Ormazabal velatia ekor.bat-200 Instruction manual

LIB
ekor.bat-200
Battery Charger
General Instructions
IG-258-EN, version 02, 16/11/2018

In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject
to change without prior notice. These characteristics, as well as the availability of components, are subject to confirmation by
Ormazabal.
CAUTION!
When medium-voltage equipment is operating, certain components are live, other parts may be in movement and some may
reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
• Elimination of hazards wherever possible.
• Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
• Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protective equipment.
• Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the
environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of Standard
IEC 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the
requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near
electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other
recommendations of a more general nature which are applicable to the situation according to current legislation[1].
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also
on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
• The equipment must be handled and transported appropriately from the factory to the place of installation.
• All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment
or its essential components.
• Service conditions must be compatible with the equipment rating.
• The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable
operating and safety principles must be clearly understood.
• Maintenance should be performed properly, taking into account the actual service and environmental conditions in
the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Warranty
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual
belongs to Ormazabal.
[1] For example, in Spain the “Regulation on technical conditions and guarantees for safety in high-voltage electrical installations” – Royal Decree
337/2014 is obligatory.

3
General Instructions
ekor.bat-200
Contents
IG-258-EN, versión 01; 16/11/2018
Contents
1. Description and main characteristics.......................4
1.1. Definition....................................4
1.2. Architecture .................................4
1.3. Processes ....................................4
1.3.1. Start-up and battery connection..............4
1.3.2. Battery charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.3.3. Battery discharge and disconnection .........5
1.3.4. Slow test or capacity measurement...........6
1.3.5. Fast test or Impedance measurement.........6
2. Characteristics............................................................7
2.1. Electrical characteristics ......................7
2.2. Dielectric strength ...........................7
2.3. Service conditions ...........................8
2.4. CE Conformity ...............................8
3. Tests ............................................................................9
3.1. ekor.bat-200 battery charger.................9
4. Connections..............................................................11
4.1. Terminal blocks .............................11
4.2. LED indications .............................12
4.3. Alarms......................................12
4.4. Front button (B1) ...........................13
4.5. Earthing ....................................13
5. Web access................................................................14
6. Unit configuration ...................................................15
6.1. Operating parameters.......................15
6.1.1. Communications parameters................16
7. Equipment test.........................................................17
7.1. Force states .................................17
7.2. Hardware test...............................17
8. On-site intervention procedures ............................18
8.1. Battery replacement ........................18

IG-258-EN, version 02; 16/11/2018
4
Description and main characteristics General Instructions
ekor.bat-200
1. Description and main characteristics
1.1. Definition
The ekor.bat-200 unit is a 24 Vdc or 48 Vdc battery charger,
depending on the model, for connection of units which
feed Ormazabal cubicles.
1.2. Architecture
The ekor.bat-200 charger is a UPS where the battery is
connected to the output, as shown in the image below.
1Input
2Output
310 kV insulation
4Phase
5Neutral
6AC
7DC
8+ 24/48 Vdc
90 V
10 Earth
11 Chassis
12 Control
13 Alarms
14 Local signalling
15 Ethernet RS232
Figure 1.1. Unit architecture
1.3. Processes
1.3.1. Start-up and battery connection
When the unit is connected at 230 Vac, it is energised at this
instant since the unit does not have an on switch.
When the charger is energised, the initial PowerUP process
extracts output voltage and checks that there are batteries
connected; if there are, the internal contact closes, starting
the battery charge process.

IG-258-EN, version 02; 16/11/2018 5
General Instructions
ekor.bat-200
Description and main characteristics
1.3.2. Battery charge
Battery charge starts following absence of alternating
current voltage (AC) or after a battery test.
The battery charge process starts with fast charge state.
The charger establishes a voltage setpoint (v_carga) and
controls battery current to ensure it does not exceed
maximum charge current (i_lim). Current is lost as the
battery discharges.
It switches from fast charge state to floating for either of the
following two reasons:
1. The maximum time set for fast charge state (tlim_carga)
is exceeded.
2. The battery current drops below a set threshold (i_flot).
Once the battery current drops below a minimum threshold
(i_flot) or maximum time is exceeded (tlim_carga), it passes
to floating state. In this state the charger establishes the
battery float voltage (v_flot). Following a float time interval
(tmin_flot), it is taken that the battery is completely charged.
The unit remains in floating state until there is an absence of
alternating current or a battery test starts.
The image below shows the typical charge process of a
battery.
In order to extend the working life of the battery, battery
voltage is compensated in accordance with temperature
in floating state. A parametrisable variable (comp_flot)
can be used to adjust the voltage to vary by each degree
centigrade.
The compensation range is limited between a maximum
and minimum temperature (comp_tmin and comp_tmax).
Temperature compensation (hab_comp) can also be
enabled in fast charge state, and there is a voltage variation
setting by degree (comp_carga). Enabling this option is only
recommended when a study indicates that it is required.
1Current (A)
2Voltage (V)
3Time
4Fast charge at constant current
5Fast charge at constant voltage
6Floating
7v_carga
8v_flot
9i_lim
10 i_flot
aVoltage per cubicle
bCharging current
Figure 1.2. Battery charge
1.3.3. Battery discharge and disconnection
In the event of absence of alternating voltage, the batteries
keep the equipment supplied for a specific time interval. A
disconnection process starts if end of battery life is reached
and the alternating voltage input is not restored.
The following operation guidelines are followed in the
disconnection process:
• The unit detects that battery life reaches its end using a
parametrisable setting (desc_v_min)
• The "End of battery life" alarm is enabled at this moment.
• If the AC input is not restored after a few minutes on
standby, the unit disconnects the battery and both the
unit and the connected charges therefore go off.
Apart from the normal discharge process, there are two
other reasons for the battery disconnecting:
• Minimum battery voltage (desc_inm). If it drops below
this threshold, the battery disconnects instantaneously.
• Maximum battery voltage (desc_v_max). If this level is
exceeded, the battery disconnects for safety reasons.

IG-258-EN, version 02; 16/11/2018
6
Description and main characteristics General Instructions
ekor.bat-200
1.3.4. Slow test or capacity measurement
The unit has an automatic mechanism implemented, which
regularly carries out a battery capacity test.
The test consists of:
• The capacity supplied by the battery is measured until:
- The minimum capacity indicated in the standard
(cap_desc) is reached, in which case the test is
passed.
- The maximum time defined for each attempt (tlim_
prueba) is reached, in which case the test is passed.
- The voltage of the battery used to fail the test (v_fin)
drops, in which case:
- If not all the envisaged re-attempts have been
carried out (rein), the battery charges and a test
attempt starts.
- If all attempts have been made, the test is failed and
the "Battery failure" alarm is generated.
Whenever a battery test is failed, the "Battery failure" alarm
is generated and no more battery tests are carried out
until this alarm is recognised. The "Battery failure" alarm is
grouped within the "Urgent failure" digital output.
1.3.5. Fast test or Impedance measurement
The fast test or battery impedance test consists of subjecting
the battery to a specific consumption in order to determine
whether it is still in a good state.
The user can carry out the "battery test" whenever
considered necessary, provided the system is floating or in
constant voltage.
Start-up can be forced using the "Forced battery test"
button in the charger's web. The result of the test is
transmitted immediately to the outside via a potential-free
alarm contact ("Urgent Alarm").
Figure 1.4 shows the response of a battery in poor state.
Figure 1.3. Battery in good state
Figure 1.4. Battery in poor state
In any case, this test is merely to indicate battery state.
If the result is that the battery is in a poor state, repeating
the test after charging for several hours and in floating
state is recommended, in order to ensure the battery was
correctly charged at the moment of the test.

IG-258-EN, version 02; 16/11/2018 7
General Instructions
ekor.bat-200
Characteristics
2. Characteristics
This section describes the main characteristics of the
ekor.bat-200 unit.
2.1. Electrical characteristics
The characteristics of the input are as follows:
Parameter Remarks Value Unit
Rated input voltage 230 Vac
Input voltage range 160…300 Vac
Input frequency range Compatible with 50/60 Hz 50…60 Hz
Start-up current < 20 A
Power factor. > 0.6
Rated power 200 W
Maximum power 500 W
Output range 48 Vcc = 39..60
24 Vcc = 18..30 V
Table 2.1. Input characteristics
The charger has four potential-free contacts.
Parameter Remarks Value Unit
Rated Voltage 24 / 48 Vdc
Maximum current 100 mA
Table 2.2. potential-free contacts
2.2. Dielectric strength
The unit withstands dielectric rigidity tests at a leakage
current of < 10 mA for the voltage indicated during 1
minute between the following parts:
• Input vs. (Output + Alarms + Temp. Sensor + Communic.
+ Earth) = 10 kVAC(Output + Temp. Sensor) vs. Earth =
2500 VAC
• Alarms vs. Earth = 1000 VAC
• Communications vs. Earth = 1000 VAC

IG-258-EN, version 02; 16/11/2018
8
Characteristics General Instructions
ekor.bat-200
2.3. Service conditions
Parameter Remarks Value Unit
Operating temperature - 40…60 °C
Storage temperature - 40…80 °C
Relative humidity Without condensation 5…90 %
Altitude Above sea level < 2000* m
Refrigeration Natural convection 0 m3/s
Environmental requirements RoHS, Directive 2002/95/CE
Table 2.3. Service conditions
For higher altitudes, check with Ormazabal for the
possible influence on equipment performance.
2.4. CE Conformity
This product complies with European Union Directive
2014/30/EU on electromagnetic compatibility, and with
IEC 60255 international standards. The unit has been
designed and manufactured for use in industrial areas, in
accordance with EMC standards. This conformity is a result
of the test carried out in accordance with article 7 of the
Directive.

IG-258-EN, version 02; 16/11/2018 9
General Instructions
ekor.bat-200
Tests
3. Tests
3.1. ekor.bat-200 battery charger
Radioelectrical interference Level Standard
Conducted radioelectrical emissions in power terminals
Level to be applied Class A, Output 24/48 Vdc
Class B, AC input EN 55022
Radiated radioelectrical emissions measurement
Level to be applied Class B, distance at 3 m EN 55022
Insulation Level Standard
Dielectric strength measurement
Power terminal, industrial frequency 10 kVac rms EN 60255-5
Power terminal, lightning impulse 30 imp, 20 kV EN 60255-5
Direct current terminal, industrial frequency 2.0 kVac/50 Hz EN 60255-5
Power terminal, lightning impulse 10 imp, 2 kV, 1.2/50 µs EN 60255-5
COM terminals, industrial frequency 1 kVac/50 Hz EN 60255-5
COM terminals, lightning impulse 10 imp, 2 kV, 1.2/50 µs EN 60255-5
Insulation resistance measurement
Direct current voltage between each group and earth ± 500 Vdc EN 60255-5
Minimum insulation strength > 100 MΩ after 5 s EN 60255-5
Insulation measurement with voltage impulses
Voltage between each group and earth, common mode ± 5 kV EN 60255-5
Voltage between terminals of each unit, differential mode ± 1 kV EN 60255-5
Immunity Level Standard
Electrostatic discharge
Direct contact mode: in metal equipment frames and connectors Level 4 (± 8 kV) EN 6100-4-2
Air mode: in all air faces Level 4 (± 15 kV) EN 6100-4-2
Radiofrequency electromagnetic eld
Level to be applied Level 3 (10 V/m) EN 61000-4-3
Fast transients in bursts
Alternating current power terminals Level 4 (± 4 kV) EN 61000-4-4
Direct current power terminals Level 4 (± 500 V) EN 61000-4-4
Ethernet, serial and others interface terminals Level 4 (± 2 kV) EN 61000-4-4
Shock wave
Alternating current power terminals, common mode Level 4 (± 4 kV) EN 61000-4-5
Alternating current power terminals, differential mode Level 4 (± 2 kV) EN 61000-4-5
Direct current power terminals, common mode Level 4 (± 500 V) EN 61000-4-5
Digital outputs, common mode Level 4 (± 2 kV) EN 61000-4-5
Digital outputs, differential mode Level 4 (± 1 kV) EN 61000-4-5
Other terminals, common mode Level 4 (± 2 kV) EN 61000-4-5
RF eld conducted interference
Level to be applied Level 3 (10 V, 150 kHz-80 MHz) EN 61000-4-6
Industrial frequency electromagnetic eld
Unit enclosure
Level 5
(100 A/m, 50 Hz, 1 min)
Grade 1
Level 5
(1000 A/m, 50 Hz,1 s)
Grade 1
EN 61000-4-8
Damped oscillatory magnetic eld
Level to be applied Level 5 (100 A/m),
Grade 1 EN 61000-4-10
Continues on the next page

IG-258-EN, version 02; 16/11/2018
10
Tests General Instructions
ekor.bat-200
Continuation
Immunity Level Standard
Oscillatory damped wave
Damped wave. Common mode Level 3 EN 61000-4-18
Damped wave. Differential mode Level 3 EN 61000-4-18
Low frequency harmonics
Power terminals Level 2 EN 61000-4-13
Electrical tests Level Standard
Holes, variations and zero-voltages in alternating current
Level to be applied Level 3 EN 61000-4-11
Power supply voltage
Level to be applied 230 Vac ± 30 %
Current peaks (start-up at rated power)
Level to be applied < 12 A
Mechanical tests Level Standard
IP Protection grade
Level to be applied IP20 EN 20324
IK Protection grade
Level to be applied IK06 EN 50102
Vibration
Level to be applied Class 2.3 Random EN 300 019-2-2
Drop
Level to be applied Class 2.3 , < 20 kg EN 300 019-2-2
Climatic Tests Level Standard
Damp heat
Level to be applied 40 °C/93 %/4 days EN 60068-2-78
Dry heat
Level to be applied Be type. 70 °C/16 h EN 60068-2-2
Cold heat
Level to be applied Ae type. - 40 °C/24 h EN 60068-2-2
Temperature variation
Level to be applied
Cold temp. = - 25 °C
Hot temp. = 60 °C
Duration = 5 cycles lasting 3 h each
EN 60068-2-14
Table 3.1. ekor.bat-200 Battery charger

IG-258-EN, version 02; 16/11/2018 11
General Instructions
ekor.bat-200
Connections
4. Connections
1AC Input (X1)
2Alarms (X2)
3Temperature sensor (X3)
4DC Output (X4)
5Serial line (COM1)
6Ethernet 3 (ETH3)
7Ethernet 2 (ETH2)
8Ethernet 1 (ETH1)
9Button (B1)
10 LED indications
Figure 4.1. Conections of the charger.
4.1. Terminal blocks
Terminal block Pins Signal Characteristics
X1
Input
1 AC input, L phase 230 Vac rms
2 AC input, N phase
X2
Alarms
1 Urgent failure alarm NC contact
2 Standalone end alarm NA Contact
3 Power failure alarm NA Contact
4 Non-urgent failure alarm NA Contact
5 Alarms common
X3
Temperature measurement
1 Temp. Sensor 1
2 Temp. Sensor 2
3 Temp. Sensor 3
X4
DC Output
1 Earth
2Free No connection
3 Positive terminal battery
4 Negative terminal battery
5 Positive terminal output
6 Negative terminal output
COM1 1-9 Serial line RS232
ETH1, ETH2 1-8 Ethernet Port
ETH3 1-8 Ethernet Port
B1 1 Pushbutton. Start up from batteries
Table 4.1. Description of charger terminal blocks

IG-258-EN, version 02; 16/11/2018
12
Connections General Instructions
ekor.bat-200
4.2. LED indications
The charger has eight light indicators. Some of these can
show double signalling. The indications only use a flashing
frequency.
LED Text Mode Associated function
Green Power ON On Charger running on battery or network
Green Battery charging Flashing Charge mode: Fast. (Constant voltage)
On Charge mode: Floating
Green Battery test On Working battery test
Yellow Battery discharging On Battery discharging
Red VAC IN ERROR Flashing Network input outside of permitted margins
Red VDC OUT ERROR Flashing 24/48 Vdc output outside of permitted margins
Red Battery ERROR Flashing Absence of battery, battery disconnected
On Battery test failure, end of battery's working life
Red Charger ERROR Flashing Anomalies in charger. Temperature sensor, others…
On Temperature sensor failure
Table 4.2. Description of the indications by LED
4.3. Alarms
Name Logic
Input network failure The contact is open in normal operation.
It closes if AC voltage input is out of range, or there is an absence of AC voltage.
Urgent charger-rectier failure
The contact is open in normal operation.
It closes if:
• There is no battery connected.
• Battery Test Failure.
• Urgent internal failures.
• Charger temperature out of range.
Non-urgent charger-rectier failure
The contact is open in normal operation.
It closes if:
• Max battery voltage
• Temperature sensor error
• Output voltage out of range.
• Battery temperature out range.
End of battery life The contact is open in normal operation.
It closes if battery voltage drops below minimum discharge voltage.
Table 4.3. Alarms

IG-258-EN, version 02; 16/11/2018 13
General Instructions
ekor.bat-200
Connections
4.4. Front button (B1)
The ekor.bat-200 charger has a button for the following
actions.
• In total disconnection state. In other words, with charger
off, without alternating voltage input and batteries
connected. If the button is pressed for 5 seconds, the
unit starts up from batteries, provided battery voltage
has an admissible value greater than the minimum
parameterised.
• With the unit running at constant voltage or floating,
the system carries out a battery reconnection in order
to check they are connected whenever the button is
pressed for more than 3 seconds. If there is a battery
connected, the charge process continues and the
battery test failure alarm resets if it is enabled. If there
is no battery, the urgent alarm due to non-connected
battery is enabled.
4.5. Earthing
When installing the equipment, it must be checked that it
is duly earthed. It must be ensured that the charger's two
earth points are duly connected.
Firstly, there is a check by initiation to ensure that earthing
has been carried out correctly in the terminal block. See
section 4.1 for the position of the earth terminal in the
terminal blocks.
It is then confirmed that the earth connection for the chassis
has been carried out correctly. The image below shows the
location of the earth connection.
Figure 4.2. Earthing connection in the chassis

IG-258-EN, version 02; 16/11/2018
14
Web access General Instructions
ekor.bat-200
5. Web access
The access port, both locally and remotely, is via the ETH1
port.
Access to the charger's webpage is via the ETH1 port,
both locally and remotely.
• LOCAL IP: 100.0.0.1
• Remote IP: Customised with the requested value
Firefox browser version 26 is recommended for an optimal
navigation experience.
1ETH3
2ETH1: Local/remote access
3ETH2
4ETH2 and ETH3, external bridge
Figure 5.1. Web access of ekor.bat-200.

IG-258-EN, version 02; 16/11/2018 15
General Instructions
ekor.bat-200
Unit configuration
6. Unit configuration
6.1. Operating parameters
Access via the web can be used to configure the charger
parameters in a dedicated menu.
Name Description Unit
AC INPUT
vin_max AC Input voltage: Upper limit V
vin_min AC Input voltage: Lower limit V
BATTERY – TYPE
tec Type of technology: PB, NC... or others 8 char
cap Battery capacity in amps hour (Ah) Ah
BATTERY – CHARGE ADJUSTMENT
ilim Battery charge maximum current A
comp_tmax Maximum temperature to apply temperature compensation °C
comp_tmin Minimum temperature to apply temperature compensation °C
BATTERY – FLOATING
v_ot Floating battery charge voltage V
comp_ot Floating temperature compensation mV/C
tmin_ot Minimum time to consider floating battery h
BATTERY – FAST CHARGE
v_carga Battery charge voltage in fast charge (V) V
comp_carga Temperature compensation in fast charge mV/C
hab_comp Enables temperature compensation in charge 0:NO/1:YES
i_ot Battery through-current to float mA
tlim_carga Maximum time to remain in fast charge h
BATTERY – BATTERY TEST
v_n Battery test: Battery voltage limit to fail the test V
period Battery test: Limit time for each test attempt Weeks
cap_desc Battery test: Discharge capacity Ah
tlim_prueba Battery test: Limit time for each test attempt h
rein Battery test: Number of attempts Units
BATTERY – ALARMS
tbat_alta Battery maximum temperature °C
tbat_baja Battery minimum temperature °C
vbat_min Battery output voltage: Lower limit V
cap_min Battery minimum capacity %
BATTERY – DISCONNECTION
desc_v_max Cut-out voltage: Upper limit V
desc_v_min Cut-out voltage: Lower limit V
desc_inm Immediate cut-out voltage V
OUTPUT VOLTAGE
vo1_nom Output voltage (main output): Rated value V
vo1_max Output voltage (main output): Upper limit V
vo1_min Output voltage (main output): Lower limit V
Table 6.1. Charger parameters

IG-258-EN, version 02; 16/11/2018
16
Unit configuration General Instructions
ekor.bat-200
6.1.1. Communications parameters
Name Description Format
Information of the unit
Installation 20 char
Sigrid Code 20 char
Model 20 char
Type Type of equipment 20 char
Manufacturer Equipment manufacturer 20 char
Serial number Serial number 20 char
MAC 20 char
Cong version Configuration version 20 char
Cong date Configuration date 20 char
IP ADDRESSES
DHCP IP assignment in access port - YES: dynamic IP assignment by DHCP -
NO: assignment through fixed parameters in the unit 0:NO/1:YES
IP_REMOTA Remote IP address 20 char
Subnet mask Subnet mask of possible "T" values 20 char
Gateway Gateway of possible "T" values 20 char
IP_LOCAL Remote IP address 20 char
Subnet mask Subnet mask of possible "T" values 20 char
SNTP Clock addresses
IP Connexion IP for the SNTP protocol 20 char
Gateway Gateway for the SNTP protocol
SI_TFALL Time without synchronising in order to consider the internal clock out-of-sync min
T_PETSINCRO Server polling period Seg
T_ESPSINCRO Time the synchronisation server waits for a response in the event of unicast request. min
RETRY t Time between re-attempts in the servers: DHCP, LDAP, NTP, SNMP seg
RETRY n Number of attempts for each of the servers: LDAP, NTP, SNMP units
LDAP Parameters
IP_LDAP Connexion IP for the LDAP protocol 20 char
Gateway Gateway for the LDAP protocol 20 char
PORT_LDAP Gateway for the LDAP protocol
Category 1
Category 2
Category 3
Category 4
Category 5
Category 6
Category 7
Category 8
LDAP tact Session time min
SNTP Clock addresses
IP_SNMP Connexion IP for the SNMP protocol 20 char
Gateway Gateway for the SNMP protocol 20 char
Rcom Reading community 8 char
Trap_com Traps community 8 char
Trap_period Time between traps min
Wcom Writing community 8 char
Table 6.2. Communication parameters

IG-258-EN, version 02; 16/11/2018 17
General Instructions
ekor.bat-200
Equipment test
7. Equipment test
7.1. Force states
Via the web, the unit can force states, switching from one
state to another in order to check operation. The forced
options are as follows:
• Floating. Switching to floating state is forced, whenever
there are batteries connected.
• Fast charge. Switching to fast charge state is forced,
whenever there are batteries connected.
• Slow test. The start of a slow test or measurement of the
discharged capacity is forced.
• Fast test. The start of a fast test or internal impedance
measurement is forced.
• Softreset.Pressingthisbuttonresetsthestatemachineat
software level. In other words, all the alarms are removed,
and all the meters and the state machine restart, always
maintaining voltage without any interruption in supply.
7.2. Hardware test
This window can be used to force the state of the luminous
indications and the digital outputs during a specific time
interval in order to test the indication LEDs, the alarms and
the connections between digital outputs and other units.
The test configuration options are described below:
• The “Start Hardware Test” box enables the tests
process. Test time is limited.
• “Maximum duration of test”. The maximum time
forced variables lasts is configured.
• LEDs. The LED associated with the front of the unit can
be enabled or disabled by clicking the box next to each
LED indication.
• “Relay”. The charger's digital outputs can be opened
or closed by clicking the box next to each relay.
This action means the proper operation of the
charger's digital outputs can be checked remotely.

IG-258-EN, version 02; 16/11/2018
18
On-site intervention procedures General Instructions
ekor.bat-200
8. On-site intervention procedures
8.1. Battery replacement
The charger can be used to replace the batteries without
having to disconnect the unit.
The different reasons it is necessary to replace batteries are:
• Preventive maintenance or replacement campaigns.
• Battery test failure.
• Other reasons, such as deterioration, breakage, etc.
The procedure to replace the batteries is as follows:
1. Disconnect old batteries and remove them.
2. It is necessary to force a battery reconnection, for which
there are two options:
a. Press the "Battery reconnection" button for
5 seconds.
b. Access the Web and press forced battery
reconnection, which can be found in the Configure\
Control window.
3. Check that the non-connected battery alarm is enabled,
meaning the urgent failure output and the “Battery
ERROR” LED will be enabled.
4. Position new batteries and make connections between
them.
5. Check that battery voltage is between 42 V and 52 V.
Installing batteries with voltage below 40 V is not
recommended.
6. Check voltage polarity.
7. Connect batteries to the charger.
8. The charger detects the presence of the batteries.
Check on the web that battery voltage is measured.
9. It is necessary to force a battery reconnection, for which
there are two options:
a. Press the "Battery reconnection" button for
5 seconds.
b. Access the Web and press forced battery
reconnection, which is found in the Configure\
Control window.
10. The charger detects battery presence.
a. If the battery is correctly connected, it switches to
fast charge state. The alarm is reset whenever there
is a failure in the battery test.
b. Ifnobatterypresenceisdetected,thenon-connected
battery alarm is enabled, meaning the urgent failure
output and the "Battery ERROR" LED are enabled.


Subject to change
without prior notice.
For further information,
contact Ormazabal.
Ormazabal
Protection &
Automation
IGORRE
Spain
www.ormazabal.com
Table of contents