CW-C241SE
–7 –
TROUBLESHOOTING GUIDE
WARNING: DISCONNECT UNIT FROM ELECTRICAL POWER SUPPLY BEFORE MAKING ANY ELECTRICAL
CHECKS.
DISCHARGE THE CAPACITOR BEFORE CHECKING IT.
TROUBLE CHECK RESULT CAUSE REMEDY
Fan Motor and 1. Supply Voltage. Less than - 10% by Rated. Customer Restarted unit Consult ELECTRICIAN.
Compressor 2. Fuse Box or Circuit Open Contacts. immediately without Repair Open Circuit.
won’t run. Breaker. waiting 3 minutes WAIT FOR 3 MINUTES.
3. Power cord or Wiring Pulled loose or Shorted. Repair or Replace it.
Harness.
4. Thermostat Setting. Higher thanROOM TEMP. Set it LOWER.
Fan Motor 1. Objects around Fan. Locked Fan. Fan Hitting Cowling or AdjustFan Positionset screw.
won’t run Foreign Materials. Remove Foreign Materials.
Frozen Bearings. Replace Fan Motor.
2. RESISTANCE between Shorted/Open circuit. Shorted or Burned out. Replace Fan Motor.
Wires.
3. Capacitor Fan Motor. OHM Meter doesn’t Deflect. Capacitor Defect. Replace Capacitor Fan.
4. Main Control Knob. No contacts at Position Main Control Knob defect. Replace Main Control Knob.
Shown.
Compressor 1. Thermostat Setting. Higher than ROOM TEMP. Set it lower.
won’t run 2. RESISTANCE between Shorted. Winding Coil touched to the Replace Compressor.
(Fan runs) Terminal and the Body.
Compressor Body.
3. RESISTANCE between Shorted. Rear Shorted or Burnt out. Replace Compressor.
Terminals.
4. Overload Protector. Infinity between Terminals. O.L. protector defect. Replace Overload Protector.
5. Capacitor Compressor. OHM Meter doesn’t deflect. Capacitor defect. Replace Capacitor Comp.
6. Thermostat. No CLICK around position. Thermostat defect. Replace Thermostat.
7. Main Control Knob. No contacts at Position Shown. Main Control Knob defect. Replace Main Control Knob.
Insufficient 1. Thermostat setting. Higher than ROOM TEMP. Set it lower.
cooling 2. Ventilation Door open. Open. Reduces capacity. Close Vent door.
3. Air Filter dirty. Clogged or Dirty. Restricted air circulation. Clean or Replace Air Filter.
4. Location of installation. Sunlight hitting outdoor side. Restricted Heat Exchanger. ConsiderbuildinganAWNING.
Obstacles. Restricted Heat Exchanger. Remove obstacles or
reinstall unit.
5. Evaporator/Condenser Clogged or Dirty. Restricted air circulation. Clean by steam cleaner.
Coil obstructed.
6. Unit capacity for the Not Satisfied. Replace the Unit with
room too small. Bigger one.
7. Temp difference and REFER PERFORMANCE Leakage of refrigerant or Locate repair leak.
Running Current. EVALUATION. refrigeration system is Flush refrigeration cycle.
blocked.
Noise 1. Source of Noise. Vibration. Faulty installation. Reinstall unit or Reinforce
the installation.
Intermittent Noise. Fan hitting objects. Adjust Fan position or
remove Foreign Materials.
Refrigerant tubing touching About 1/2" Clearance.
each other.
Fan splashing Drain Water. Consider Attaching the
Drain Pan and pull plug
in bottom pan.
(REFER INSTALLATION
INSTRUCTIONS)
Water dripping 1. Unit Installation. Tilted to inside room. Restricted run off. Tilt unit to outside slightly.
inside room 2. Drain Tray-STYROFOAM Clogged. Clogged or blocked. Removetheforeignmaterials.
Pieces blocking Drain (REFER OPERATING
Channel. INSTRUCTIONS)
Frozen 1. Thermostat Setting Set too low for ambient Outdoor TEMP. Low Set Main Control Knob to
Evaporator conditions. (Night time) Fan to melt ICE and Set
the Temp. Control to higher
temperature.
2. Air Filter/Evaporator. Clogged or Dirty. Restricted air circulation Clean Air Filter/Evaporator.
3. Temp. difference and REFER PERFORMANCE Leakage of refrigerant or Locate repair leak.
Running Current. EVALUATION. refrigeration system is Flush refrigeration cycle.
blocked.