
INSTALL THE DETECTOR BASE
1. Open area smoke or heat detectors are
Intended for mounting on a ceiling or a
Wall in accordance with the fire standard
In your country.
2. Attach mounting base to ceiling or wall. The
base of the detector can be mounted
directly onto an electrical junction box such
a an octagonal (75mm, 90mm or 100mm) a
round (75mm), or a square (100mm) box
without using any type of mechanical
adapter.
3. Position all wires flat against terminals, and
fasten the wires on the terminals, See
Figure a.
4. Terminals functions description :
Terminal 2: IN+(Zone Input+) Terminal 6: IN+(Zone Output+) Terminal 6: Remote Indicator+
Terminal 5: IN- (Zone Input-) Terminal 5: IN-(Zone Output-) Terminal 3: Remote Indicator-
INSTALL THE DETECTOR HEAD
1. Align detector head alignment mark line
with the base’s start alignment mark line as
shown in Figure 2
2. Push the detector head into the base while
turning it clockwise to secure it in place.
3. Do not install the detector head until the
area is thoroughly cleaned of construction
debris, dusts, etc.
4. After all detectors have been installed,
apply power to the control panel.
5. Test the detector(s) as described in the
TESTING section of this manual.
6. Notify the proper authorities that the system
is in operation.