unit
(switchable).
• Output status can be monitored using LED indicator.
Model Number Structure
■Model Number Legend
1. Basic Model
K8AB: Measuring and Monitoring Relays
2. Functions
PM: Three-phase Phase-sequence Phase-loss Relay (Simultaneous upper and lower monitoring)
3. Rated Input Voltage
1: 115, 127, 133, 138, 200, 220, 230, 240 VAC
2: 220, 230, 240, 277, 380, 400, 415, 480 VAC
Single K8AB Monitors 3-phase Power Supply with 3 or 4 Wires
Monitoring Relays can be used to monitor 3-phase power supplies with 3 or 4 wires simply by changing DIP switch settings.
A Single K8AB Can Monitor a 3-phase Power Supply Anywhere in the World
Reduces Maintenance Parts Inventory
SW3 ON ON OFF OFF
SW4 ON OFF ON OFF
K8AB-P@1SW2 ON P-N 138 V 133 V 127 V 115 V
OFF P-P 240 V 230 V 220 V 200 V
K8AB-P@2SW2 ON P-N 277 V 240 V 230 V 220 V
OFF P-P 480 V 415 V 400 V 380 V
123
K8AB-@@
Phase to phase voltage (3 wires)
Phase to neutral voltage (4 wires)
L1 L2 L3 L1 L2 L3 N
400VAC
400VAC
400VAC
230VAC
230VAC
230VAC

2Three-phase Phase-sequence Phase-loss Relay K8AB-PM Cat. No. N146-E1-02
Ordering Information
■List of Models
Note: 1. Three-phase 3-wire or 4-wire and the input range are switched using a DIP switch.
2. The power supply is shared with the rated input voltage.
Ratings and Specifications
■Ratings
Three-phase Phase-sequence Phase-loss Relay Rated input (See note 2.) Model
3-phase 3-wire mode 200, 220, 230, 240 VAC K8AB-PM1
3-phase 4-wire mode 115, 127, 133, 138 VAC
3-phase 3-wire mode 380, 400, 415, 480 VAC K8AB-PM2
3-phase 4-wire mode 220, 230, 240, 277 VAC
Rated input
voltage K8AB-PM1 Three-phase, three-wire Mode: 200, 220, 230 and 240 VAC
Three-phase, four-wire Mode: 115, 127, 133 and 138 VAC
K8AB-PM2 Three-phase, three-wire Mode: 380, 400, 415 and 480 VAC
Three-phase, four-wire Mode: 220, 230, 240 and 277 VAC
Input load K8AB-PM1: 25 VA max.
K8AB-PM2: 45 VA max.
Operating value setting range (OVER, UNDER) Overvoltage
−30% to 25% of rated input voltage
Undervoltage
−30% to 25% of rated input voltage
Note: The rated input voltage can be switched using the DIP switch.
Operating value 100% operation at set value
Reset value 5% of operating value (fixed)
Reset method Automatic reset
Operating time
setting range (T) Overvoltage/undervoltage 0.1 to 30 s
Reversed phase/phase loss 0.1 s max.
Startup lock time (LOCK) 1 s or 5 s (Switched using DIP switch.)
Indicators Power (PWR): Green, Relay output (RY): Yellow, OVER/UNDER: Red
Output relays Two SPDT relays (NC operation)
Output relay ratings Rated load
Resistive load
6 A at 250 VAC (cosφ= 1)
6 A at 30 VDC (L/R = 0 ms)
Inductive load
1 A at 250 VAC (cosφ= 0.4)
1 A at 30 VDC (L/R = 7 ms)
Maximum contact voltage: 250 VAC
Maximum contact current: 6 A AC
Maximum switching capacity: 1,500 VA
Minimum load: 10 mA at 5 VDC
Mechanical life: 10,000,000 operations
Electrical life: Make: 50,000 times, Break: 30,000 times
Ambient operating temperature −20 to 60°C (with no condensation or icing)
Storage temperature −40 to 70°C (with no condensation or icing)
Ambient operating humidity 25% to 85% (with no condensation)
Storage humidity 25% to 85% (with no condensation)
Altitude 2,000 m max.
Terminal screw tightening torque 0.49 N·m
Terminal wiring method Recommended wire
Solid wire: 2.5 mm2
Twisted wires: AWG16, AWG18
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
2. Two wires can be twisted together.
Recommended ferrules
Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
Case color Munsell 5Y8/1
Case material ABS resin (self-extinguishing resin) UL94-V0
Weight Approx. 130 g
Mounting Mounted to DIN Track or via M4 screws (tightening torque: 1.2 N·m)
Dimensions 22.5 (W) ×90 (H) ×100 (D) mm

Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay K8AB-PM 3
■Specifications
Input frequency range 45 to 65 Hz
Overload capacity Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input
Setting error Operating value Set value ±10% of full scale
Operating time
Startup lock time Set value ±0.5 s
Repeat error Operating value Operating value ±2%
Error calculation: Error = ((Maximum operating value −Minimum operating value (over 10 operations))/2)/
Average value ×100%
Reset value Overvoltage: Operating value x 95% ±2%
Undervoltage: Operating value x 105% ±2%
Error calculation: Error = ((Maximum reset value −Minimum reset value (over 10 resets))/2)/Average value
×100%
Operating time Operating time repeat error: ±50 ms
Overvoltage: Measured when input suddenly changes from 70% to 120% of setting.
Undervoltage: Measured when input suddenly changes from 120% to 70% of setting.
The input voltage, however, must be between 70% and 125% of rating.
Startup lock time Startup lock time repeat error: ±0.5 s
(The operating time when the operating time is set to the minimum value and the power supply suddenly
changes from 0% to 100%.)
Temperature influence Operating value
Drift based on measured value at standard temperature:
−20°C to standard temperature: ±1,000 ppm/°C max.
Standard temperature to 60°C: ±1,000 ppm/°C max.
(Humidity: 25% to 80%)
Operating time
Fluctuation based on measured value at standard temperature:
−20°C to standard temperature: ±10% max.
Standard temperature to 60°C: ±10% max.
(Humidity: 25% to 80%)
Humidity influence Operating value
Based on ambient humidity of 65%
25% to 80%: ±5% max.
Operating time
Based on ambient room humidity
25% to 80%: ±10% max.
Influence of input frequency At 45 to 65 Hz
Operating value ±5% max.
Operating time ±10% max.
Note: The error in the operating value and operating time under standard conditions.
Applicable
standards Conforming standards EN60255-5 and EN60255-6
Installation environment (Pollution Degree 2, Overvoltage Category III)
EMC EN61326
Safety standards UL508
Insulation resistance 20 MΩmin.
Between external terminals and case
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals
Dielectric strength 2,000 VAC for one minute
Between external terminals and case
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals
Noise immunity 1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Vibration resistance Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s2
10 sweeps of 5 min each in X, Y, and Z directions
Shock resistance 100 m/s2, 3 times each in 6 directions along three axes (up/down, left/right, forward/backward)
Degree of protection Terminal section: Finger protection

4Three-phase Phase-sequence Phase-loss Relay K8AB-PM Cat. No. N146-E1-02
Connections
■Wiring Diagram
Overvoltage/Undervoltage and Phase Sequence/Phase Loss Operation Diagram
Operation Indicators
Note: 1. While phase loss is detected, Over_Ry will also be OFF.
2. The indicator flashes at 1-second intervals when reversed
phases are detected and at 0.5-second intervals during the
detection time.
Flashing Lit
Flashing
Lit
Overvoltage alarm indicator
Undervoltage setting value
Overvoltage
setting value
Undervoltage alarm indicator
Overvoltage relay
Undervoltage relay
Input
Hysteresis: Fixed at 5%
Hysteresis: Fixed at 5%
T: Operating time (0.1 to 30 s)
T: Operating time (0.1 to 30 s)
T1: Power ONlock (1 s or 5 s)
Phase loss operation Phase sequence operation
Flashing Flashing
Input
Undervoltage alarm indicator
Undervoltage relay
L1
L3
L2
L3
L2
L1
L1
L2
L3
L1
L2
L3
T1
L1
L2
L3
T
T
Note: 1. The K8AB-PM output relay is normally operative.
2. The power ON lock prevents unnecessary alarms from being generated during the
instable period when the power is first turned on. There is no relay output during timer
operation.
3. Phase loss is detected by L1, L2, and L3 voltage drops.
A phase loss will exist if any of the phases drops below 60%of the rated input.
4. L1 and L2 function both as the power supply terminals and as input terminals. If the
voltage drops dramatically, then the Relay will not operate due to an undervoltage.
5. Phase loss on the power supply or load side cannot be detected in the motor load
during operation.
Item Display Contact operation
Ry_LED Over_LED Under_LED Over_Ry Under_Ry
Over-
voltage
ON ON OFF OFF ON
Under-
voltage
ON OFF ON ON OFF
Phase
loss
OFF OFF (See
note 1.)
ON OFF
(See note
1.)
OFF
Re-
versed
phase
ON OFF Flashing
(See note
2.)
ON OFF
Correct
phase
ON OFF OFF ON ON
Load
Voltage input
Signal output
14
12
L1
L2
L3
11
L1NL2 L3
Signal output
24
22
21
Undervoltage
Phase loss,
reversed phase
Overvoltage
N

Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay K8AB-PM 5
Nomenclature
■Front Indicators
Note: The input across L1 and L2 is used for the internal power
supply. Therefore, the powerindicator will notbe lit ifthere isno
input across L1 and L2.
Setting Knobs
Note: 1. Use either a solid wire of 2.5 mm2maximum or a ferrule with
insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted
into the terminal must be 8 mm or less to maintain dielectric
strength after connection.
Recommended ferrules
Phoenix Contact
•Al 1,5-8BK (for AWG16)
•Al 1-8RD (for AWG18)
•Al 0,75-8GY (for AWG18)
2. Tightening torque
Recommended: 0.49 N·m
Maximum: 0.54 N·m
Power indicator
Relay status indicator
Overvoltage knob
(OVER)
Undervoltage knob
(UNDER)
Operating time knob (T)
Alarm indicator
Terminal block
(See notes 1 and 2.)
Terminal block
(See notes 1 and 2.)
0.1
Item Meaning
Power indicator
(PWR: Green) Lit when power is being supplied (see note).
Relay status indicator
(RY: Yellow) Lit when relay is operating (normally lit).
Alarm
indicator Overvoltage:
Red Lit when there is an overvoltage.
Theindicator flashestoindicatetheerrorstatus after
the overvoltage has exceeded the threshold value
while the operating time is being clocked.
Undervoltage:
Red •Lit when there is an undervoltage or phase loss.
The indicator flashes to indicate the error status
after the undervoltage has exceeded the threshold
value while the operating time is being clocked.
•Lit when there is a phase sequence error.
Item Usage
Overvoltage knob
(OVER) Can be set between −30% and 25% of the rated
input.
Undervoltage knob
(UNDER) Can be set between −30% and 25% of the rated
input.
Operating time knob (T) Used to set the operating time to 0.1 to 30 s.
For 2.5 mm2or
smaller solid wires For ferrules with
insulating sleeves
8 mm max. 8 mm max.

6Three-phase Phase-sequence Phase-loss Relay K8AB-PM Cat. No. N146-E1-02
■Operation and Setting Methods
Connections
1. Input
Connect to L1, L2, and L3 (for three-phase three-wire mode) or L1, L2, L3, and N (for three-phase four-
wire mode), depending on the mode selected using pin 2 on the DIP switch.
The Unit will not operate correctly if the DIP switch setting and the wiring do not agree.
Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase
sequence is incorrect.
2. Outputs
Terminals 11, 12, and 14 are the output terminals for overvoltage (SPDT).
Terminals 21, 22, and 24 are the output terminals for undervoltage, phase loss, and reversed phase
(SPDT).
DIP Switch Settings
The power ON lock time, number of wires, and rated voltage are set using the DIP switch located on the bottom of the Unit.
Load
Voltage input
Signal output
14
12
L1
L2
L3
11
L1NL2L3
Signal output
24
22
21
Undervoltage
Phase loss,
reversed phase
Overvoltage
N
ON
OFF
SW1
SW2
SW3
SW4
DIP switch
DIP Switch Functions
K8AB-PM1
Note: All pins are set to OFF at the factory.
K8AB-PM2
Note: All pins are set to OFF at the factory.
SWITCH ON ●↑
OFF ❍↓
Power ON lock
time 5 s --- --- --- ●
1 s --- --- --- ❍
Number of wires Three-phase, four-wire --- --- ●---
Three-phase, three-wire --- --- ❍---
Rated voltage Three-phase,
three-wire Three-phase,
four-wire
240 V 138 V ●●--- ---
230 V 133 V ●❍--- ---
220 V 127 V ❍●--- ---
200 V 115 V ❍❍--- ---
SWITCH ON ●↑
OFF ❍↓
Power ON lock
time 5 s --- --- --- ●
1 s --- --- --- ❍
Number of wires Three-phase, four-wire --- --- ●---
Three-phase, three-wire --- --- ❍---
Rated voltage Three-phase,
three-wire Three-phase,
four-wire
480 V 277 V ●●--- ---
415 V 240 V ●❍--- ---
400 V 230 V ❍●--- ---
380 V 220 V ❍❍--- ---
ON
OFF
43
32 1
ON
OFF
43
32 1

Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay K8AB-PM 7
lSetting Method
1. Overvoltage
The overvoltage knob (OVER) is used to set the overvoltage threshold.
The overvoltage can be set to between −30% and 25% of the rated input voltage.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the voltage.
The rated input depends on the model and DIP switch setting.
Example: K8AB-PM1 with Pin 2 Turned OFF (Three-phase, Three-wire Mode) and Pins 3 and 4 Turned OFF (Rated Voltage of 200 V)
The rated input voltage is 200 VAC and the setting range is 140 to 250 V.
2. Undervoltage
Undervoltage is set using the undervoltage knob (UNDER).
The undervoltage can be set to between −30% and 25% of the rated input.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the voltage.
The rated input depends on the model and DIP switch setting.
Example: K8AB-PM1 with Pin 2 Turned OFF (Three-phase, Three-wire Mode) and Pins 3 and 4 Turned OFF (Rated Voltage of 200 V)
The rated input voltage is 200 VAC and the setting range is 140 to 250 V.
3. Operating Time
The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the operating time.
If the input exceeds (or drops lower than) the voltage setting, the alarm indicator will start flashing for the set period and then stay lit.
Dimensions (Unit: mm)
Three-phase Voltage with Phase-sequence, Phase-loss Relays
22.5 100
72
90
5
5
K8AB-PM1
K8AB-PM2

8Three-phase Phase-sequence Phase-loss Relay K8AB-PM Cat. No. N146-E1-02
Safety Precautions
■Precautions for Safe Use
Make sure to follow the instructions below to ensure safety.
1. Do not use or keep this product in the following environments.
•Outdoors, or places subject to direct sunlight or wearing
weather.
•Places where dust, iron powder, or corrosive gases (in
particular, sulfuric or ammonia gas) exist.
•Places subject to static electricity or inductive noise.
•Places where water or oil come in contact with the product.
2. Make sure to install this product in the correct direction.
3. There is a remote risk of electric shock. Do not touch terminals
while electricity is being supplied.
4. Make sure to thoroughly understand all instructions in the
Instructions Manual before handling this product.
5. Make sure to confirm terminal makings and polarity for correct
wiring.
6. Tighten terminal screws firmly using the following torque.
Recommended tightening torque: 0.49 N·m
Maximum tightening torque: 0.54 N·m max.
7. Operating ambient temperature and humidity for this product
must be within the indicated rating when using this product.
8. There is a remote risk of explosion. Do not use this product where
flammable or explosive gas exists.
9. Make sure that no weight rests on the product after installation.
10.To enable an operator to turn off this product easily, install
switches or circuit breakers that conform to relevant requirements
of IEC60947-1 and IEC60947-3, and label them appropriately.
■Precautions for Correct Use
For Proper Use
1. Do not use the product in the following locations.
•Places subject to radiant heat from heat generating devices.
•Places subject to vibrations or physical shocks.
2. Make sure to use setting values appropriate for the controlled
object. Failure to do so can cause unintended operation, and may
result in accident or corruption of the product.
3. Do not use thinner or similar solvent for cleaning. Use commercial
alcohol.
4. When discarding, properly dispose of the product as industrial
waste.
5. Only use this product within a board whose structure allows no
possibility for fire to escape.
About Installation
1. When wiring, use only recommended crimp terminals.
2. Do not block areas around the product for proper dissipation of
heat. (If you do not secure space for heat dissipation, life cycle of
the product will be compromised.)
3. To avoid electrical shocks, make sure that power is not supplied to
the product while wiring.
4. To avoid electrical shocks, make sure that power is not supplied to
the product when performing DIP switch settings.
Noise Countermeasures
1. Do not install the product near devices generating strong high
frequency waves or surges.
2. When using a noise filter, check the voltage and current and
install it as close to the product as possible.
3. In order to prevent inductive noise, wire the lines connected to the
product separately from power lines carrying high voltages or
currents. Do not wire in parallel with or on the same cable as
power lines.
Other measures for reducing noise include running lines along
separate ducts and using shield lines.
To avoid faulty operations,
malfunctions, or failure, observe the
following operating instructions.
1. When turning on the power, make sure to realize rated voltage
within 1 second from the time of first supply of electricity.
2. Make sure to use power supply for operations, inputs, and
transformer with the appropriate capacity and rated burden.
3. Maintenance and handling of this product may only be performed
by qualified personnel.
4. Distortion ratio of input wave forms must be 30% or less. Use of
this product with circuits that have large distortion in wave forms
may result in unwanted operations.
5. Using this product for thyristor controls or inverters will result in
errors.
6. When setting the volume, adjust the control from the minimum
side to the maximum side.

Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay K8AB-PM 9
Checking Operation
Overvoltages
Gradually increase the input from 80% of the setting.
The input value will equal the operating value when the
input exceeds the setting and the alarm indicator starts
flashing. Operation can be checked by the relay output that
will start after the operating time has passed.
Undervoltage
Gradually decrease the input from 120% of the setting and
check the operation using the same method as for
overvoltage.
Example: For monitoring mode set to three-phase three-wire
monitoring, a rated voltage of 200 V, and an operating time
of 5 s.
Note: K8AB-PM@output relays are normally operative.
Connection Diagram 1
How to Measure the Operating Time
Overvoltage
Change the input suddenly from 0% to 120% of the set
value and measure the time until the Unit operates.
Undervoltage
Change the input suddenly from 120% to 0% of the set
value and measure the time until the Unit operates.
Operating Time
Adjust the slide resistor so that the voltage applied to the
K8AB terminals is 120% of the set value (for overvoltage
detection) and 80% of the set value (for undervoltage
detection) when the auxiliary relay operates, as shown in
connection diagram 2. Close the switch and use the cycle
counter to measure the operating time.
Connection Diagram 2
Checking the Phase Sequence and Phase Loss
Operation
Phase Sequence
Switch the wiring, as shown by the dotted lines in
connection diagram 1, to reverse the phase sequence and
check that the K8AB operates.
Phase loss
Create a phase loss for any input phase and check that the
K8AB operates.
Operating Adjustment Knobs
Use a screwdriver to turn the knobs. There is a stopper to
prevent the knob from turning any further once it has been
turned completely to the left or right. Do not force the knob
past these limits.
Questions and Answers
Q
Operating set value
Input voltage
Alarm indicator
Relay output
Flashing
Lit
5 s
0 to 150 V
V1
Three-phase variable
autotransformer
Overvoltage
Undervoltage
L1
L2
L3
3φ,
200 VAC V2 V3
L1
L2
L3
Q
3φ, 200 VAC
L1
L2
L3
±C 200 V
Cycle counter
V1
V2 V3
X
X/a X/b
L1
L2
L3
R1
R2
R1: Slide resistor
200 Ω200 W
R2: 100 Ω400 W
Q
Q

10 Three-phase Phase-sequence Phase-loss Relay K8AB-PM Cat. No. N146-E1-02
Load-side Phase Loss
In principle, phase loss cannot be detected on the load side
because the K8AB-PM@measures three-phase voltage to
determine phase loss.
Motor Load Phase Loss during Operation
Motor load phase loss cannot be detected during operation.
It can be used to detect phase loss at startup.
Normally, three-phase motors will continue to rotate even if
one phase is open. The three-phase voltage will be induced
at the motor terminals. The diagram shows voltage induction
at the motor terminals when phase R has been lost with a
load applied to a three-phase motor. The horizontal axis
shows the motor load as a percentage of the rated load, and
the vertical axis shows voltage as a percentage of the rated
voltage. The lines in the graph show the voltage induced at
the motor terminals for each load phase loss occurs during
operation. As the graph shows, phase loss cannot be
detected because the motor terminal voltage does not drop
very much even if a phase is lost when the load on the motor
is light. To detect motor load phase loss during operation,
use the undervoltage detection function to detect the motor
terminal voltages at phase loss.
Set the operating time carefully because it will affect the time
from when the phase loss occurs until tripping when this
function is used.
Characteristic Curve Diagram
Note: For phase loss of phase R. VST, VTR, and VRS indicate the motor
terminal voltage at phase loss.
Overvoltage Detection When Only One Phase Exceeds
the Overvoltage Threshold
The K8AB-PM@monitors each of the three-phase voltages.
This means an overvoltage is detected if even only one
phase exceeds the threshold value. The same applies to
undervoltages.
Questions and Answers
Q
Q
100
95
90
85
80
75
70
65
60
55
50
45
100 2030405060708090100110
VST
VTR
VRS
Note: This characteristic curve shows the approximate
values only.
Voltage (as a percentage of rated voltage)
Motor load (as a percentage of rated load)
Q

Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay K8AB-PM 11

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
© OMRON Corporation 2009 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Tokyo, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Cat. No. N146-E1-02 Printed in Japan
0706-0.7M (0505) (C)
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRONrepresentative if you have any
questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other
period if specified) from date of sale by OMRON.
OMRONMAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES
THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS
OF THEIR INTENDED USE. OMRONDISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRONSHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR
COMMERCIAL LOSS INANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ONCONTRACT,
WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRONfor any act exceed the individual price of the product on which liability is asserted.
INNO EVENT SHALL OMRONBE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS
UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND
MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATIONOR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRONshall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in
the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used.
Knowand observe all prohibitions of use applicable to this product.
NEVERUSETHEPRODUCTSFOR ANAPPLICATIONINVOLVING SERIOUSRISKTOLIFEORPROPERTYWITHOUTENSURING
THAT THE SYSTEM AS A WHOLE HAS BEENDESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRONPRODUCTS ARE
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHINTHE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty.
It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual
performance is subject to the OMRONWarranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your
OMRONrepresentative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
CSM_1_5_0114
Other manuals for K8AB-PM Series
1
This manual suits for next models
2
Table of contents
Other Omron Relay manuals

Omron
Omron MK-I - User manual

Omron
Omron ZEN User manual

Omron
Omron MY4H User manual

Omron
Omron K8AB-PA1 User manual

Omron
Omron K6EL User manual

Omron
Omron K8AK-VW User manual

Omron
Omron ZEN 10 User manual

Omron
Omron K8AK-AS User manual

Omron
Omron G9SB - DATASHEET 1 User manual

Omron
Omron K8AB-TH User manual

Omron
Omron ZEN User manual

Omron
Omron K8AK-TH User manual

Omron
Omron K8AK-AS1 24VAC/DC User manual

Omron
Omron K8DT-VW User manual

Omron
Omron G3PC User manual

Omron
Omron G3PA-VD Series User manual

Omron
Omron G7J - User manual

Omron
Omron K8DT-PM User manual

Omron
Omron ZEN-8E Use and care manual

Omron
Omron K8AK-VW2 24 VAC/DC User manual