Installation Manual
AIR-TO-WATER HEATPUMP MONO BLOC
WH-MDC05H3E5, WH-MDC07H3E5, WH-MDC09H3E5, WH-MDC12H6E5,
WH-MDC16H6E5, WH-MXC09H3E5, WH-MXC12H6E5, WH-MXC09H3E8,
WH-MXC12H9E8, WH-MXC16H9E8
ACXF60-17020-AA
APPENDIX
This section introduces variation of various systems using Air-To-Water Heatpump and actual setting method.
1-1 Introduce application related to temperature setting.
Temperature setting variation for heating
1. Remote Controller
Mono bloc
Floor heating
Mono bloc
or
Connect floor heating or radiator directly to the Mono bloc.
This is the basic form of the most simple system.
2. Room Thermostat
Mono bloc Mono bloc receive Room Thermo signal
(ON/OFF) from Remote controller to
control HP and circulation pump.
There is a build-in thermistor in the
remote controller.
Floor heating
Mono bloc
or
Connect floor heating or radiator directly to the Mono bloc.
Install the remote controller in the room where floor heating is installed.
This is an application that uses remote controller as Room Thermostat.
3. External Room Thermostat
Mono bloc
Room
thermostat
(Field supply)
Floor heating
Mono bloc
or
Connect floor heating or radiator directly to Mono bloc.
Install separate external Room Thermostat (field supply) in the room where floor heating is installed.
This is an application that uses external Room Thermostat.
1
Variation of system
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - No
Zone & Sensor:
Water temperature
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - No
Zone & Sensor:
Room thermostat
Internal
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - No
Zone & Sensor:
Room thermostat
(External)
1
4. Room Thermistor
or
Mono bloc
Max: 30m
Thermistor
Mono bloc compare between
room temperature and setting
temperature on the Remote
controller to control HP and
circulation pump.
Floor heating
Mono bloc
Connect floor heating or radiator directly to Mono bloc.
Install separate external room thermistor (specified by Panasonic) in the room where floor heating is installed.
This is an application that uses external room thermistor.
There are 2 kinds of circulation water temperature setting method.
Direct: set direct circulation water temperature (fixed value)
Compensation curve: set circulation water temperature depends on outdoor ambient temperature
In case of Room thermo or Room thermistor, compensation curve can be set.
In this case, compensation curve is shifted according to the thermo ON/OFF situation.
• (Example) If room temperature increasing speed is;
very slow oshift up the compensation curve
very fast oshift down the compensation curve
Examples of installations
Floor heating 1 + Floor heating 2
or
Mono bloc
Room
thermostat
(field supply)
Thermistor 2
Thermistor 1
Buffer tank
Pump 2
Pump 1
Mixing valve 2
Mixing valve 1
Mono bloc
Floor heating 2
Floor heating 1
Connect floor heating to 2 circuits through buffer tank as shown in the figure.
Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits.
Install the remote controller in one of the circuit and use it as Room Thermostat.
Install external Room Thermostat (field supply) in another circuit.
Both circuits can set circulation water temperature independently.
Install buffer tank thermistor on buffer tank.
It requires connection setting of buffer tank and T temperature setting at heating operation separately.
This system requires optional PCB (CZ-NS4P).
Floor heating + Radiator
Mono bloc
Radiator
Thermistor 1
Thermistor 2
Buffer tank
Pump 2
Pump 1
Mixing valve 1
Mono bloc
Floor heating
or
Connect floor heating or radiator to 2 circuits through buffer tank as shown in figure.
Install pumps and thermistors (specified by Panasonic) on both circuits.
Install mixing valve in the circuit with lower temperature among the 2 circuits.
(Generally, if install floor heating and radiator circuit at 2 zones, install mixing valve in floor heating circuit.)
For temperature setting, select circulation water temperature for both circuits.
Both circuits can set circulation water temperature independently.
Install buffer tank thermistor on buffer tank.
It requires connection setting of buffer tank and T temperature setting at heating operation separately.
This system requires the optional PCB (CZ-NS4P).
Mind that if there is no mixing valve at the secondary side, the circulation water temperature may get higher than setting temperature.
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - No
Zone & Sensor:
Room thermistor
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Room thermostat
Internal
Zone 2:Sensor
Room
Room thermostat
(External)
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Water temperature
Zone 2:Sensor
Room
Water temperature
2
Floor heating + Swimming pool
Mono bloc
Thermistor 1 Heat EXT
Thermistor 3
Thermistor 2
Buffer tank
Pump 2
Pump 3
Pump 1
Mixing
valve 1
Mixing
valve 2
Mono bloc
Floor heating 1 Swimming pool
or
Connect floor heating and swimming pool to 2 circuits through buffer tank as shown in figure.
Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits.
Then, install additional pool heat exchanger, pool pump and pool sensor on pool circuit.
Install the remote controller in room where floor heating is installed. Circulation water temperature of floor heating and swimming pool can be
set independently.
Install buffer tank sensor on buffer tank.
It requires connection setting of buffer tank and T temperature setting at heating operation separately. This system requires the optional
PCB (CZ-NS4P).
KMust connect swimming pool to “Zone 2”.
If it is connected to swimming pool, operation of pool will stop when “Cooling” is operated.
Swimming pool only
Thermistor
Pump
Swimming pool
Heat EXT
This is an application that connects to the swimming pool only.
Connects pool heat exchanger directly to Mono bloc without
using buffer tank.
Install pool pump and pool sensor (specified by Panasonic) at
secondary side of the pool heat exchanger.
Install the remote controller in room where floor heating is installed.
Temperature of swimming pool can be set independently.
This system requires the optional PCB (CZ-NS4P).
In this application, cooling mode cannot be selected. (not display on remote controller)
Mono bloc
Mono bloc
or
Simple 2 zone (Floor heating + Radiator)
This is an example of simple 2 zone control without using buffer tank.
Built-in pump from Mono bloc served as a pump in zone 1.
Install mixing valve, pump and thermistor (specified by Panasonic) on zone 2 circuit.
Please be sure to assign high temperature side to zone 1 as temperature of zone 1 cannot be adjusted.
Zone 1 thermistor is required to display temperature of zone 1 on remote controller.
Circulation water temperature of both circuits can be set independently.
(However, temperature of high temperature side and low temperature side cannot be reversed)
This system requires the optional PCB (CZ-NS4P).
(CAUTION)
• Thermistor 1 does not affect operation directly. But error happens if it is not installed.
• Please adjust flow rate of zone 1 and zone 2 to be in balance. If it is not adjusted correctly, it may affects
the performance.
(If zone 2 pump flow rate is too high, there is possibility that no hot water flowing to zone 1.)
Flow rate can be confirmed by “Actuator Check” from maintenance menu.
Floor heating
Thermistor 2
Thermistor 1
Pump 2
Mixing valve
Mono bloc
Mono bloc
Radiator
or
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Room thermostat
Internal
Zone 2
Swimming pool
T
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 1 Zone system
Zone :Swimming pool
T
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Water temperature
Zone 2:Sensor
Room
Water temperature
Operation setup
Heat
T for heating ON – 1°C
Cool
T for cooling ON – 1°C
3
1-2. Introduce applications of system that uses optional equipment.
DHW (Domestic Hot Water) Tank connection
Mono bloc
Tank
Tank thermistor
3-way valve for tank
Booster heater
Mono bloc
Floor heating
or
This is an application that connects the DHW tank to the Mono bloc through 3-way valve.
DHW tank’s temperature is detected by tank thermistor (specified by Panasonic).
Tank + Solar connection
Mono bloc
Tank
Tank thermistor
3-way valve for tank
Solar pump
Floor heating
Solar thermistor
or
Mono bloc
This is an application that connects the DHW tank to the Mono bloc through 3-way valve before connect the solar water heater to heat up the
tank. DHW tank’s temperature is detected by tank thermistor (specified by Panasonic). Solar panel’s temperature is detected by solar thermistor
(specified by Panasonic).
DHW tank shall use tank with built-in solar heat exchange coil independently.
Heat accumulation operates automatically by comparing the temperature of tank thermistor and solar thermistor.
During winter season, solar pump for circuit protection will be activated continuously. If does not want to activate the solar pump operation, please
use glycol and set the anti-freezing operation start temperature to -20°C.
This system requires optional PCB (CZ-NS4P).
Buffer tank connection
or
Mono bloc
Thermistor
Buffer tank
Pump
Mono bloc
Floor heating
This is an application that connects the buffer tank to the Mono bloc.
Buffer tank’s temperature is detected by buffer tank thermistor (specified by Panasonic).
This system requires optional PCB (CZ-NS4P).
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Tank connection - Yes
Solar connection - Yes
DHW tank
T turn ON
T turn OFF
Antifreeze
Hi limit
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Buffer Tank connection - Yes
T for buffer tank
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - No
Tank connection - Yes
4
Buffer tank + Solar
This is an application that connects the buffer tank to the Mono bloc before connecting to the solar water heater to heat up the tank.
Buffer tank’s temperature is detected by buffer tank thermistor (specified by Panasonic).
Solar panel’s temperature is detected by solar thermistor (specified by Panasonic).
Buffer tank shall use tank with built-in solar heat exchange coil independently.
During winter season, solar pump for circuit protection will be activated continuously. If does not want to activate the solar pump operation, please
use glycol and set the anti-freezing operation start temperature to -20°C.
Heat accumulation operates automatically by comparing the temperature of tank thermistor and solar thermistor.
This system requires optional PCB (CZ-NS4P).
Boiler connection
or
Thermistor
Boiler
Mixing
valve
Floor heating
Pump
Buffer tank
Mono bloc
Mono bloc
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Buffer Tank connection - Yes
T for buffer tank
Solar connection - Yes
Buffer tank
T turn ON
T turn OFF
Antifreeze
Hi limit
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Bivalent - Yes
Turn ON: outdoor temp
Control pattern
2
How to ſx external device
Connecting Cables Length
When connecting cables between Mono bloc and external devices, the length of the said cables must not exceed the maximum length as shown in the table.
External device Maximum cables length (m) External device Maximum cables length (m)
Two-way valve 50 Outdoor air sensor 30
Three-way valve 50 Tank OLP 30
Mixing valve 50 Buffer tank sensor 30
Room thermostat 50 Pool water sensor 30
Booster heater 50 Solar sensor 30
Extra pump 50 Water sensor 30
Solar pump 50 Demand signal 50
Pool pump 50 SG signal 50
Pump 50 Heat/Cool switch 50
Boiler contact 50 External compressor switch 50
External control 50
Tank sensor 30
Room sensor 30
This is an application that connects the boiler to the Mono bloc,
to compensate for insufficient capacity by operate boiler when
outdoor temperature drops & heat pump capacity is insufficient.
Boiler is connected parallel with heat pump against heating circuit.
There are 3 modes selectable by remote controller for boiler connection.
Besides that, an application that connects to the DHW tank’s circuit to heat up tank’s hot water is also possible.
(Operation setting of boiler shall be responsible by installer.)
This system requires optional PCB (CZ-NS4P).
Depending on the settings of the boiler, it is recommended to install buffer tank as temperature of circulating water may get higher. (It must connect
to buffer tank especially when selecting Advanced Parallel setting.)
WARNING
Panasonic is NOT responsible for incorrect or unsafe situation of the boiler system.
CAUTION
Make sure the boiler and its integration in the system complies with applicable legislation.
Make sure the return water temperature from the heating circuit to the Mono bloc does NOT exceed 55°C.
Boiler is turned off by safety control when the water temperature of the heating circuit exceed 85°C.
Solar thermistor
Thermistor
Solar pump
Mixing valve
Floor heating
Pump
Buffer tank
Mono bloc
Mono bloc
or
5
Connection of the main PCB
OLP for booster
heater
Zone 1 room sensor
Outdoor air sensor
Tank sensor
External control
Remote controller
Boiler contact
Extra pump
Booster heater
H C N LC O N C O N
Optional
Thermostat 1
3-way
valve
2-way
valve
QSignal inputs
Optional Thermostat
L N =AC230V, Heat, Cool=Thermostat heat, Cool
terminal
KIt does not function when using the optional PCB
OLP for booster
heater
Dry contact Vcc-Bit1, Vcc-Bit2 open/short
(System setup necessary)
It is connected to the safety device (OLP) of DHW
tank.
External control
Dry contact Open=not operate, Short=operate
(System setup necessary)
Able to turn ON/OFF the operation by external switch
Remote controller
Connected (Please use 2 cores wire for relocation
and extension. Total cable length shall be 50m or
less.)
QOutputs
3-way valve AC230V N=Neutral Open, Close=direction (For circuit
switching when connected to DHW tank)
2-way valve AC230V N=Neutral Open, Close (Prevent water circuit
pass through during cooling mode)
Extra pump AC230V (Used when Mono bloc pump capacity is
insufficient)
Booster heater AC230V (Used when using booster heater in DHW tank)
Boiler contact Dry contact (System setup necessary)
QThermistor inputs
Zone 1 room
sensor
PAW-A2W-TSRT KIt does not work when using
the optional PCB
Outdoor air
sensor
AW-A2W-TSOD (Total cable length shall be 30m
or less)
Tank sensor Please use Panasonic specified part
Connection of Optional PCB (CZ-NS4P)
Ext.
comp.
SW
Heat/
Cool
SW
SG
signal
Vcc
Bit1
Bit2
Solar
sensor
Mixing
valve 2
Mixing
valve 1
Optional
Thermostat 2
Optional
Thermostat 1
Demand
signal
Zone 1
water
sensor
Zone 2
water
sensor
Pool
water
sensor
Buffer
Tank
sensor
Zone 1
room
sensor
Zone 2
room
sensor
Zone 1
Pump
Error
signal
Pool
Pump
Solar
Pump
Zone 2
Pump
N O CN O CL N Cool Heat L N Cool Heat
Signal inputs
Optional Thermostat L N =AC230V, Heat, Cool=Thermostat heat, Cool
terminal
SG signal
Dry contact Vcc-Bit1, Vcc-Bit2 open/short (System
setup necessary)
Switching SW (Please connect to the 2 contacts
controller)
Heat/Cool SW Dry contact Open=Heat, Short=Cool (System setup
necessary)
External comp.SW Dry contact Open=Comp.ON, Short=Comp.OFF
(System setup necessary)
Demand signal DC 0~10V (System setup necessary)
Please connect to the DC 0~10V controller.
QOutputs
Mixing valve AC230V N=Neutral Open, Close=mixture direction
Operating time: 30s~120s
Pool pump AC230V
Solar pump AC230V
Zone pump AC230V
QThermistor inputs
Zone room sensor PAW-A2W-TSRT
Buffer tank sensor PAW-A2W-TSBU
Pool water sensor PAW-A2W-TSHC
Zone water sensor PAW-A2W-TSHC
Solar sensor PAW-A2W-TSSO
Recommended External Device Specification
• Th is s ec ti on e xp la in s ab ou t th e ex te rn al d ev ic es ( op ti on al )
recommended by Panasonic. Please always ensure to use the correct
external device during system installation.
• For optional sensor.
1. Buffer tank sensor: PAW-A2W-TSBU
Use for measurement of the buffer tank temperature.
Insert the sensor into the sensor pocket and paste it on the buffer
tank surface.
40
black
brown
blue
Dimensions (mm)
Ø6
2. Zone water sensor: PAW-A2W-TSHC
Use to detect the water temperature of the control zone.
Mount it on the water piping by using the stainless steel metal strap
and contact paste (both are included).
93
70
35
Dimensions (mm)
3. Outdoor sensor: PAW-A2W-TSOD
If the installation location of the outdoor unit is exposed to direct
sunlight, the outdoor air temperature sensor will be unable to
measure the actual outdoor ambient temperature correctly.
In this case, optional outdoor temperature sensor can be fixed at a
suitable location to more accurately measure ambient temperature.
70
93
46
Dimensions (mm)
6
4. Room sensor: PAW-A2W-TSRT
Install the room temperature sensor to the room which requires
room temperature control.
Dimensions (mm)
86
86
6030
5. Solar sensor: PAW-A2W-TSSO
Use for measurement of the solar panel temperature.
Insert the sensor into the sensor pocket and paste it on the solar
panel surface.
40
black
brown
blue
Dimensions (mm)
Ø6
6. Please refer to the table below for sensor characteristic of the
sensors mentioned above.
Temperature
(°C)
Resistance
(k
Ω
)
Temperature
(°C)
Resistance
(k
Ω
)
30 5.326 150 0.147
25 6.523 140 0.186
20 8.044 130 0.236
15 9.980 120 0.302
10 12.443 110 0.390
5 15.604 100 0.511
0 19.70 90 0.686
-5 25.05 80 0.932
-10 32.10 70 1.279
-15 41.45 65 1.504
-20 53.92 60 1.777
-25 70.53 55 2.106
-30 93.05 50 2.508
-35 124.24 45 3.003
-40 167.82 40 3.615
35 4.375
• For optional pump.
Power supply: AC230V/50Hz, <500W
Recommended part: Yonos 25/6: made by Wilo
• For optional mixing valve.
Power supply: AC230V/50Hz (input open/output close)
Operating time: 30s~120s
Recommended part: 167032: made by Caleffi
3-1. Remote Controller Outline
A
B
C
D
GFE
Name Function
A: Main screen Display information
B: Menu Open/Close main menu
C: Triangle (Move) Select or change item
D: Operate Start/Stop operation
E: Back Back to previous item
F: Quick Menu Open/Close Quick menu
G: OK Confirm
3
System installation
Name Function
1: Function icon Display set function/status
Holiday mode Demand
control
Weekly timer Room
heater
Quiet mode Tank heater
Remote controller
room thermostat Solar
Powerful mode Boiler
24
40˚c
10:34am, Mon
18˚c
5
6
4
3
2
1
˚
c
12:00am,Mon
7
2: Mode Display set mode/current status of mode
Heating Cooling
Auto Hot water supply Auto heating Auto cooling
Heat pump operating
3: Temp setting Set room temp Compensation
curve
Set direct water
temp Set pool temp
4: Display Heat temp Display current heating temperature (it is set temperature when enclosed by line)
5: Display tank temp Display current tank temperature (it is set temperature when enclosed by line)
6: Outdoor temp Display outdoor temp
First time of power ON (Start of installation)
Initialization 12:00am,Mon
Initializing.
When power
is ON, firstly
initialization
screen appears
(10 sec)
«
12:00am,Mon
Start
When
initialization
screen ends, it
turns to normal
screen.
«
Language 12:00am,Mon
ENGLISH
FRANÇAIS
DEUTSCH
ITALIANO
Select Confirm
When any button
is pressed,
language setting
screen appears.
(CAUTION) If
initial setting is
not performed, it
does not go into
menu.
« Set language & confirm
Clock format 12:00am,Mon
24h
am/pm
Select Confirm
When language
is set, setting
screen of time
display appears
(24h/am/pm)
« Set time display & confirm
Date & time 12:00am,Mon
Year/Month/Day Hour : Min
2015 / 01 / 01 12 : 00
Select Confirm
YY/MM/DD/Time
setup screen
appears
« Set YY/MM/DD/Time & confirm
12:00am,Mon
Start
Back to initial
screen
« Press menu, select Installer setup
Main Menu 12:00am,Mon
System check
Personal setup
Service contact
Installer setup
Select Confirm
« Confirm to go into Installer setup
8
3-2. Installer Setup
1
System setup Optional PCB connectivity Yes/No
2KOnly when the selection for optional PCB is Yes
Zone & Sensor 1 Zone system/2 Zone system Zone settings
3
Heater capacity Capacity select
4
Anti freezing Yes/No
5
Tank connection Yes/No
6KOnly when the selection for optional PCB is Yes
Buffer Tank connection Yes/No 'T setup
7KOnly when the selection for Tank connection is Yes
Tank heater External/Internal Heater ON time setup
8
Base pan heater Yes/No A / B
9
Alternative outdoor sensor Yes/No
10
Bivalent connection Yes/No Bivalent setup
11
External SW Yes/No
12 KOnly when the selection for optional PCB is Yes
Solar connection Yes/No Tank setup Solar setup
13 KOnly when the selection for optional PCB is Yes
External Error signal Yes/No
14 KOnly when the selection for optional PCB is Yes
Demand control Yes/No
15 KOnly when the selection for optional PCB is Yes
SG ready Yes/No Capacity setup
16 KOnly when the selection for optional PCB is Yes
External Compressor SW Yes/No
17
Circulation liquid Water/glycol
18 KOnly when the selection for optional PCB is Yes
Heat-Cool SW Yes/No
19
Force Heater Auto/Manual
9
20
Operation setup Heat Water temp. for heating ON Compensation curve Compensation curve setup
KCooling model only
21 Direct Direct temp. setup
Outdoor temp. for heating OFF
Heating OFF Temp. setup
22 'T for heating ON 'T for heating setup
23
Outdoor temp. for heater ON
O/D temp for heater ON setup
24 (Display only if Cool exist, or else skip)
Cool Water temp. for cooling ON Compensation curve Compensation curve setup
KCooling model only
25 Direct Direct temp. setup
'T for Cooling ON 'T for cooling setup
26
Auto Outdoor temp. for
(Heat to Cool) Heat Cool change temp. setup
27
Outdoor temp. for
(Cool to Heat) Cool Heat change temp. setup
28
Tank Floor operation time (max.) Max. operation time for Heat & Cool mode setup
29
Tank heat up time (max.) Max. operation time for Tank mode setup
30
Tank re-heat temp. Tank re-heat temp. setup
31
Sterilization Sterilization day and temp. and time setup
32
Service setup Pump maximum speed Pump maximum speed setup Air purge
33
Pump down Pump down ON/OFF
34
Dry concrete ON (Dry concrete)
35 Edit (Dry concrete schedule) Day and temp. setup
Service contact Contact 1 Name and Tel No. setup
Contact 2 Name and Tel No. setup
KOnly when the
selection for Tank
is Yes
3-3. System Setup
1. Optional PCB connectivity Initial setting: No System setup 12:00am,Mon
Optional PCB connectivity
Zone & Sensor
Heater capacity
Anti freezing
Select Confirm
If function below is necessary, please purchase and install optional PCB.
Please select Yes after installing optional PCB.
• 2-zone control
• Pool
• Buffer tank
• Solar
• External error signal output
• Demand control
• SG ready
• Stop heat source unit by external SW
2. Zone & Sensor Initial setting: Room and Water temp. System setup 12:00am,Mon
Optional PCB connectivity
Zone & Sensor
Heater capacity
Anti freezing
Select Confirm
If no Optional PCB connectivity
Select sensor of room temperature control from the following 3 items
1Water temperature (Circulation water temperature)
2Room thermostat (Internal or External)
3Room thermistor
When there is Optional PCB connectivity
1Select either 1 zone control or 2 zone control.
If it is 1 zone, select either room or pool, select sensor
If it is 2 zone, after select sensor of zone 1, select either room or pool for zone 2, select sensor
(CAUTION) In 2 zone system, pool function can be set at zone 2 only.
10
3. Heater capacity Initial setting: Depend on model System setup 12:00am,Mon
Optional PCB connectivity
Zone & Sensor
Heater capacity
Anti freezing
Select Confirm
If there is built-in Heater, set the selectable heater capacity.
(CAUTION) There are models which cannot select heater.
4. Anti freezing Initial setting: Yes System setup 12:00am,Mon
Optional PCB connectivity
Zone & Sensor
Heater capacity
Anti freezing
Select Confirm
Operate anti-freezing of water circulation circuit.
If select Yes, when the water temperature is reaching its freezing temperature, the circulation
pump will start up. If the water temperature does not reach the pump stop temperature, back-
up heater will be activated.
(CAUTION) If set No, when the water temperature is reaching its freezing temperature or
below 0°C, the water circulation circuit may freeze and cause malfunction.
5. Tank connection Initial setting: No System setup 12:00am,Mon
Zone & Sensor
Heater capacity
Anti freezing
Tank connection
Select Confirm
Select whether it is connected to hot water tank or not.
If set Yes, it becomes setting that uses hot water function.
Hot water temperature of tank can be set from main screen.
6. Buffer Tank connection Initial setting: No System setup 12:00am,Mon
Heater capacity
Anti freezing
Tank connection
Buffer tank connection
Select Confirm
Select whether it is connected to buffer tank for heating or not.
If buffer tank is used, please set Yes.
Connect buffer tank thermistor and set, 'T ('T use to increase primary side temp against
secondary side target temp).
(CAUTION) Does not display if there is no Optional PCB.
If the buffer tank capacity is not so large, please set larger value for 'T.
7. Tank heater Initial setting: Internal System setup 12:00am,Mon
Anti freezing
Tank connection
Buffer tank connection
Tank heater
Select Confirm
Select to use either built-in heater or external heater as heater for hot water tank.
If heater is installed on tank, please select External.
(CAUTION) Does not display if there is no tank for hot water supply.
Please set “Tank heater” to “ON” in the “Function setup” from remote controller when using
heater to boil the tank.
External A setting which is using booster heater installed on DHW
tank to boil the tank.
The permissible heater capacity is 3kW and below.
The operation to boil the tank with heater is as below.
In addition, be sure to set suitable “Tank heater: ON time”
Internal A setting which is using backup heater of Mono bloc to boil
the tank.
The operation to boil the tank with heater is as below.
5
53
HP thermo OFF
HP
Booster heater
Tank temp.
ON time
Pump
For 65°C setting
65
53
HP thermo OFF
HP
Backup heater
Tank temp.
A
Pump
For 65°C setting
11
8. Base pan heater Initial setting: No System setup 12:00am,Mon
Tank connection
Buffer tank connection
Tank heater
Base pan heater
Select Confirm
Select whether Base pan heater is installed or not.
If set Yes, select to use either heater A or B.
A: Turn on Heater when heating with defrost operation only
B: Turn on Heater at heating
9. Alternative outdoor sensor Initial setting: No System setup 12:00am,Mon
Buffer tank connection
Tank heater
Base pan heater
Alternative outdoor sensor
Select Confirm
Set Yes if outdoor sensor is installed.
Controlled by optional outdoor sensor without reading the outdoor sensor of heat pump unit.
10. Bivalent connection Initial setting: No System setup 12:00am,Mon
Tank heater
Base pan heater
Alternative outdoor sensor
Bivalent connection
Select Confirm
Set if heat pump linked with boiler operation.
Connect the start signal of the boiler in boiler contact terminal (main PCB).
Set Bivalent connection to YES.
After that, please begin setting according to remote controller instruction.
Boiler icon will be displayed on remote controller top screen.
There are 3 different modes in the boiler operation. Movement of each modes are shown below.
1Alternative (switch to boiler operation when drops below setting temperature)
2Parallel (allow boiler operation when drops below setting temperature)
3Advanced Parallel (able to slightly delay boiler operation time of parallel operation)
When the boiler operation is “ON”, “boiler contact” is “ON”, “_”(underscore) will be displayed below the boiler icon.
Please set target temperature of boiler to be the same as heat pump temperature.
When boiler temperature is higher than heat pump temperature, zone temperature cannot be achieved if mixing valve is not installed.
This product only allows one signal to control the boiler operation. Operation setting of boiler shall be responsible by installer.
operate heat pump only
-10°C (setting from remote controller)
operate boiler only
Alternative mode
Outdoor temp.
operate heat pump only
-10°C (setting from remote controller)
operate boiler and heat
pump simultaneously
Parallel mode
Outdoor temp.
operate heat pump only
-10°C (setting from remote controller)
operate boiler and heat
pump simultaneously
For heating
Outdoor temp.
Advanced Parallel mode
AND
Circulation water temp.
Setting temp
Boiler temp. OFF
= Setting -2°C
(setting from
remote controller)
Boiler temp. ON
= Setting -8°C
(setting from
remote controller)
Although heat pump operates
but water temperature does
not reach this temperature for
more than 30 mins (setting
from remote controller)
operate heat pump only
-10°C (setting from remote controller)
operate boiler and heat
pump simultaneously
For DHW tank
Outdoor temp.
AND
time
Tank setting
temp.
30 min (setting from
remote control)
If actual tank temp. does
not achieve the setting
temp. within 30min
(setting from remote
controller), the boiler
turn ON
When tank
temp. is
achieved, both
operations
stop
Heat pump
thermo ON
Tank temp.
Lowering
Tank
temp. Boiling initial
temp.
Heat
pump
Boiler
In Advanced Parallel mode, setting for both heating and tank can be made
simultaneously. During operation of “Heating/Tank” mode, when each time
the mode is switched, the boiler output will be reset to OFF. Please have
good understanding on the boiler control characteristic in order to select the
optimal setting for the system.
11. External SW Initial setting: No System setup 12:00am,Mon
Base pan heater
Alternative outdoor sensor
Bivalent connection
External SW
Select Confirm
Able to turn ON/OFF the operation by external switch.
12
12. Solar connection Initial setting: No System setup 12:00am,Mon
Alternative outdoor sensor
Bivalent connection
External SW
Solar connection
Select Confirm
Set when solar water heater is installed.
Setting include items below.
1Set either buffer tank or DHW tank for connection with solar water heater.
2Set temperature difference between solar panel thermistor and buffer tank or DHW tank
thermistor to operate the solar pump.
3Set temperature difference between solar panel thermistor and buffer tank or DHW tank
thermistor to stop the solar pump.
4Anti-freezing operation start temperature (please change setting based on usage of glycol.)
5Solar pump stop operation when it exceeds high limit temperature (when tank temperature exceed designated temperature (70~90°C))
13. External Error signal Initial setting: No System setup 12:00am,Mon
Bivalent connection
External SW
Solar connection
External Error signal
Select Confirm
Set when external error display unit is installed.
Turn on Dry Contact SW when error happened.
(CAUTION) Does not display when there is no Optional PCB.
When error occurs, error signal will be ON.
After turn off “close” from the display, error signal will still remain ON.
14. Demand control Initial setting: No System setup 12:00am,Mon
External SW
Solar connection
External Error signal
Demand control
Select Confirm
Set when there is demand control.
Adjust terminal voltage within 1 ~ 10 V to change the operating current limit.
(CAUTION) Does not display when there is no Optional PCB.
Analog input
[v]
Rate
[%]
Analog input
[v]
Rate
[%]
Analog input
[v]
Rate
[%]
0.0 not activate 3.9 ~ 4.1 40 7.4 ~ 7.6 75
0.1 ~ 0.6 4.2 45 40 7.7 80 75
0.7 10 not
activate
4.3 7.8
0.8 4.4 ~ 4.6 45 7.9 ~ 8.1 80
0.9 ~ 1.1 10 4.7 50 45 8.2 85 80
1.2 15 10 4.8 8.3
1.3 4.9 ~ 5.1 50 8.4 ~ 8.6 85
1.4 ~ 1.6 15 5.2 55 50 8.7 90 85
1.7 20 15 5.3 8.8
1.8 5.4 ~ 5.6 55 8.9 ~ 9.1 90
1.9 ~ 2.1 20 5.7 60 55 9.2 95 90
2.2 25 20 5.8 9.3
2.3 5.9 ~ 6.1 60 9.4 ~ 9.6 95
2.4 ~ 2.6 25 6.2 65 60 9.7 100 95
2.7 30 25 6.3 9.8
2.8 6.4 ~ 6.6 65 9.9 ~ 100
2.9 ~ 3.1 30 6.7 70 65 *A minimum operating current is applied on each model for
protection purpose.
*0.2 voltage hysteresis is provided.
*The value of voltage after 2nd decimal point are cut off.
3.2 35 30 6.8
3.3 6.9 ~ 7.1 70
3.4 ~ 3.6 35 7.2 75 70
3.7 40 35 7.3
3.8
15. SG ready Initial setting: No System setup 12:00am,Mon
Solar connection
External Error signal
Demand control
SG ready
Select Confirm
Switch operation of heat pump by open-short of 2 terminals.
Setting belows are possible
SG signal Working pattern
Vcc-bit1 Vcc-bit2
Open Open Normal
Short Open Heat pump and Heater OFF
Open Short Capacity 1
Short Short Capacity 2
Capacity setting 1
- Heating capacity ___%
Set by SG ready setting of remote controller
- DHW capacity ___%
Capacity setting 2
- Heating capacity ___%
- DHW capacity ___%
13
16. External Compressor SW Initial setting: No System setup 12:00am,Mon
External Error signal
Demand control
SG ready
External compressor SW
Select Confirm
Set when external compressor SW is connected.
SW is connected to external devices to control power consumption, ON signal will stop
compressor’s operation. (Heating operation etc. are not cancelled).
(CAUTION) Does not display if there is no Optional PCB.
If follow Swiss standard power connection, need to turn on DIP SW of main unit PCB. ON/OFF
signal used to ON/OFF tank heater (for sterilization purpose)
17. Circulation Liquid Initial setting: Water System setup 12:00am,Mon
Demand control
SG ready
External compressor SW
Circulation liquid
Select Confirm
Set circulation of heating water.
There are 2 types of settings, water and anti-freeze function.
(CAUTION) Please set glycol when using anti-freeze function.
It may cause error if setting is wrong.
18. Heat-Cool SW Initial setting: Disable System setup 12:00am,Mon
SG ready
External compressor SW
Circulation liquid
Heat-Cool SW
Select Confirm
Able to switch (fix) heating & cooling by external switch.
(Open) : Fix at Heating (Heating +DHW)
(Short) : Fix at Cooling (Cooling +DHW)
(CAUTION) This setting is disabled for model without Cooling.
(CAUTION) Does not display if there is no Optional PCB.
Timer function cannot be used. Cannot use Auto mode.
19. Force Heater Initial setting: Manual System setup 12:00am,Mon
External compressor SW
Circulation liquid
Heat-Cool SW
Force Heater
Select Confirm
Under manual mode, user can turn on force heater through quick menu.
If selection is ‘auto’, force heater mode will turn automatically if pop up error happen during
operation.
Force heater will operate follow the latest mode selection, mode selection is disable under
force heater operation.
Heater source will ON during force heater mode.
3-4. Operation Setup
Heat
20. Water temp. for heating ON Initial setting: compensation curve
   

      
   
Hot water temperature
compensation curve
Outdoor
temperature
Decide temperature
of 4 points as shown
in diagram
Set target water temperature to operate heating operation.
Compensation curve: Target water temperature change in conjunction with outdoor
ambient temperature change.
Direct: Set direct circulation water temperature.
In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
21. Outdoor temp. for heating OFF Initial setting: 24°C
   
OFF
ON
Set outdoor temp to stop heating.
Setting range is 5°C ~ 35°C
22. 'T for heating ON Initial setting: 5°C Out
Return
Out — Return = 1°C ~ 15°C
Set temp difference between out temp & return temp of circulating water of Heating operation.
When temp gap is enlarged, it is energy saving but less comfort. When the gap gets
smaller, energy saving effect gets worse but it is more comfortable.
Setting range is 1°C ~ 15°C
23. Outdoor temp. for heater ON Initial setting: 0°C
 
C
OFF
ON
Set outdoor temp when back-up heater starts to operate.
Setting range is -15°C ~ 20°C
User shall set whether to use or not to use heater.
14
Cool
24. Water temp. for cooling ON Initial setting: Compensation curve
       
  
   
compensation curve
Set target water temperature to operate cooling operation.
Compensation curve: Target water temperature change in conjunction with outdoor ambient
temperature change.
Direct: Set direct circulation water temperature.
In 2 zone system, zone 1 and zone 2 water temperature can be set separately.
25. 'T for cooling ON Initial setting: 5°C Out
Return
Return — Out = 1°C ~ 15°C
Set temp difference between out temp & return temp of circulating water of Cooling operation.
When temp gap is enlarged, it is energy saving but less comfort. When the gap gets smaller,
energy saving effect gets worse but it is more comfortable.
Setting range is 1°C ~ 15°C
Auto
26. Outdoor temp. for (Heat to Cool) Initial setting: 15°C

C
Heat
Cool
Outdoor temp. rising
Set outdoor temp that switches from heating to cooling by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
27. Outdoor temp. for (Cool to Heat) Initial setting: 10°C
  
C
Heat
Cool
Outdoor temp. dropping
Set outdoor temp that switches from Cooling to Heating by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
Tank
28. Floor operation time (max.) Initial setting: 8h Heat
Tank
30min ~ 10h
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more frequently.
It is a function for Heating + Tank operation.
29. Tank heat up time (max.) Initial setting: 60min Heat
Tank
5min ~ 4h
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating operation, but it may
not fully boil the tank.
30. Tank re-heat temp. Initial setting: -8°C
-12°C ~ -2°C
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become max temp.)
Setting range is -12°C ~ -2°C
31. Sterilization Initial setting: 65°C 10min ②① ③Set timer to perform sterilization.
1Set operating day & time. (Weekly timer format)
2Sterilization temp (55~75°C KIf use back-up heater, it is 65°C)
3Operation time (Time to run sterilization when it reached setting temp 5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
3-5. Service Setup
32. Pump maximum speed Initial setting: Depend on model Service setup 12:00am,Mon
Flow rate Max. Duty Operation
88:8 L/min 0xCE Air Purge
Select
Normally setting is not necessary.
Please adjust when need to reduce the pump sound etc.
Besides that, it has Air Purge function.
15
33. Pump down Service setup 17:26, Wed
Pump down:
ON
Confirm
Service setup 12:00am,Mon
Pump down:
ON
Confirm
Pump down operation
in progress!
OFF
Operate pump down operation
34. Dry concrete
   
     
       
       
   
Stage
Operate concrete curing operation.
Select Edit, set temp for every stage (1~99 1 is for 1 day).
Setting range is 25~55°C
When it is turned ON, dry concrete starts.
When it is 2 zone, it dries both zones.
35. Service contact Contact-1: Bryan Adams
ABC/ abc 0-9/ Other
A B C D E F G H I J K L M N O P Q R
S T U V W X Y Z a b c d e f g h i
j k l m n o p q r s t u v w x y z
Select Enter
Service setup 12:00am,Mon
Service contact:
Contact 1
Contact 2
Select Confirm
Able to set name & tel no. of contact
person when there is breakdown etc. or
client has trouble. (2 items)
4
Service and maintenance
When connect CN-CNT connector with computer
Please use optional USB cable to connect with CN-CNT connector.
After connected, it requests for driver. If PC is under Windows Vista
or later version, it automatically installs the driver under internet
environment.
If PC uses Windows XP or earlier version and there is no internet
access, please get FTDI Ltd's USB - RS232C conversion IC driver
(VCP driver) and install.
http://www.ftdichip.com/Drivers/VCP.htm
If forget Password and cannot operate remote controller
Press for 5 sec.
Password unlock screen appears, press Confirm and it shall reset.
Password will become 0000. Please reset it again.
(CAUTION) Only display when it is locked by password.
Maintenance menu
Setting method of Maintenance menu
Maintenance menu 12:00am,Mon
Actuator check
Test mode
Sensor setup
Reset password
Select Confirm
Press for 5 sec.
Items that can be set
1Actuator check (Manual ON/OFF all functional parts)
(CAUTION) As there is no protection action, please be careful
not to cause any error when operating each part (do
not turn on pump when there is no water etc.)
2Test mode (Test run)
Normally it is not used.
3Sensor setup (offset gap of detected temp of each sensor within
-2~2°C range)
(CAUTION) Please use only when sensor is deviated.
It affects temperature control.
4Reset password (Reset password)
Custom menu
Setting method of Custom menu
Custom menu 12:00am,Mon
Cool mode
Back-up heater
Reset energy monitor
Select Confirm
Please press for 10 sec.
Items that can be set
1Cool mode (Set With/Without Cooling function) Default is without
(CAUTION) As with/without Cool mode may affect electricity
application, please be careful and do not simply
change it.
In Cool mode, please be careful if piping is not
insulated properly, dew may form on pipe and water
may drip on the floor and damage the floor.
2Backup heater (Use/Do not use Backup heater)
(CAUTION) It is different from to use/not to use backup heater
set by client. When this setting is used, heater
power on due to protection against frost will be
disabled. (Please use this setting when it is required
by utility company.)
By using this setting, it cannot defrost due to low
Heating's setting temp and operation may stop
(H75)
Please set under the responsibility of installer.
When it stops frequently, it may be due to
insufficient circulation flow rate, setting temp of
heating is too low etc.
3Reset energy monitor (delete memory of Energy monitor)
Please use when moving house and handover the unit.
16
ENGLISH
ACXF60-17020-AA
PRINTED IN MALAYSIA
1/17

This manual suits for next models

9

Other Panasonic Heat Pump manuals

Panasonic WH-MXC09G3E8 User manual

Panasonic

Panasonic WH-MXC09G3E8 User manual

Panasonic WH-MDF06D3E5 User manual

Panasonic

Panasonic WH-MDF06D3E5 User manual

Panasonic WH-SXC16F9E8 User manual

Panasonic

Panasonic WH-SXC16F9E8 User manual

Panasonic WH-SDC0309K3E5 User manual

Panasonic

Panasonic WH-SDC0309K3E5 User manual

Panasonic S-80MW1E5 Service manual

Panasonic

Panasonic S-80MW1E5 Service manual

Panasonic WH-SDC12F6E5 User manual

Panasonic

Panasonic WH-SDC12F6E5 User manual

Panasonic AQUAREA WH-ADC H Series User manual

Panasonic

Panasonic AQUAREA WH-ADC H Series User manual

Panasonic WH-MHF12G6E5 User manual

Panasonic

Panasonic WH-MHF12G6E5 User manual

Panasonic WH-SDC09F3E8 Series User manual

Panasonic

Panasonic WH-SDC09F3E8 Series User manual

Panasonic WH-MDC09C3E8 User manual

Panasonic

Panasonic WH-MDC09C3E8 User manual

Panasonic WH-SDC09H3E5 User manual

Panasonic

Panasonic WH-SDC09H3E5 User manual

Panasonic WH-MHF12G9E8 User manual

Panasonic

Panasonic WH-MHF12G9E8 User manual

Panasonic WH-MXC09J3E5-1 User manual

Panasonic

Panasonic WH-MXC09J3E5-1 User manual

Panasonic WH-SD24BE5 User manual

Panasonic

Panasonic WH-SD24BE5 User manual

Panasonic WH-MXC12G9E8 User manual

Panasonic

Panasonic WH-MXC12G9E8 User manual

Panasonic Aquarea B1 Technical manual

Panasonic

Panasonic Aquarea B1 Technical manual

Panasonic WH-UD28AE User manual

Panasonic

Panasonic WH-UD28AE User manual

Panasonic WH-SDH09C0E8 User manual

Panasonic

Panasonic WH-SDH09C0E8 User manual

Panasonic S-26PK1U6 User manual

Panasonic

Panasonic S-26PK1U6 User manual

Panasonic WH-SDC03H3E5 User manual

Panasonic

Panasonic WH-SDC03H3E5 User manual

Panasonic CS-E12NKUAW User manual

Panasonic

Panasonic CS-E12NKUAW User manual

Panasonic WH-MDF09C3E8 User manual

Panasonic

Panasonic WH-MDF09C3E8 User manual

Panasonic WH-MDC05H3E5 User manual

Panasonic

Panasonic WH-MDC05H3E5 User manual

Panasonic WH-ADC0309J3E5 Technical manual

Panasonic

Panasonic WH-ADC0309J3E5 Technical manual

Popular Heat Pump manuals by other brands

Nibe HBS 05 Installer manual

Nibe

Nibe HBS 05 Installer manual

Baxi Geoflo Operation, installation & maintenance instructions

Baxi

Baxi Geoflo Operation, installation & maintenance instructions

Mitsubishi Electric PUZ-WM50VHA Service manual

Mitsubishi Electric

Mitsubishi Electric PUZ-WM50VHA Service manual

AERMEC CU 31 manual

AERMEC

AERMEC CU 31 manual

Jula 416-068 operating instructions

Jula

Jula 416-068 operating instructions

Sanyo 36UHW72R Specifications

Sanyo

Sanyo 36UHW72R Specifications

Mitsubishi Electric PUHZ-SW75VHA Service manual

Mitsubishi Electric

Mitsubishi Electric PUHZ-SW75VHA Service manual

Hitachi RAS-4FSNME1 instruction manual

Hitachi

Hitachi RAS-4FSNME1 instruction manual

Zodiac POWER PAC 1M Instructions for installation and use

Zodiac

Zodiac POWER PAC 1M Instructions for installation and use

Daikin FWE03D Series installation manual

Daikin

Daikin FWE03D Series installation manual

Automatic Heating AHGR410AW Series Installation and instruction manual

Automatic Heating

Automatic Heating AHGR410AW Series Installation and instruction manual

Robur K18 Simplygas Installation, use and maintenance manual

Robur

Robur K18 Simplygas Installation, use and maintenance manual

Carrier 50ZH Series Installation, Start-Up and Service Instructions

Carrier

Carrier 50ZH Series Installation, Start-Up and Service Instructions

American Standard WK 100 Series Installation operation & maintenance

American Standard

American Standard WK 100 Series Installation operation & maintenance

Daikin Altherma 3 R W Installer's reference guide

Daikin

Daikin Altherma 3 R W Installer's reference guide

Carrier 50PEC09-18 Aquazone Installation, Start-Up and Service Instructions

Carrier

Carrier 50PEC09-18 Aquazone Installation, Start-Up and Service Instructions

Maritime Geothermal NORDIC installation manual

Maritime Geothermal

Maritime Geothermal NORDIC installation manual

Dimplex LIAC12IM6 operating instructions

Dimplex

Dimplex LIAC12IM6 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.