PAT DS 350 / 1334 GRAPHIC User manual

LOAD MOMENT INDICATOR
DS 350 / 1334 GRAPHIC
RCL for Lattice Boom Truck Cranes
OPERATOR'S MANUAL
P/N L-B H9L0021 / PAT 031-300-190-088, Rev. -, 09/15/2000


Operator's Manual
DS 350 / 1334
TABLE OF CONTENTS
1 GENERAL INFORMATION.......................................................................................1
2 WARNINGS.............................................................................................................1
3 SYSTEM DESCRIPTION ..........................................................................................2
SYSTEM FUNCTION ............................................................................................................................... 3
OPERATING CONSOLE...........................................................................................................................4
LC DISPLAY.......................................................................................................................................... 4
CONTROL IDENTIFICATION .................................................................................................................... 5
4 CONFIGURATION SETUP......................................................................................10
RCL SETUP PROCEDURE ...................................................................................................................10
HOIST-IN-USE QUICK SELECTION.........................................................................................................16
OUTRIGGER POSITION QUICK SELECTION (IF APPLICABLE).....................................................17
5 OPERATION..........................................................................................................18
LIMIT SETTING................................................................................................................................... 20
Radius Limitation.................................................................................................. 21
Tip Height Limitation.............................................................................................23
Boom Angle Limitation.......................................................................................... 25
Slewing Angle Limitation / VirtualWall Definition ...................................................27
INFO CRANE CONFIGURATION............................................................................................................37
DISPLAY CONTRAST CONTROL...........................................................................................................38
6 PRE-OPERATION INSPECTION AND CALIBRATION VERIFICATION .....................39
7 SERVICE AND MAINTENANCE..............................................................................43
8 TROUBLESHOOTING............................................................................................44
General Information 1

Operator's Manual
DS 350 / 1334
The RCL can only work correctly, if all adjustments have been properly set. For correct
adjustment, the operator has to answer thoroughly and correctly all questions asked during
the setup procedure in accordance with the real rigging state of the crane. To prevent
material damage and serious or even fatal accidents, the correct adjustment of the RCL has to
be ensured before starting the crane operation.
1 GENERAL INFORMATION
The PAT Rated Capacity Limiter (RCL) DS 350 has been designed to provide the crane operator
with the essential information required to operate the machine within its design parameters.
Using different sensing devices, the Rated Capacity Limiter monitors various crane functions and
provides the operator with a continuous reading of the crane’s capacity. The readings
continuously change as the crane moves through the motions needed to make the lift.
The RCL provides the operator with information regarding the angle of the boom, working
radius, rated load and the total calculated weight being lifted by the crane.
If non permitted conditions are approached, the DS 350 Rated Capacity Limiter will warn the
operator by sounding an audible alarm, lighting a warning light and locking out those functions
that may aggravate the crane’s condition.
2 WARNINGS
The RCL is an operational aid that warns a crane operator of approaching overload conditions and
of over hoist conditions that could cause damage to equipment and personnel.
The device is not, and shall not, be a substitute for good operator judgment, experience and use
of accepted safe crane operating procedures.
The responsibility for the safe crane operation shall remain with the crane operator who shall
ensure that all warnings and instructions supplied are fully understood and observed.
Prior to operating the crane, the operator must carefully and thoroughly read and understand the
information in this manual to ensure that he knows the operation and limitations of indicator and
crane.
Proper functioning depends upon proper daily inspection and observance of the operating instructions
set forth in this manual. Refer to Section 6. Pre-Operation Inspection and Calibration Verification of
this handbook.

System Description
2
1. Operator’s Console
2. Central Unit
3. Cable Reel
4. Boom Angle Sensor
5. Junction Box
6. Line rider (Tensiometer)
7. A2B Switch
3 SYSTEM DESCRIPTION
The PAT Rated Capacity Limiter DS 350 consists of a central microprocessor unit, operating
console, angle sensor, line riders, and anti-two block switches.
The system operates on the principle of reference/real comparison. The real value, resulting from
the load measurement is compared with the reference data, stored in the central processor
memory and evaluated in the microprocessor. When limits are reached, an overload warning
signal is generated at the operator’s console. At the same time, the aggravating crane movements,
such as hoist up and boom down, will be stopped.
The fixed data regarding the crane, such as capacity charts, boom weights, centers of gravity
and dimensions are stored in memory chips in the central processor unit. This data is the
reference information used to calculate the operating conditions.
The boom angle is measured by the angle sensor, mounted in the boom base. The cable reel
cable serves as an electrical conductor for the anti two-block switches and line rider signals.
The hoist load is measured by line riders mounted on top of the boom, close to the tip.
The interactive user guidance considerably simplifies the input of operating modes as well as the
setting of geometry limit values.
Fig. 1: Components of the RCL system PAT DS 350

System Description
3
System Function
Upon switching on crane ignition switch, the system starts
with an automatic test of the RCL system, of lamps and
audible alarm. During the test, the LC display shows the
initial logo. (approximately 35seconds)
The previous configuration setup will be displayed showing bold
symbols as selected inputs and must only be confirmed OK if
that configuration setup equals the crane’s actual configuration.
Otherwise it must be deleted to enter a new configuration. (
chapter 4)
The operating configuration is determined by an interactive
step-by-step interrogation of the rigging states and reeving.
(chapter 4)
The configuration setup entered will be displayed showing
bold symbols as selected inputs and must be confirmed OK
to set the system into operation or deleted to enter a new
configuration. ( chapter4)
Upon acknowledgment of the inputs the system is ready for
operation.
START
SELF TEST
OK or DEL
operating
configuration
OK
DEL
Interactive INPUT
operating configuration
DEL
OK or DEL
operating
configuration
OK
OPERATIONAL

System Description
4
Operating Console
The console has 3 functions:
inputs by the crane operator (operating configuration, reeving, and calibration)
input of geometry limit values and signalization of exceeded limit values
display of important data andinformation
The operator’s console is mounted in the crane’s cab in the operator’s field of vision. For a better
identification of displays and operating elements, they are continuously backlit during operation.
LC Display
The LC display (LCD) used in the PAT DS 350 operator’s console is a high-resolution, wide
temperature-range component with transflective characteristics that give it a high visibility in
sunlight and during backlit night operation. Due to the nature of any LCD, it works on the
principle of polarization of light. It should be noted that dual polarizations that are at a certain
angle to each other can reduce the amount of light up to completely eliminating it if that angle
becomes perpendicular. This can have significance if the operator is wearing polarized
sunglasses that happen to be at perpendicularly polarized in relation to the LCD’s polarization. In
this rare case, the operator has to work without sunglasses or find different sunglasses that do
not have this characteristic, in order to avoid having the visibility of the display impaired.
The LCD contains an automatic temperature compensation that will adjust the LCD’s contrast
according to the surrounding temperature. In case of rapid or drastic temperature changes, it might
be advisable to support this automatic function by using the manual contrast adjustment feature. (
chapter 5.3)

System Description
5
Control Identification
This unit contains a display and different controls that are described as follows:
Fig 2: Operator’s Console
1. LC Display Area
2. Rated Capacity Limit Light
3. Rated Capacity Prewarning Light
4. Alarm Light “Anti-Two-Block”
5. By-Pass Warning Light
6. Button “ Alarm Stop”
7. Button and Control Light “TARE”
8. Button and Control Light
“LIMITS”
9. Button and Control Light “ SELECT
OPERATION MODE”
10.Button and Control Light "INFO"
11.Button and Control Light
"CONTROL"
12. Audible Alarm
13.By-Pass Key Switch
14.Button and Control Light "By-Pass
Anti-Two-Block"
15.Button and Control Light "By-Pass
RCL Kick-out function"
F1. Button "Function 1 "
F2. Button "Function 2 "
F3. Button "Function 3 "
F4. Button "Function 4 "
13
5
4
3
2
15
STOP
14
C TRL
11
10
1
SEL 9
LIM
8
TA RE
7
6
F4
F3
F2
F1
12

System Description
6
1
LC-Display
Examples:
Bargraph
Anti-two Block
Radius
The LC display visualizes graphical symbols, texts and numerical
values. Depending on the selected operating mode (setup, limit mode
or RCL representation), the corresponding information is indicated on
the display.
Please refer to the description of the different operating modes for the
signification of the individual elements. Refer to chapter 5 for complete list
of symbols.
Rated Capacity Limit Light
The red RATED CAPACITY LIMIT LIGHT (2) warns the operator that a
rated load condition has been reached. It lights up when the load on
the crane reaches the crane load capacity. The audible alarm also
sounds when this condition has been reached.
The following crane movements will be stopped concurrently:
Hoist up
boom down
Rated Capacity Pre-warning Light
The yellow RATED CAPACITY PRE-WARNING LIGHT (3) will light up
when the load on the crane reaches the defined pre-warning area, thus
indicating that an overload condition is approaching.
This means for the operator to continue his crane operation with
extreme caution.
Alarm Light “ Anti-2-Block”
The red “ Anti Two-Block Alarm Light ” (4) lights up when the anti-two-
block limit switch contacts open, indicating that a two-blocking
condition is approaching. At the same time the audible alarm will
sound.
The following crane movements will be stopped subsequently: hoist up and
boom down (depending on your machine).

System Description
7
By-Pass Key Warning Light
The red BY-PASS WARNING LIGHT (5) flashes to indicate that the kick-
out function of the A2B / RCL system is deactivated.
Button and Control Light “ Alarm Stop”
This ALARM STOP BUTTON (6) allows the audible alarm to be silenced
for approximately 15 seconds by pressing this button. Reference
“ Audible Alarm” (12).
Button and Control Light “ Tare”
The button “TARE” (7) is used to indicate the “Net load” on the LC
Display (1). Net load is the present load, less lifting tackle and hook
block. The Tare Button (7) has to be activated before lifting.
After pushing the “Tare Button” (7) the load display is set to zero (taring)
and the control light lights up. After lifting a load the display shows the
net load (pay load).
The net load display will change to the actual load display when the
boom radius is changed (either by angle or length).
Button "LIMITS"
Button to start the function "program limit values". For
the proceeding please refer to chapter 5.1.

System Description
8
The correct setting is of utmost importance for the proper function of the system and the
crane. Therefore only operators who are thoroughly familiar with use and operation of the
system shall set this button.
Button "SELECT"
Button to start the function "set operating mode". For
the proceeding please refer to chapter 4.1.
Button "INFO"
Button to start the function "information crane configuration"
Please refer to chapter 5.2.
Button "CONTROL"
Button to start additional functions.
Please refer to chapter 5.3.
Audible Alarm
The AUDIBLE ALARM (12), sounds during the following conditions:
overload condition
approaching two-block condition
preset limits reached
malfunction of the RCL system
operating error
The alarm can be temporarily silenced by pushing the button “ Alarm
Stop” (6).

System Description
9
Key Switch
The anti-two-block switch kick-out function is deactivated when the
KEY SWITCH (13) is turned to position "B" and the “By-pass A2B”
button (14) is pushed.
Or
The RCL kick-out function is deactivated when the KEY SWITCH (13) is
turned to position "B" and the “ By-pass RCL” button (15) is pushed.
KEY SWITCH (13) can be operated only by using the matching button.
Button "By-pass A2B"
This button can be operated only if key switch (13) is turned to position B.
While pushing this button, the kick-out function of the anti-two-block
switch is deactivated.
The By-Pass Warning Light (5) flashes to indicate that the kick-out function
is deactivated.
Button "By-pass RCL"
This button can be operated only if key switch (13) is turned to position B.
While pushing this button, the control lever lockout function of the RCL is
deactivated.
The By-Pass Warning Light (5) flashes to indicate that the kick-out function
Since button (14) and (15) deactivate the kick-out function of the RCL system / the anti two- block
system, the following instructions must be obeyed:
The by-pass function shall be used with discretion, as unwarranted use of it to override
the control lever lockout system can result in harm to the crane and danger to property
and persons.
Never use the by-pass function to either overload or operate the crane in a non-
permissible range.

System Description
1
0
is deactivated.

System Description
1
1
The correct setting is of utmost importance for the proper functioning of the system and the
crane. Therefore, only operators who are thoroughly familiar with the crane and the operation
of the system should execute the setting of the system according to the operating
configuration of the crane.
4 CONFIGURATION SETUP
The RCL setup procedure allows the operator to input the crane configuration using interactive
displays. The operator must complete the configuration setup procedure for the Rated Capacity
Limiter system by confirming (pressing OK) to set the system into operation or deleted (pressing DEL)
to enter a new configuration. The previous configuration setup will be displayed shown in bold
symbols and must match the current crane operating configuration.
RCL Setup Procedure
...starts: manually after each modification of the crane configuration by
pressing "SEL" (9)button.
...is operated: by answering the different questions using functionalbuttons
F1...F4 in accordance with the actual configuration of the crane.
...is cancelled: any time by pressing again the "SEL" (9) button. The system,
however, is only ready for operation, if the procedure has been
completed and the selections have been confirmed.
If the system is turned off, all adjustments remain stored. When turning the system on again these
adjustments can be acknowledged by merely pressing the OK button (provided that the crane
configuration has not been modified!).
During the programming procedure the Rated Capacity Prewarning Light (3) and the Rated
Capacity Limiter Light (2) will light up and the crane functions will be interrupted.
Note: If a configuration is selected which is not available, the display will indicate error code E04.
In this case, the procedure has to be repeated with valid values!

Configuration Setup
11
The RCL programming procedure consists of the following steps:
setting the boom typeconfiguration
setting the counterweight configuration
setting lower configuration
specify boom / setting the hoist configuration and reevings
selecting the pick point
confirmation of the programming procedure
For easy operation, the computer guides the operator through the procedure step by step.
(interactive operation)
Definition of the Displayed Symbols:
The following illustrations define the symbols appearing on the display during the setup
procedure for your crane. Not all symbols will be shown, depending on the crane model and the
answers to the questions.
Setting the boom typeconfiguration
Symbol description.
main boom operation
jib operation
main boom tip extension jib

Configuration Setup
12
Setting the outrigger / counterweight configuration
Retracted outriggers
Extended outriggers
Note: During the programming procedure this picture may be
skipped depending on the boom selection, if skipped outrigger
position must be fully extended 2.
WARNING: The front bumper outrigger is required, along with the four main outriggers, for all
"On Outrigger" capacities. All outriggers must also be properly set before swinging the
upper equipped with the " A", "B", or " ABC" counterweight. Always set the four main
outriggers before attempting to set the front bumper outrigger.
no bumper counter weight
A bumper counter weight
A +B bumper counter weight
increase counterweight
confirm counterweight
Note: During the programming procedure this picture may be
skipped depending on previous selection (i.e. boom selection
or outrigger position)
decrease counterweight
increase counterweight
confirm counterweight
Note: During the programming procedure this picture may be
skipped depending on previous selection (i.e. boom selection
or outrigger position)

Configuration Setup
13
decrease counterweight
increase counterweight
confirm counterweight
decrease counterweight
increase counterweight
confirm counterweight
Specify boom / jib lengths (example jib):
Select jib length:
Select jib offset:
decrease jib length
increase jib length
confirm jib length selection
5jib offset
15jib offset
25jib offset
Select main boom
length: increase main boom length
decrease main boom length
confirm main boom length
selection

Configuration Setup
14
Setting the hoist configuration and reeving (example jib)
Set front hoist drum
pick point:
Select front hoist
reeving:
select pick point 1
select pick point 2
no use of front hoist drum
decrease reeving
increase reeving
confirm reeving
Note: During the programming procedure
this picture may be skipped depending
on previous selection (i.e. front hoist not
used)
Set rear hoist drum pick
point:
Select rear hoist reeving:
select pick point 1
select pick point 2
no use of rear hoist drum
decrease reeving
increase reeving
confirm reeving
Note: During the programming procedure
this picture may be skipped depending
on previous selection (i.e. rear hoist not
used)

Configuration Setup
15
Once you have set the pick-points, you can switch between them by selecting which hoist drum
is in use:
Select hoist-in-use (example jib)
Hoist-in-use
selection: use pick point 1 asdefined above
use pick point 2 as defined above
Under each pick point that you had set, you will find a symbol of the crane with the
corresponding hoist drum filled in black.
Confirmation of the programming procedure
At the end of the procedure all selections are represented once again in symbolic forms.
If selections have been made, the corresponding symbols are filled black (i.e. hoist drums).
Hoist-in-use quick selection
(chapter 4.2)
outrigger position quick selection
(chapter 4.3)
cancel procedure
confirm inputs

Configuration Setup
16
Directly call function "Hoist-in-use quick selection".
Hoist-in-use quick selection
If, during the crane operation, the crane is switched over from using one hoist drum to the
other, i.e. from front to rear hoist drum, the RCL system has to be adjusted to this modification.
This modification can be entered without having to go through the whole RCL setup procedure
again:
Call RCL setup procedure.
Select hoist in use (example):
use pick point 1 as defined
use pick point 2 as defined
Confirm modification.
(call up the function again if you have selected
the wrong hoist drum by mistake)
Note: If a configuration is selected which is not available on the crane, the system will not
accept the selection and the display will indicate the error code E04.
Table of contents
Other PAT Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Keysight Technologies
Keysight Technologies N4374B user guide

Tektronix
Tektronix 7L5 instruction manual

ThermoWorks
ThermoWorks ThermaQ operating instructions

Elesa
Elesa DD51-E operating instructions

Niigata seiki
Niigata seiki LSL-26 instruction manual

Apera Instruments
Apera Instruments MP511 instruction manual