Instruction Manual
1. Marking
VisuNet FLX – System with Enclosure
RemoteMonitorRM-320S-*
PersonalComputerPC-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3GExec[ic]IICT4Gc
IECExcertificate:IECExULD22.0019X
IECExmarking:Exec[ic]IICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3DExtc[ic]IIICT85°CDc
IECExcertificate:IECExULD22.0019X
IECExmarking:Extc[ic]IIICT85°CDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL),ControlDrawing116-0478
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G,T4
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB,T85°C
ClassIII,Zone22,GroupIIIA,T85°C
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Division2,GroupsA-D
ClassII,Division2,GroupsE,F,G
ClassIII
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Zone2,GroupIIC
ClassII,Zone22,GroupIIIB
ClassIII,Zone22,GroupIIIA
VisuNet FLX – System with Enclosure
DirectMonitorDM-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3GExecIICT4Gc
IECExcertificate:IECExULD22.0019X
IECExmarking:ExecIICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3DExtcIIICT85°CDc
IECExcertificate:IECExULD22.0019X
IECExmarking:ExtcIIICT85°CDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL)
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G,T4
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB,T85°C
ClassIII,Zone22,GroupIIIA,T85°C
The*-markedlettersofthetypecodeareplaceholdersforversionsofthe
device.
Pepperl+FuchsGroup
Lilienthalstraße200,68307Mannheim,Germany
Internet:www.pepperl-fuchs.com
2. Validity
Specificprocessesandinstructionsinthisinstructionmanualrequire
specialprovisionstoguaranteethesafetyoftheoperatingpersonnel.
3. Target Group, Personnel
Responsibilityforplanning,assembly,commissioning,operation,
maintenance,anddismountinglieswiththeplantoperator.
Thepersonnelmustbeappropriatelytrainedandqualifiedinordertocarry
outmounting,installation,commissioning,operation,maintenance,and
dismountingofthedevice.Thetrainedandqualifiedpersonnelmusthave
readandunderstoodtheinstructionmanual.
4. Reference to Further Documentation
Observelaws,standards,anddirectivesapplicabletotheintendeduse
andtheoperatinglocation.ObserveDirective1999/92/ECinrelationto
hazardousareas.
Thecorrespondingdatasheets,manuals,declarationsofconformity,EU-
typeexaminationcertificates,certificates,andcontroldrawingsif
applicable(seedatasheet)areanintegralpartofthisdocument.Youcan
findthisinformationunderwww.pepperl-fuchs.com.
Forspecificdeviceinformationsuchastheyearofconstruction,
scantheQRcodeonthedevice.Asanalternative,entertheserialnumber
intheserialnumbersearchatwww.pepperl-fuchs.com.
Duetoconstantrevisions,documentationissubjecttopermanentchange.
Pleasereferonlytothemostup-to-dateversion,whichcanbefoundunder
www.pepperl-fuchs.com.
5. Intended Use
Thedeviceisonlyapprovedforappropriateandintendeduse.Ignoring
theseinstructionswillvoidanywarrantyandabsolvethemanufacturer
fromanyliability.
TheVisuNetFLXSystemsaredesignedforZone2/22andnon-Ex
applications.Thedifferentmountingandconfiguringoptionsleadtothe
highestapplicationflexibility.Duetoafullymodulardesign,thenew
platform,whichisgearedtotheneedsofthe(petro-)chemicaland
pharmaceuticalindustries,theHMIscanbeconfiguredtofitexactlyand
enablessimpleandfastadjustmentsinthefield.
Usethedeviceonlywithinthespecifiedambienttemperaturerange.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Taketheintendeduseoftheconnecteddevicesfromthecorresponding
documentation.
Taketheintendeduseoftheinstalleddevicesfromthecorresponding
documentation.
Thedeviceisanelectricalapparatusforhazardousareas.
Thedeviceisnotsuitableforseparatinghazardousareas.
DevicesforwhichspecificconditionsofuseapplyhavetheXmarkingat
theendofthecertificatenumber.
Onlyusethedevicestationary.
6. Improper Use
Protectionofthepersonnelandtheplantisnotensuredifthedeviceisnot
usedaccordingtoitsintendeduse.
Thedeviceisnotsuitabletoseparateintrinsicallysafecircuitsfromnon-
intrinsicallysafecircuits.
Thedeviceisnotsuitableforseparatinghazardousareas.
7. Specific Conditions of Use
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Avoidinadmissiblyhighelectrostaticchargeonthedevice.
Mountthedeviceinalocationwithlowelectrostaticcharge.
Securetheconnectionsofthenon-intrinsicallysafecircuits
againstlooseningbysuitablemeans.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
Someinterfacesofthedevicemustbeclosedduringoperation
intheexplosion-hazardousarea.Ensurethattheseinterfacesareclosed.
For DC Supply
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryII(orbetter)accordingtoIEC/EN60664-1.
Onlyconnectsuppliesthatprovideprotectionagainstelectricshock(e.g.
SELVorPELV).
For AC Supply
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryIII(orbetter)accordingtoIEC/EN60664-1.
8. Mounting and Installation
Priortomounting,installation,andcommissioningofthedeviceyou
shouldmakeyourselffamiliarwiththedeviceandcarefullyreadthe
instructionmanual.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
Usemountingmaterialswhicharesuitabletosecurethedevicesafely.
Usemountingmaterialsthatfitthenatureofthemountingsurface.
Onlyuseaccessoriesspecifiedbythemanufacturer.
DOCT-7048D/2022-06 1/3
Mountthedeviceinaweatherprooflocation.
Ensurethattheoperatinglocationhasasufficientfloorloadcapacity.
Ifmountingtheenclosureonconcreteuseexpansionanchors.When
mountingtheenclosuretoasteelframeworkusevibrationresistant
mountingmaterial.
Ensurethatallfastenersarepresent.
Observethetighteningtorqueofthescrews.
Protectthedeviceagainstlong-termorexcessivemechanicalvibrations.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Thedeviceisheavy.Inordertoavoidpersonalinjuriesorproperty
damage,makeappropriateprovisionsforthemountingprocedure.
Donotmountthedeviceatlocationswhereanaggressiveatmosphere
maybepresent.
Donotdamagethebreatherdrain.
Donotcoverthebreatherdrain.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-14.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-25.
Ifthedevicehasalreadybeenoperatedingeneralelectricalinstallations,
thedevicemaysubsequentlynolongerbeinstalledinelectrical
installationsusedincombinationwithhazardousareas.
Ensurethattheequipotentialbondingconnectionsareingoodcondition,
andarenotdamagedorcorroded.
Ensurethattheterminalsareingoodconditionandarenotdamagedor
corroded.
Whenconnectingintrinsicallysafedeviceswithintrinsicallysafecircuitsof
associatedapparatus,observethemaximumpeakvalueswithregardto
explosionprotection(verificationofintrinsicsafety).Observethe
standardsIEC/EN60079-14orIEC/EN60079-25.
Provideatransientprotection.Ensurethatthepeakvalueofthetransient
protectiondoesnotexceed140%oftheratedvoltage.
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Thedevicemustbedisconnectedfromthepowersupplypriorto
installationandmaintenance.Thepowersupplymaybeactivatedonly
afterallthecircuitsrequiredforoperationhavebeenfullyassembledand
connected.
OnlyconnectadevicethatisinaccordancewithIEC/EN60950-1andis
designedassafetyextra-lowprotectivevoltage(SELV)system.
Protectthecircuitagainstovervoltage(e.g.,lightning).
Thedeviceprovidesagroundingterminaltowhichanequipotential
bondingconductorwithaminimumcrosssectionof4mm2mustbe
connected.
Requirements in Relation to Intrinsic Safety
Securetheconnectionsofthenon-intrinsicallysafecircuits
againstlooseningbysuitablemeans.
IfcircuitswithtypeofprotectionExiareoperatedwithnon-intrinsically
safecircuits,theymustnolongerbeusedascircuitswithtypeof
protectionExi.
Observethemaximumvaluesofthedevice,whenconnectingthedevice
tointrinsicallysafeapparatus.
Keeptheseparationdistancesbetweenallnon-intrinsicallysafecircuits
andintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Observethecomplianceoftheseparationdistancesbetweentwo
adjacentintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Circuitsofintrinsicallysafeapparatuscanbeledintohazardousareas,
wherebyspecialattentionmustbepaidtomaintainingseparation
distancestoallnon-intrinsicallysafecircuitsaccordingtotherequirements
inIEC/EN60079-14.
ObservethegroundingrequirementsfortypeofprotectionExiaccording
toIEC/EN6007914.
Forintrinsicallysafecircuits,thedielectricstrengthoftheinsulationagainst
otherintrinsicallysafecircuitsandagainsttheshieldmustbe
atleast500VaccordingtoIEC/EN60079-14.
Equipotentialbondingmustbeachievedalongtheintrinsicallysafe
circuits.
Requirements for Cable Glands
Installthecablesandthecableglandsinaccordance
withIEC/ENIEC60079-0andIEC/EN60079-14.
Onlyusecablesandconnectionlineswithatemperaturerange
appropriatetotheapplication.
Useonlyoneconnectionlineperopening.
Useonlyoneconductorperterminal.
Adjustthesealingelementofthecableglandtothediameterofthecables
andconnectionlinesused.
Observethetighteningtorqueofthecableglands.
Tightenallcableglandswiththeappropriatetorque.
Ensurethatallcableglandsareingoodconditionandaresecurely
tightened.
Closeallunusedcableglandswiththeappropriatesealingplugs.
Requirements for Cables and Connection Lines
Observethemaximumpermissiblelengthofcablesandconnectionlines.
Thedielectricstrengthoftheinsulationmustbeatleast500Vaccordingto
IEC/EN60079-14.
Observethepermissiblecorecrosssectionoftheconductor.
Theinsulationstrippinglengthmustbeconsidered.
Wheninstallingtheconductorstheinsulationmustreachuptothe
terminal.
Whenusingstrandedconductors,crimpwireendferrulesonthe
conductorends.
Observetheminimumbendingradiusoftheconductors.
Thenominalcorecrosssectionofaconnectedconductoris2.5mm2
(solid,finelystranded,andstranded).
Unusedcablesandconnectionlinesmustbeeitherconnectedtoterminals
orsecurelytieddownandisolated.
Installthecablesandconnectionlinesinsuchawaythattheyare
protectedfromultravioletradiation.
Installcablesandcableglandsinawaythattheyarenotexposedto
mechanicalhazards.
Equipotentialbondingmustbeachievedalongthefieldcircuits.
Requirements in Relation to Electrostatics
Avoidelectrostaticchargeswhichcouldresultinelectrostaticdischarges
whileinstalling,operating,ormaintainingthedevice.
Mountthedeviceinalocationwithlowelectrostaticcharge.
Avoidinadmissiblyhighelectrostaticchargeofthecablesandconnection
lines.
Includethemetalhousingcomponentsintheequipotentialbonding.
Anelectrostaticchargeposesanignitionhazardincaseofdischarge.
Includethefastenersintheequipotentialbonding.
Requirements for Surrounding Enclosures
Ifadditionalsurroundingenclosuresarerequired,thefollowingpointsmust
beconsideredduringinstallation:
lDegreeofprotectionaccordingtoIEC/EN60529
lResistancetolightaccordingtoIEC/EN60079-0
lResistancetoimpactaccordingtoIEC/EN60079-0
lResistancetochemicalagentsaccordingtoIEC/EN60079-0
lThermalenduranceaccordingtoIEC/EN60079-0
lElectrostaticsaccordingtoIEC/EN60079-0
Mountthesurroundingenclosureinawaythatallhousingoutlets,e.g.,
cableglandsandbreatherdrainsfacedownwards.
Whentheenclosurecoverisfitted,ensurethatallfastenersarefully
tightened.
Mountthedevicesothatitcomplieswiththespecifieddegreeof
protectionaccordingtoIEC/EN60529.
Forcableglandsonlyuseincomingcablediametersoftheappropriate
size.
Ensurethatthesurroundingenclosureisnotdamaged,distorted,or
corroded.
Ensurethatallsealsareclean,undamaged,andcorrectlyfitted.
Tightenallscrewsofthesurroundingenclosure/surroundingenclosure
coverwiththeappropriatetorque.
Closeallunusedenclosureholeswiththeappropriatestoppingplugs.
9. Operation, Maintenance, Repair
Priortousingtheproductmakeyourselffamiliarwithit.Readthe
instructionmanualcarefully.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
ObserveIEC/EN60079-17formaintenanceandinspection.
Donotuseadamagedorpolluteddevice.
Ifthereisadefect,thedevicemustberepairedbyPepperl+Fuchs.
Thedevicemustnotberepaired,changed,ormanipulated.Incaseof
failure,alwaysreplacethedevicewithanoriginaldevice.
Observethewarningmarkings.
Donotremovethewarningmarkings.
Ifthedeviceisinstalledinpotentiallyexplosivedustatmosphere,remove
dustlayerswhichexceed5mminregularintervals.
Removethedustbeforeopeningthesurroundingenclosure.
Connectionordisconnectionofenergizednon-intrinsicallysafecircuitsis
onlypermittedintheabsenceofapotentiallyexplosiveatmosphere.
Ifcleaningisnecessarywhilethedeviceislocatedinahazardousarea,in
ordertoavoidelectrostaticchargingonlyuseacleandampcloth.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Thedevicecangetveryhotduringoperation.Toprotectthedevicefrom
excessiveheating,observetherequiredclearancesandsufficient
ventilationwheninstallingthedevice.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
DOCT-7048D/2022-06 2/3
Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
Someinterfacesofthedevicemustbeclosedduringoperation
intheexplosion-hazardousarea.Ensurethattheseinterfacesareclosed.
10. Delivery, Transport, Disposal
Checkthepackagingandcontentsfordamage.
Checkifyouhavereceivedeveryitemandiftheitemsreceivedarethe
onesyouordered.
Keeptheoriginalpackaging.Alwaysstoreandtransportthedeviceinthe
originalpackaging.
Storethedeviceinacleananddryenvironment.Thepermittedambient
conditionsmustbeconsidered,seedatasheet.
Thedevice,built-incomponents,packaging,andanybatteriescontained
withinmustbedisposedincompliancewiththeapplicablelawsand
guidelinesoftherespectivecountry.
DOCT-7048D/2022-06 3/3

This manual suits for next models

1

Other Pepperl+Fuchs Desktop manuals

Pepperl+Fuchs VisuNet IXD RM-IXD2100-19U User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet IXD RM-IXD2100-19U User manual

Pepperl+Fuchs VisuNet GXP RM-GXP1100-22F User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet GXP RM-GXP1100-22F User manual

Pepperl+Fuchs VisuNet EX1 User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet EX1 User manual

Pepperl+Fuchs Ecom Pad-Ex 01 HR DZ2 User manual

Pepperl+Fuchs

Pepperl+Fuchs Ecom Pad-Ex 01 HR DZ2 User manual

Popular Desktop manuals by other brands

Sharp MZ-800 owner's manual

Sharp

Sharp MZ-800 owner's manual

IBM PC 100 Technical manual

IBM

IBM PC 100 Technical manual

IBM NetVista X40 Wprowadzenie

IBM

IBM NetVista X40 Wprowadzenie

Avalue Technology EPC-BSW Quick reference guide

Avalue Technology

Avalue Technology EPC-BSW Quick reference guide

Elo TouchSystems M-Series user guide

Elo TouchSystems

Elo TouchSystems M-Series user guide

Lenovo ThinkCentre Edge 92 Ghidul utilizatorului

Lenovo

Lenovo ThinkCentre Edge 92 Ghidul utilizatorului

Lenovo J100 Quick reference guide

Lenovo

Lenovo J100 Quick reference guide

NEC PowerMate 2000 Series Service and reference manual

NEC

NEC PowerMate 2000 Series Service and reference manual

Dell XPS Gen 5 Service manual

Dell

Dell XPS Gen 5 Service manual

Dell Inspiron 24 3477 All-in-One Service manual

Dell

Dell Inspiron 24 3477 All-in-One Service manual

SeaLevel Relio R1 user manual

SeaLevel

SeaLevel Relio R1 user manual

Dell GX260 - Optiplex Pentium 4 2.0GHz 512MB 40GB... Features list

Dell

Dell GX260 - Optiplex Pentium 4 2.0GHz 512MB 40GB... Features list

AXIOMTEK GOT5103W-845 user manual

AXIOMTEK

AXIOMTEK GOT5103W-845 user manual

Lenovo ideacentre 510A-15ICK Hardware Maintenance Manual

Lenovo

Lenovo ideacentre 510A-15ICK Hardware Maintenance Manual

Siemens Nixdorf PCD-B series operating manual

Siemens Nixdorf

Siemens Nixdorf PCD-B series operating manual

Dell 9200 Service manual

Dell

Dell 9200 Service manual

HP Compaq d330 ST installation instructions

HP

HP Compaq d330 ST installation instructions

HP Series 200 Hardware Support Document

HP

HP Series 200 Hardware Support Document

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.