
19
Refrigerant Charging
(1) Execute refrigerant charging immediately after evacuation. (2) Charge refrigerant R744 (CO2refrigerant).
(3) Do not mix with other refrigerant.
Refrigerant Charging
Method of Charging
(1) Close the vacuum valve of the manifold gauge set exclusively for CO2refrigerant, and separate the vacuum pump.
(2) Place the refrigerant cylinder on the platform scale, and open the refrigerant cylinder valve and manifold gauge set
charging valve.
Notes: 1. Close the access ports of the low pressure and high pressure service valve.
2. Place the platform scale on a flat surface and perform zero-point adjustment.
(3) With the refrigeration unit being stopped, open the joint valve attached to the service piping and the access port of the
high pressure service valve, and charge liquid state refrigerant via the access port of the high pressure service valve.
Calculate the initial refrigerant charging quantity by using the formula below.
Initial refrigerant charging quantity = 0.25 (kg / ft) x Display case footage + 0.09 (kg / m) x Piping length (one-way: m)
Notes: 1. Do not absolutely charge liquid refrigerant from the low pressure side (low pressure access port).
2. If it is difficult to adjust refrigerant charging rate by operating the joint valve and manifold gauge set
charging valve, attach a capillary tube between the refrigerant cylinder and manifold gauge set.
3. Do not attach a capillary tube between the manifold gauge set and service piping.
4. For the method of charging refrigerant, refer to the Engineering Service Manual “Refrigerant Charging
Procedure."
(4) When the liquid refrigerant no longer goes into the refrigeration unit, close the access port of the high pressure service
valve and make the refrigeration unit in cooling operation condition to adjust refrigerant quantity.
Note: Refrigerant quantity adjustment should conform to the “Adjusting Refrigerant Quantity of the Refrigeration Unit"
in the section "Adjustment during Operation."
(5) After completing refrigerant quantity adjustment, close the refrigerant cylinder valve and check that the access ports of
the low pressure and high pressure service valve have been closed.
(6) Slowly open the purge valve of the manifold gauge set to emit the remaining refrigerant in the service piping and
manifold gauge set.
Note: Since refrigerant becomes cold when released, use caution when opening the valve for frost bite.
(7) After completing the operation, check gland nut loosening of the low pressure and high pressure service valves and
fasten them if any looseness exists. Fastening torque is 10 ±2 N・m.
Evacuation [Perform after completing electrical wiring.]
To avoid inclusion of air or moisture in the refrigerant circuit, be sure to execute vacuum drying of the entire circuit before
charging refrigerant by using a vacuum pump. Execute evacuation after securely carrying out airtight test by using the
following sequence.
Before starting evacuation, refer to the Engineering Service Manual “Vacuum Pump
Attachment and Evacuation Procedure.”
(1) Connect electrical wiring
Before starting evacuation, electronic expansion valve and solenoid valve
need to be opened.
(2) Before supplying power
• Turn ON the operation switch S1.
• Turn ON the DIP switch SW13-1 on the control PCB.
• Set the Slide switch SW15 (“Control/Check”) on the control PCB to “Check.”
(3) Supply power
Confirm that the digital display repeatedly alternates between “Low pressure Æ
High pressure ÆUnit outlet pressureÆuAcU.“
Electronic expansion valve and solenoid valve will open.
(4) Evacuation
• Connect a pressure gauge (vacuum pressure gauge) and vacuum pump to
the access ports of the low pressure and high pressure service valve, and
apply evacuation from the two ports.
• Evacuate down to 133 Pa (1 Torr), the target level for evacuation, and continue
for 1 to 3 hours.
(5) After evacuation
• Charge the refrigerant up to approximately 0.5MPa.
• Set the Slide switch SW15 (“Control/Check”) on the control PCB to “Control”.
• Turn OFF the DIP switch SW13-1 on the control PCB.
• Turn OFF the operation switch S1.
Front of refrigeration unit
Access port of low pressure
service valve
Access port of high pressure
service valve
Compressor
Electrical box