Record data can be confirmed.(Surge current level and its record time)
Instruction manual
【Caution】
・The lightning memory can only be installed on earth wire. Do not install it
on power line.
・Indoor use only. Do not use it outdoor.
・Do not expose the lightning memory in the environmental conditions such as
rain, direct sunshine, corrosion gas and dust.
・Remove the batteries and store the lightning memory when it is not used.
・Do not handle the lightning memory with wet hand.
・Push the button slowly and carefully. Prevent a mechanical shock or do not drop it.
・Do not dismantle or remodel it.
・Do not use different batteries except specified batteries.
・In the event of lightning surge exceeding the specification, the lightning memory
may fail.
【Warning】
・Do not install the lightning memory or replace the batteries when lightning strikes.
1 Safety instruction
6 Indication of record data
①Open the 2 lids for batteries on the bottom.
②Insert 2 pieces of LR03 (AAA) size batteries
with care of polarity.
③After inserting the batteries, LCD shows the
operation menu and then LCD turns off for
measurement mode.
④Close the lids and fix them until they click.
【Important】
It is recommended that the batteries are replaced every 2 years.
After replacing the batteries, the time returns to initial setting. (00/01/01 00:00)
Make sure to set the time correctly after replacing the batteries.
(Record data will not be lost.)
Conduct the operation test by pushing “TEST” button after replacing the batteries.
Please read the instructions before installing the product, as this
instruction manual explains how to use the lightning memory effectively
and safely.
2 Insert the batteries
【Record data indication】
【Example of record data】
Surge level
Indication Explanation
S Small Surge indication more than 100A
L Large Surge indication more than 1kA
T Test Test operation
5 Operation test
When pushing “TEST” button for more than 1 second during
LCD turns off (Measurement mode), time, “T”, and the number
of count are shown. The test operation is recorded to internal
memory. Because of this operation, this device can be confirmed
that it is normal. 【Test indication】
Year Month Day
Hour Count
Surge level
Minute
1) Installation by screws
Earth wire is passed through the
bottom dent and fix it by M5 or M6
screws. (2 parts, 1.5 to 2N・m)
It becomes measurement condition.
2) Installation by cable ties
Earth wire is passed through the
bottom dent and fix it by 2 cable ties.
It becomes measurement condition.
3 Time setting
①Push “TEST” button and “DATA” button at the
same time for more than 1 second. The LCD
changes to the time setting mode.
※If these buttons are not pushed for more than 10 second,
LCD turns off and returns to measurement mode.
②Set year, month, day, hour, minute in order by pushing
the buttons.
“TIME” button:Increase the number
“TEST” button:Decrease the number
“DATA”button:Set the number and move to next setting
③After setting the time(minute) and push “DATA”
button, LCD shows “SET” and time setting is completed.
④If “TIME” button is pushed for more than 1 second, LCD
shows the current time for 5 seconds. Check this time
that is correct.
9 Specification
Name LIGHTNING MEMORY
Type OLM-2、OLM-2S
Power source LR03 (AAA) type Alkali battery 2 pieces
(※Recommendation frequency of batteries replacement:2 years)
Applied wire 2.0~22mm2IV or KIV wire
Indication current S:100A±30% (8/20μs)
L:1kA±30% (8/20μs)
Max. current 25kA(8/20μs, 10/350μs)
Max. number of record 99(It cannot record data above 99 )
Signal contact
(OLM-2S)
Open collector output
The signal contact becomes “close”(1s) when operating
and testing.
(If the number of record is more than 99, the signal
contact output operates.)
Maximum operating voltage:DC80V
Maximum operating current:50mA
Time accuracy Monthly difference ±15 seconds
Applied use Indoor use only
Applied temperature Measurement -20℃to +50℃(No dewing)
Indication 0℃to +50℃(No dewing)
■Contact(Handling store or OTOWA)
OTOWA ELECTRIC CO., LTD.
https://www.otowadenki.com/
Head Office (Japan):TEL +81-6-6429-5951
【Time setting mode】
【Time setting completed】
4 Installation
【TIME button】
8 Delete of record data
1) Delete of record data
Push “TIME” button and “TEST” button at the same time for
more than 1second. LCD shows “00” and all record data are
deleted.
【Important】
If record data are deleted, these data cannot be restored.
2) Maximum record data
Totally maximum 99 data can be recorded. If total data
becomes 99, more data cannot be recorded. If operation test is
conducted, LCD shows “DATA FULL”.
Even when the recorded data is 99, the signal contact becomes
“close” when operating and testing.(OLM-2S)
【Delete of record data】
【Max. record data】
【Installation by screws】
【Installation by cable ties】
Screw
Cable tie
Earth wire
Earth wire
00/_ _/_ _
_ _:_ _
18/12/23
13:46SET
18/12/23
13:47:36
【Important】
Detection current might be worse when
this product is installed in a metal box.
LIGHTNING MEMORY OLM-2S(With signal contact output)
△
!
△
!
18/12/23
13:48T01
①When pushing “DATA”
button for more than 1 second,
the number of record data is sho
operation)
②When pushing “TIME” button or “TEST” button
the number of record is shown, the newest
shown.
③If pushing “TIME” button or “TEST”
the record data on LCD scrolls in order.
④If these buttons are
not pushed for more than 10 second,
LCD turns off and returns to measurement mode.
【Indication meaning】
03
19/01/13
05:43S03
18/12/28
12:34L02
7 Signal contact output (OLM-2S)
00
- - DATA - -
- - FULL - -
The signal contact becomes “close”(1sec) when operating and testing.
When using the signal contact output, please connect to the monitoring device using
the harness of signal contact output. (cable length: 300mm,wire diameter: 0.36mm)
DC voltage Recommended SPD
DC12V SL-GV12J
DC24V SL-GV24J
DC48V SL-GV48J
DC80V LS-T1FS
【Important】
・The signal contact output should be used less than
maximum operating voltage and m
current.
・
Take care of the voltage drop when extending the wires
from the harness of signal contact output.
・Connect the red wire of harness to + side of
and the white wire of harness to —side.
・Please install the SPD for protecting
the monitoring device from induced
lightning on the signal line.
【Signal contact terminal】
No.G1-325-18-027c