http://www.hicoolopticlimate.com/
7
3. Compressorstartswithdelayafterexternalwatervalvestarts.
Afterexternalwatervalveworksfor9seconds,systemstartscompressoraftermakingsurethecirculating
waterfillstheheatexchanger.
4. Loadingandunloadingwithtimedelay.
Toavoiddestroytopowersupplynet,compressorscanonlystartwithtimegapof 〖Cd〗seconds.
5. Balancerunningtimeofcompressors.
Toreachthebalanceofrunningtimeforeachcompressor,compressorstartfirstwillstopfirst.
6. Lightintensityishigherthansettingvalue Coolingindaytime.
Systemworksforcoolingonlyaccordingtosettingvalue.Thesettingrangeis18~32 withaccuracyof
1,compressorstartswithtimedelayof30s.
7. Lightintensityislowerthansettingvalue Heatinginnighttime.
A)Whenindoortemperature <heatingsettingtemperature,systemworksforheating;
B)Heatingmode(Withauxiliaryelectricalheaters,compressordoesnotstart),temperaturesettingrangeis
18~32 withaccuracyof1 .
Theindoortemperatureislowthanthesettemperature2 ,electricheaterstart.
Theindoortemperatureishigherthanthesettemperature,electricheatingstop.
C)Dehumidificationmode:Thehumidityintheeveningexceedsthesethumidityvalue,dehumidification
modeisturnedon(thedehumidificationmodeisnotneededduringthedaytime).
Lessthanthesethumidityvalue-humiditydifferenceD[5],turnoffthedehumidificationmode.
8. Lightscontrol
Duringdaytime,whentheindoortemperatureisgreaterthanb[F] (default),thelightcontrolrelayis
closed(therelayisnormallyclosed,thelightisturnedon),andthelightisturnedoff.Thecontroltemperature
differenceis5°C,iethelightrelayisdisconnectedwhentheindoortemperatureisbelowb[F]-5 (default).
9. Illuminationcontrol
Whentheilluminanceisgreaterthanthe(bA)setting,themodeisdaytimemode
Whentheilluminanceislessthan(bA)-(bE) ,themodeisnighttimemode.When(bA)-(bE)islessthan
(bA),thecurrentmodeismaintained.
10. Watervalvecontrol
A)Start/stopwiththecompressor.Beforethecompressorstarts,thewatervalveisopenedfirst,andthedelay
timeis10Stodetectthestatusofthewaterflowswitch.Whentherehavewaterflow,thecompressorcanbe
turnedon;afterthecompressorstops,thedelaytimeis10stoclosethewatervalve.
11. Drainpumpcontrol
Afterthecondensatelevelswitchisclosed,thedrainpumpstartstorun.Afterthecondensatelevelswitchis
disconnected,turnoffthedrainpumpafterc[7]seconds.
2.5Systemprotectionsanderrorcode
Controllerwillstartrelativeprotectionsfordifferenterrors,andshowtheerrorcodeondisplay.Errorcode
showsatclockposition(88:88)withEE:XX.
EE : XX
Error Errorcode