• Documentation supplied
• Installation manual & Service logbook
• Template for connecting pipeworkk
•Immersion heater(s) - (3kW).
•Thermostats / thermal cut-out.
•Drain Cock.
•Lid for cylinder.
1.2Health and safety regulations
Handling Operations Regulations 1992 defines
manual handling as: “any transporting or
supporting of a load (including the lifting,
putting down, pushing, pulling, carrying or
moving thereof by hand or bodily force” The
Regulations set no specific requirements such as
weight limits. However common sense still has
to be used based on an ergonomic approach for
each individual. The Super S should be
transported and stored in a vertical position.
1.3Siting the Super S
The cylinder should not be positioned until the
connecting pipework and cables are
fitted. There are few restrictions on the siting of
the OSO Super S, however it should not be sited
anywhere open to frost attack. The unit should
be placed on a stable flat surface capable of
withstanding the weight of the cylinder when
full (see table on page 16) and access must be
allowed for maintenance purposes. Prior to
positioning the cylinder, wind out the feet in the
base to protrude by 10mm(35mm if using
optional wall bracket). If wall mounted with an
OSO wall bracket, the wall should be capable of
withstanding the forces generated by the weight
of the full cylinder. Provision should also be
allowed for the routing of the discharge pipe
away from the cylinder to an outside point
according to building regulation G3.
1.4Component check list
Components supplied with the unit in a
separate accessory kit for site fitting
• Expansion vessel with wall bracket
(Super S 300 only).
• Tundish (including screws).
• Plastic cable clamp.
Components factory fitted
• Expansion vessels with T piece
connector.
• Flexible hose for expansion vessel.
• Combination valve, includes line
strainer, pressure reducing valve, balanced cold
water connection, (for shower or bidet only),
blanking cap for balanced cold water
connection, temperature & pressure relief valve
and hot water blending valve.
1.5 Supply requirements
An uninterrupted 22mm cold water mains
supply is recommended, however if only a
15mm supply is available, this may be used
provided there is sufficient flow rate
available A minimum standing pressure of
2.5 bar and a flow rate of 20 litres per
minute with a 1 bar dynamic pressure is
recommended. The cylinder will operate at
lower pressures and flow rates however the
performance will be compromised. The OSO
unvented unit is designed for use with
supply pressure up to 8 bar. For pressures
over 8 bar an additional pressure reducing
valve must be fitted in the supply pipe to the
unit.
1.6 Expansion vessels
Super S 120-250: Twin expansion vessels
(single on 120) are factory fitted to the
multifunction valve Part K (see fig 1, page 3)
using the supplied flexible hose.
Super S 300: An external expansion vessel is
provided to be connected to the multifunction
valve Part K (see fig. 1, page 3)
The vessel(s) accommodate expanded water
when the cylinder is heated and prevents the
cylinder reaching itsmaximum working
pressure.
1.7 Non-compatible products.
Solid fuel boilers, wood burning stoves and
other non-thermostatically controlled heat
sources must not be used with unvented
cylinders.
1.8 Wall mounting
Wall mounting brackets are available for
OSO unvented units Super S 120-180.