Pepperl+Fuchs VisuNet FLX RM-320S Series User manual

Instruction Manual
1. Marking
VisuNet FLX – System with Enclosure
RemoteMonitorRM-320S-*
PersonalComputerPC-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3GExec[ic]IICT4Gc
IECExcertificate:IECExULD22.0019X
IECExmarking:Exec[ic]IICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3DExtc[ic]IIICT85°CDc
IECExcertificate:IECExULD22.0019X
IECExmarking:Extc[ic]IIICT85°CDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL),ControlDrawing116-0478
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G,T4
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB,T85°C
ClassIII,Zone22,GroupIIIA,T85°C
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Division2,GroupsA-D
ClassII,Division2,GroupsE,F,G
ClassIII
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Zone2,GroupIIC
ClassII,Zone22,GroupIIIB
ClassIII,Zone22,GroupIIIA
VisuNet FLX – System with Enclosure
DirectMonitorDM-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3GExecIICT4Gc
IECExcertificate:IECExULD22.0019X
IECExmarking:ExecIICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3DExtcIIICT85°CDc
IECExcertificate:IECExULD22.0019X
IECExmarking:ExtcIIICT85°CDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL)
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G,T4
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB,T85°C
ClassIII,Zone22,GroupIIIA,T85°C
The*-markedlettersofthetypecodeareplaceholdersforversionsofthe
device.
Pepperl+FuchsGroup
Lilienthalstraße200,68307Mannheim,Germany
Internet:www.pepperl-fuchs.com
2. Validity
Specificprocessesandinstructionsinthisinstructionmanualrequire
specialprovisionstoguaranteethesafetyoftheoperatingpersonnel.
3. Target Group, Personnel
Responsibilityforplanning,assembly,commissioning,operation,
maintenance,anddismountinglieswiththeplantoperator.
Thepersonnelmustbeappropriatelytrainedandqualifiedinordertocarry
outmounting,installation,commissioning,operation,maintenance,and
dismountingofthedevice.Thetrainedandqualifiedpersonnelmusthave
readandunderstoodtheinstructionmanual.
4. Reference to Further Documentation
Observelaws,standards,anddirectivesapplicabletotheintendeduse
andtheoperatinglocation.ObserveDirective1999/92/ECinrelationto
hazardousareas.
Thecorrespondingdatasheets,manuals,declarationsofconformity,EU-
typeexaminationcertificates,certificates,andcontroldrawingsif
applicable(seedatasheet)areanintegralpartofthisdocument.Youcan
findthisinformationunderwww.pepperl-fuchs.com.
Forspecificdeviceinformationsuchastheyearofconstruction,
scantheQRcodeonthedevice.Asanalternative,entertheserialnumber
intheserialnumbersearchatwww.pepperl-fuchs.com.
Duetoconstantrevisions,documentationissubjecttopermanentchange.
Pleasereferonlytothemostup-to-dateversion,whichcanbefoundunder
www.pepperl-fuchs.com.
5. Intended Use
Thedeviceisonlyapprovedforappropriateandintendeduse.Ignoring
theseinstructionswillvoidanywarrantyandabsolvethemanufacturer
fromanyliability.
TheVisuNetFLXSystemsaredesignedforZone2/22andnon-Ex
applications.Thedifferentmountingandconfiguringoptionsleadtothe
highestapplicationflexibility.Duetoafullymodulardesign,thenew
platform,whichisgearedtotheneedsofthe(petro-)chemicaland
pharmaceuticalindustries,theHMIscanbeconfiguredtofitexactlyand
enablessimpleandfastadjustmentsinthefield.
Usethedeviceonlywithinthespecifiedambienttemperaturerange.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Taketheintendeduseoftheconnecteddevicesfromthecorresponding
documentation.
Taketheintendeduseoftheinstalleddevicesfromthecorresponding
documentation.
Thedeviceisanelectricalapparatusforhazardousareas.
Thedeviceisnotsuitableforseparatinghazardousareas.
DevicesforwhichspecificconditionsofuseapplyhavetheXmarkingat
theendofthecertificatenumber.
Onlyusethedevicestationary.
6. Improper Use
Protectionofthepersonnelandtheplantisnotensuredifthedeviceisnot
usedaccordingtoitsintendeduse.
Thedeviceisnotsuitabletoseparateintrinsicallysafecircuitsfromnon-
intrinsicallysafecircuits.
Thedeviceisnotsuitableforseparatinghazardousareas.
7. Specific Conditions of Use
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Avoidinadmissiblyhighelectrostaticchargeonthedevice.
Mountthedeviceinalocationwithlowelectrostaticcharge.
Securetheconnectionsofthenon-intrinsicallysafecircuits
againstlooseningbysuitablemeans.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
Someinterfacesofthedevicemustbeclosedduringoperation
intheexplosion-hazardousarea.Ensurethattheseinterfacesareclosed.
For DC Supply
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryII(orbetter)accordingtoIEC/EN60664-1.
Onlyconnectsuppliesthatprovideprotectionagainstelectricshock(e.g.
SELVorPELV).
For AC Supply
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryIII(orbetter)accordingtoIEC/EN60664-1.
8. Mounting and Installation
Priortomounting,installation,andcommissioningofthedeviceyou
shouldmakeyourselffamiliarwiththedeviceandcarefullyreadthe
instructionmanual.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
Usemountingmaterialswhicharesuitabletosecurethedevicesafely.
Usemountingmaterialsthatfitthenatureofthemountingsurface.
Onlyuseaccessoriesspecifiedbythemanufacturer.
DOCT-7048D/2022-06 1/3

Mountthedeviceinaweatherprooflocation.
Ensurethattheoperatinglocationhasasufficientfloorloadcapacity.
Ifmountingtheenclosureonconcreteuseexpansionanchors.When
mountingtheenclosuretoasteelframeworkusevibrationresistant
mountingmaterial.
Ensurethatallfastenersarepresent.
Observethetighteningtorqueofthescrews.
Protectthedeviceagainstlong-termorexcessivemechanicalvibrations.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Thedeviceisheavy.Inordertoavoidpersonalinjuriesorproperty
damage,makeappropriateprovisionsforthemountingprocedure.
Donotmountthedeviceatlocationswhereanaggressiveatmosphere
maybepresent.
Donotdamagethebreatherdrain.
Donotcoverthebreatherdrain.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-14.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-25.
Ifthedevicehasalreadybeenoperatedingeneralelectricalinstallations,
thedevicemaysubsequentlynolongerbeinstalledinelectrical
installationsusedincombinationwithhazardousareas.
Ensurethattheequipotentialbondingconnectionsareingoodcondition,
andarenotdamagedorcorroded.
Ensurethattheterminalsareingoodconditionandarenotdamagedor
corroded.
Whenconnectingintrinsicallysafedeviceswithintrinsicallysafecircuitsof
associatedapparatus,observethemaximumpeakvalueswithregardto
explosionprotection(verificationofintrinsicsafety).Observethe
standardsIEC/EN60079-14orIEC/EN60079-25.
Provideatransientprotection.Ensurethatthepeakvalueofthetransient
protectiondoesnotexceed140%oftheratedvoltage.
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Thedevicemustbedisconnectedfromthepowersupplypriorto
installationandmaintenance.Thepowersupplymaybeactivatedonly
afterallthecircuitsrequiredforoperationhavebeenfullyassembledand
connected.
OnlyconnectadevicethatisinaccordancewithIEC/EN60950-1andis
designedassafetyextra-lowprotectivevoltage(SELV)system.
Protectthecircuitagainstovervoltage(e.g.,lightning).
Thedeviceprovidesagroundingterminaltowhichanequipotential
bondingconductorwithaminimumcrosssectionof4mm2mustbe
connected.
Requirements in Relation to Intrinsic Safety
Securetheconnectionsofthenon-intrinsicallysafecircuits
againstlooseningbysuitablemeans.
IfcircuitswithtypeofprotectionExiareoperatedwithnon-intrinsically
safecircuits,theymustnolongerbeusedascircuitswithtypeof
protectionExi.
Observethemaximumvaluesofthedevice,whenconnectingthedevice
tointrinsicallysafeapparatus.
Keeptheseparationdistancesbetweenallnon-intrinsicallysafecircuits
andintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Observethecomplianceoftheseparationdistancesbetweentwo
adjacentintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Circuitsofintrinsicallysafeapparatuscanbeledintohazardousareas,
wherebyspecialattentionmustbepaidtomaintainingseparation
distancestoallnon-intrinsicallysafecircuitsaccordingtotherequirements
inIEC/EN60079-14.
ObservethegroundingrequirementsfortypeofprotectionExiaccording
toIEC/EN6007914.
Forintrinsicallysafecircuits,thedielectricstrengthoftheinsulationagainst
otherintrinsicallysafecircuitsandagainsttheshieldmustbe
atleast500VaccordingtoIEC/EN60079-14.
Equipotentialbondingmustbeachievedalongtheintrinsicallysafe
circuits.
Requirements for Cable Glands
Installthecablesandthecableglandsinaccordance
withIEC/ENIEC60079-0andIEC/EN60079-14.
Onlyusecablesandconnectionlineswithatemperaturerange
appropriatetotheapplication.
Useonlyoneconnectionlineperopening.
Useonlyoneconductorperterminal.
Adjustthesealingelementofthecableglandtothediameterofthecables
andconnectionlinesused.
Observethetighteningtorqueofthecableglands.
Tightenallcableglandswiththeappropriatetorque.
Ensurethatallcableglandsareingoodconditionandaresecurely
tightened.
Closeallunusedcableglandswiththeappropriatesealingplugs.
Requirements for Cables and Connection Lines
Observethemaximumpermissiblelengthofcablesandconnectionlines.
Thedielectricstrengthoftheinsulationmustbeatleast500Vaccordingto
IEC/EN60079-14.
Observethepermissiblecorecrosssectionoftheconductor.
Theinsulationstrippinglengthmustbeconsidered.
Wheninstallingtheconductorstheinsulationmustreachuptothe
terminal.
Whenusingstrandedconductors,crimpwireendferrulesonthe
conductorends.
Observetheminimumbendingradiusoftheconductors.
Thenominalcorecrosssectionofaconnectedconductoris2.5mm2
(solid,finelystranded,andstranded).
Unusedcablesandconnectionlinesmustbeeitherconnectedtoterminals
orsecurelytieddownandisolated.
Installthecablesandconnectionlinesinsuchawaythattheyare
protectedfromultravioletradiation.
Installcablesandcableglandsinawaythattheyarenotexposedto
mechanicalhazards.
Equipotentialbondingmustbeachievedalongthefieldcircuits.
Requirements in Relation to Electrostatics
Avoidelectrostaticchargeswhichcouldresultinelectrostaticdischarges
whileinstalling,operating,ormaintainingthedevice.
Mountthedeviceinalocationwithlowelectrostaticcharge.
Avoidinadmissiblyhighelectrostaticchargeofthecablesandconnection
lines.
Includethemetalhousingcomponentsintheequipotentialbonding.
Anelectrostaticchargeposesanignitionhazardincaseofdischarge.
Includethefastenersintheequipotentialbonding.
Requirements for Surrounding Enclosures
Ifadditionalsurroundingenclosuresarerequired,thefollowingpointsmust
beconsideredduringinstallation:
lDegreeofprotectionaccordingtoIEC/EN60529
lResistancetolightaccordingtoIEC/EN60079-0
lResistancetoimpactaccordingtoIEC/EN60079-0
lResistancetochemicalagentsaccordingtoIEC/EN60079-0
lThermalenduranceaccordingtoIEC/EN60079-0
lElectrostaticsaccordingtoIEC/EN60079-0
Mountthesurroundingenclosureinawaythatallhousingoutlets,e.g.,
cableglandsandbreatherdrainsfacedownwards.
Whentheenclosurecoverisfitted,ensurethatallfastenersarefully
tightened.
Mountthedevicesothatitcomplieswiththespecifieddegreeof
protectionaccordingtoIEC/EN60529.
Forcableglandsonlyuseincomingcablediametersoftheappropriate
size.
Ensurethatthesurroundingenclosureisnotdamaged,distorted,or
corroded.
Ensurethatallsealsareclean,undamaged,andcorrectlyfitted.
Tightenallscrewsofthesurroundingenclosure/surroundingenclosure
coverwiththeappropriatetorque.
Closeallunusedenclosureholeswiththeappropriatestoppingplugs.
9. Operation, Maintenance, Repair
Priortousingtheproductmakeyourselffamiliarwithit.Readthe
instructionmanualcarefully.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
ObserveIEC/EN60079-17formaintenanceandinspection.
Donotuseadamagedorpolluteddevice.
Ifthereisadefect,thedevicemustberepairedbyPepperl+Fuchs.
Thedevicemustnotberepaired,changed,ormanipulated.Incaseof
failure,alwaysreplacethedevicewithanoriginaldevice.
Observethewarningmarkings.
Donotremovethewarningmarkings.
Ifthedeviceisinstalledinpotentiallyexplosivedustatmosphere,remove
dustlayerswhichexceed5mminregularintervals.
Removethedustbeforeopeningthesurroundingenclosure.
Connectionordisconnectionofenergizednon-intrinsicallysafecircuitsis
onlypermittedintheabsenceofapotentiallyexplosiveatmosphere.
Ifcleaningisnecessarywhilethedeviceislocatedinahazardousarea,in
ordertoavoidelectrostaticchargingonlyuseacleandampcloth.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Thedevicecangetveryhotduringoperation.Toprotectthedevicefrom
excessiveheating,observetherequiredclearancesandsufficient
ventilationwheninstallingthedevice.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
DOCT-7048D/2022-06 2/3

Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
Someinterfacesofthedevicemustbeclosedduringoperation
intheexplosion-hazardousarea.Ensurethattheseinterfacesareclosed.
10. Delivery, Transport, Disposal
Checkthepackagingandcontentsfordamage.
Checkifyouhavereceivedeveryitemandiftheitemsreceivedarethe
onesyouordered.
Keeptheoriginalpackaging.Alwaysstoreandtransportthedeviceinthe
originalpackaging.
Storethedeviceinacleananddryenvironment.Thepermittedambient
conditionsmustbeconsidered,seedatasheet.
Thedevice,built-incomponents,packaging,andanybatteriescontained
withinmustbedisposedincompliancewiththeapplicablelawsand
guidelinesoftherespectivecountry.
DOCT-7048D/2022-06 3/3
This manual suits for next models
1
Other Pepperl+Fuchs Desktop manuals
Popular Desktop manuals by other brands

HP
HP Workstation xw3100 Service and technical reference guide

Micro Star Computer
Micro Star Computer AG220 Series user manual

HP
HP 8000f - Elite Ultra-slim Desktop PC Technical reference guide

Tektronix
Tektronix K475 instructions

Dell
Dell OptiPlex 7070 Micro Service manual

Acnodes
Acnodes RMC 5210A Specifications