PDC spas Balboa ProView Use and maintenance manual

™
Fill the spa to its correct operang level. Be sure to open all valves and jets in the plumbing system before filling to allow as much
air as possible to escape from the plumbing and the control system during the filling process.
Aer turning the power on at the main power panel, the top-side panel will display a startup screen.
Aer the inial start-up sequence, the control will enter Priming Mode and display a Priming
Mode screen. Only pump icons appear on the priming mode screen. During the priming mode,
the heater is disabled to allow the priming process to be completed without the possibility of
energizing the heater under low-flow or no-flow condions. Nothing comes on automacally,
but the pump(s) can be energized by selecng the “Jet” buons. Manually exit Priming Mode
by pressing the “Exit” Buon.
As soon as the Priming Mode screen appears on the panel, select the “Jets 1” buon once to start Pump 1 in low-speed and then
again to switch to high-speed. Also, select the other pumps, to turn them on. The pumps should be running in high-speed to
facilitate priming. If the pumps have not primed aer 2 minutes, and water is not flowing from the jets in the spa, do not allow the
pumps to connue to run. Turn o the pumps and repeat the process. Note: Turning the power o and back on again will iniate a
new pump priming session. Somemes momentarily turning the pump o and on will help it to prime. Do not do this more than 5
mes. If the pump(s) will not prime, shut o the power to the spa and call for service.
Important: A pump should not be allowed to run without priming for more than 2 minutes. Under NO circumstances should a
pump be allowed to run without priming beyond the end of the 4-5 minute priming mode. Doing so may cause damage to the
pump and cause the system to energize the heater and go into an overheat condion.
You can manually exit Priming Mode by navigang to the “Back” buon on the Priming Mode Screen. Note that if you do not
manually exit the priming mode as described above, the priming mode will be automacally terminated aer 4-5 minutes. Be sure
that the pump(s) have been primed by this me.
Once the system has exited Priming Mode, the top-side panel will display the Main Screen, but the display will not show the
temperature yet, as shown below. This is because the system requires approximately 1 minute of water flowing through the
heater to determine the water temperature and display it.
On the Spa Screen, select a “Jets” buon once to turn the pump on or o, and to shi between low- and high-speeds if equipped.
If le running, the pump will turn o aer a me-out period. The pump 1 low-speed will me out aer 30 minutes. The high-speed
will me-out aer 15 minutes.

Important informaon about spa operaon can be seen quickly from the
Main Screen.
The most important features, including Set Temperature adjustment, can
be accessed from this screen.
The actual water temperature can be seen in large text and the desired,
or Set Temperature, can be selected and adjusted. Time-of-day, Ozone
operaon and Filter Operaon status is available, along with other mes-
sages and alerts. High Temperature Range vs. Low Temperature Range is
indicated in the upper right corner.
A Lock icon is visible if the panel or sengs are locked.
The Menu choices on the right can be selected and the screen will change to show more detailed controls or program funcons.
Navigang the enre menu structure is done with the 5 buons on the control panel.
When a text item changes to white during navigaon, that indicates the item is selected for acon. Operang or changing a
selected item is generally done with the center or “Select” buon.
The only item that can be changed on the le side of the Main Screen is the Set
Temperature. Press the Le Arrow buon to change the Set Temperature num-
ber to white. The Set Temperature can then be adjusted with the up and down
buons. Pressing the Select buon or the Right Arrow buon will save the new
set temperature.
On the right side of the screen, the menu selecons can be selected with the Up and Down Buons. Use the Select Buon to
choose an item. Selecng one of these items will change to a dierent screen with addional controls.
At the boom of the screen, messages may appear at various mes. Some messages must be dismissed by the user.
--If an Up or Down buon is pressed and held when the Set Temperature is selected, the temperature will
connue to change unl the buon is released, or the Temperature Range limits are reached.
The Spa Screen shows all available equipment to control, as well as other features, like Invert, in one
easy-to-navigate screen. The display shows icons that are related to the equipment installed on a parcular spa model, so this
screen may change depending on the installaon.
The navigaon buons are used to select an individual device. The device that is chosen is highlighted with a white outline and
the text under the icon changes to white. Once a device is selected, it can be controlled using the center Select Buon.
Some devices, like pumps, may have more than one ON state, so the icon will change to reflect the state that the equipment is in.
The Sengs Screen is where all programming and other spa behaviors are controlled.
This screen has several features that can be acted on directly. These features include Temp Range, Heat Mode, and Invert Panel.
When one of these items is highlighted, the Select Buon is used to toggle between two sengs.
™’

This system incorporates two temperature range sengs with independent set temperatures. The specific range can
be selected on the Sengs screen and is visible on the Main Screen in the upper right corner of the
display.
These ranges can be used for various reasons, with a common use being a “ready to use” seng vs. a
“vacaon” seng. Each range maintains its own set temperature as programmed by the user. This way,
when a range is chosen, the spa will heat to the set temperature associated with that range.
High Range can be set between 80°F and 104°F.
Low Range can be set between 50°F and 99°F.
In order for the spa to heat, a pump needs to circulate water through the heater. The pump that performs this funcon is known
as the “heater pump.”
The heater pump will be a 2-speed pump (Pump 1).
READY Mode will circulate water every 1/2 hour, using Pump 1 Low, in order to maintain a constant water temperature, heat as
needed, and refresh the temperature display. This is known as “polling.”
REST Mode will only allow heang during programmed filter cycles. Since polling does not occur, the temperature display may not
show a current temperature unl the heater pump has been running for a minute or two.
While Pump 1 High can be turned on and o, Pump 1 Low will run unl set temperature is reached, or 1 hour has passed.
--
READY/REST appears in the display if the spa is in Rest Mode and
the Jets 1 Buon is pressed. It is assumed that the spa is being used
and will heat to set temperature. While Pump 1 High can be turned
on and o, Pump 1 Low will run unl set
temperature is reached, or 1 hour has passed. Aer 1 hour, the
System will revert to Rest Mode. This mode can also be reset by
entering the Sengs Menu and changing the Heat Mode.
--
Seng the me-of-day is important for determining filtraon
mes and other background features. “Set Time” will appear on
the display if no me-of-day is set in the memory.
On the Sengs Screen, select the Time-of-Day line. On the Time-
of-Day screen, simply navigate right and le to select the Hour,
Minutes, AM/PM and 12/24 Hour segments. Use the Up and
Down Buons to make changes.
When changes are made, the icon to go “Back” changes to
“Save” and a new icon for “Cancel” appears under the Save icon.
Navigang to the le will highlight the Save icon, and navigang
down from there will allow the user to cancel the pending
change. Pressing the “Select” buon will save or cancel the
changes and go back to the previous screen.
NOTE: If power is interrupted to the system, Time-of-Day will be maintained for several days.
Back
Settings
Temp Range
Heat Mode
Time of Day
Filter Cycles
Light Cycle
Invert Panel
Lock
High
Ready
™’

™’
Using the same navigaon and adjustment as Seng the Time, Filter Cycles are set using a start me and a duraon. Each seng can be
adjusted in 15-minute increments. The panel calculates the end me and displays it automacally.
Pump 1 low and the ozone generator will run during filtraon.
The system is factory-programmed with one filter cycle that will run
in the evening (assuming the me-of-day is properly set) when
energy rates are oen lower. The filter me and duraon are
programmable.
A second filter cycle can be enabled as needed.
At the start of each filter cycle, the water will run briefly to purge the plumbing to maintain good water quality.
-
Filter Cycle 2 is OFF by default.
Simply navigate to the Filter Cycle 2 line by pressing the Right Navigaon Buon, and when “NO” is highlighted, press Up or Down to
toggle Filter Cycle 2 on and o. When Filter Cycle 2 is ON, it can be adjusted in the same manner as Filter Cycle 1 by navigang to the
right.
It is possible to overlap Filter Cycle 1 and Filter Cycle 2, which will shorten overall filtraon by the overlap amount.
In order to maintain sanitary condions, as well as protect against freezing, secondary water devices will purge water from their respec-
ve plumbing by running briefly at the beginning of each filter cycle.
If the Filter Cycle 1 duraon is set for 24 hours, enabling Filter Cycle 2 will iniate a purge when Filter Cycle 2 is programmed to begin.
Selecng Invert Panel will flip the display and the buons so the panel can be easily operated from inside or outside the hot tub.
The control can be restricted to prevent unwanted use or temperature adjustments. Locking the Panel prevents the controller from be-
ing used, but all automac funcons are sll acve. Locking the Sengs allows Jets and other features to be used, but the Set Tempera-
ture and other programmed sengs cannot be adjusted. Sengs Lock allows access to a reduced selecon of menu items. These in-
clude Set Temperature, Invert, Lock, Ulies, Informaon and Fault Log. They can be seen, not changed or edited.
1) Scroll to seng, press select buon.
2) Scroll to lock, press select buon.
3) Press > to Highlight either Seng or Panel.
4) Press select buon.
5) “Seng” will light and be acvated.
6) Press < key, press select buon twice.
7) If Panel is selected, press select buon,
control will return to main screen.
1) Scroll to seng, press select buon.
2) Scroll to Lock, press select buon.
3) Press > key to highlight Seng.
4) Press Select buon.
5) Press select buon twice, press key.
6) Press <, press select buon twice.
1) Press select buon.
2) Press > key.
3) Press select buon twice.
4) Press key.
5) Press <, press select buon
twice.

™’
-
Hold Mode is used to disable the pumps during service funcons like cleaning or replacing the filter. Hold Mode will last for 1 hour
unless the mode is exited manually. If spa service will require more than an hour, it is best to simply shut down power to the spa.
The Ulies Menu and Preferences selecons are to be accessed only by qualified service techs.
Change the temperature between Fahrenheit and Celsius
Change the clock between 12 hr. and 24 hr. display.
Turn the reminder messages (like “Clean Filter”) On or O.
Cleanup Cycle Duraon is not always enabled, so it may not appear. When it is available, set the length of me Pump 1
will run aer each use. 0-4 hours are available.
Pressing the Select Buon when Color is highlighted will cycle through 5 background colors available in the control.
Change the language displayed on the panel.
-
When a pump is turned on by a buon press, a clean-up cycle begins 30 minutes aer the pump is turned o or mes out. The
pump and the ozone generator will run for 30 minutes or more, depending on the system.
If the temperature sensors within the heater detect a low enough temperature, then the water devices automacally acvate to
provide freeze protecon. The water devices will run either connuously or periodically depending on condions.
The Ground Fault Circuit Interrupter (GFCI) or Residual Current Detector (RCD) is an important safety device and is required
equipment on a hot tub installaon.
CE registered systems do not have an RCD Test Feature due to the nature of the electrical service. The end-user must be trained how to
properly test and reset the RCD.
Most messages and alerts will appear at the boom of the normally used screens. Several alerts and messages may be displayed in a
sequence. Some messages can be reset from the panel. Messages that can be reset will appear with a “right arrow” at the end of the
message. This message can be selected by navigang to it at pressing the Select buon.
Aer the pump has been running for 1 minute, the temperature will be displayed. NOTE: The icon on the main screen
will glow red when the heater is acvated. The Jets 1 icon will also glow red while in low speed and the heater is acvated.
A potenal freeze condion has been detected, or the Aux Freeze Switch has closed. All water devices are acvated. In some cases,
pumps may turn on and o and the heater may operate during Freeze Protecon. This is an operaonal message, not an error indicator.

™’
The system has detected a spa water temp of 110°F (43.3°C) or more, and spa funcons are disabled. System will auto reset when the
spa water temp is below 108°F (42.2°C). Check for extended pump operaon or high ambient temp.
-
There may not be enough water flow through the heater to carry the heat away from the heang element. Heater start up will begin
again aer about 1 min. See “Flow Related Checks” below.
There is not enough water flow through the heater to carry the heat away from the heang element and the heater has been
disabled. See “Flow Related Checks” below. Aer the problem has been resolved, you must press any buon to reset and begin heater
start up.
Possible dry heater, or not enough water in the heater to start it. The spa is shut down for 15 min. Press any buon to reset the heater
start-up. See “Flow Related Checks” below.
There is not enough water in the heater to start it. The spa is shut down. Aer the problem has been resolved, you must clear the mes-
sage to restart heater start up. See “Flow Related Checks” below.
One of the water temp sensors has detected 118°f (47.8°C) in the heater and the spa is shut down. You must clear the message when
water is below 108°f (42.2°C). See “Flow Related Checks” below.
-
Check for low water level, sucon flow restricons, closed valves, trapped air, too many closed jets and pump prime. On some sys-
tems, even when spa is shut down by an error condion, some equipment may occasionally turn on to connue monitoring tempera-
ture or if freeze protecon is needed.
-
The temperature sensors MAY be out of sync by 2°F or 3°F. Call for Service.
--
The temperature sensors ARE out of sync. The fault above has been established for at least 1 hour. Call for service.
A temperature sensor or sensor circuit has failed. Call for Service.
The control panel is not receiving communicaon from the System. Call for Service.
-
At Power-Up, the system has failed the Program Checksum Test. This indicates a problem with the firmware (operaon
program) and requires a service call.

™’
(Persistent Memory Error)*
Contact your dealer or service organizaon if this message appears on more than one power-up.
Contact your dealer or service organizaon.
(Spa will not Start Up)
Contact your dealer or service organizaon.
(System Could Not Test the GFCI)
(North America Only) May indicate an unsafe installaon. Contact your dealer or service organizaon.
Water may be overheated. POWER DOWN THE SPA. DO NOT ENTER THE WATER. Contact your dealer or service organizaon.
A Pump Appears to have been Stuck ON when spa was last powered. POWER DOWN THE SPA. DO NOT ENTER THE WATER.
Contact your dealer or service organizaon.
Reminder Messages can be suppressed by using the Preferences Menu.
May appear on a regular schedule, i.e. every 30 days. Clean the filter media as instructed by the manufacturer.
(or RCD)
May appear on a regular schedule, i.e. every 30 days.
The GFCI or RCD is an important safety device and must be tested on a regular basis to verify its reliability. Every user should be
trained to safely test the GFCI or RCD associated with the hot tub installaon. A GFCI or RCD (European) will have a TEST and RESET
buon on it that allows a user to verify proper funcon.
May appear on a regular schedule, i.e. every 90 days. Change the water in the spa on regular basis to maintain proper chemical
balance and sanitary condions.
May appear on a regular schedule, i.e. every 30 days. Filters should be replaced regularly to maintain proper spa funcon and
sanitary condions.
Do not aempt service of this control system. Contact your dealer or service organizaon for assistance. Follow all owner’s
manual power connecon instrucons. Installaon must be performed by a licensed electrician and all grounding connecons
must be properly installed.
Table of contents
Popular Control Unit manuals by other brands

Samson
Samson 2357-1 Mounting and operating instructions

Siemens
Siemens AP 118 Operating and mounting instructions

Spectrum Brands
Spectrum Brands Pfister 013-PFL Quick installation guide

GF
GF 582 High Purity instruction manual

DentalEZ
DentalEZ RAMVAC WC-110 installation instructions

Veeder-Root
Veeder-Root DPLLD Site Prep and Installation Guide