Pepperl+Fuchs VisuNet FLX RM-320S Series User manual

Instruction Manual
1. Marking
VisuNet FLX – System with Enclosure
RemoteMonitorRM-320S-*
PersonalComputerPC-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3GExec[ic]IICT4Gc
IECExcertificate:IECExULD22.0019X
IECExmarking:Exec[ic]IICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3DExtc[ic]IIICT85°CDc
IECExcertificate:IECExULD22.0019X
IECExmarking:Extc[ic]IIICT85°CDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL),ControlDrawing116-0478
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G,T4
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB,T85°C
ClassIII,Zone22,GroupIIIA,T85°C
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Division2,GroupsA-D
ClassII,Division2,GroupsE,F,G
ClassIII
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Zone2,GroupIIC
ClassII,Zone22,GroupIIIB
ClassIII,Zone22,GroupIIIA
VisuNet FLX – System with Enclosure
DirectMonitorDM-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3GExecIICT4Gc
IECExcertificate:IECExULD22.0019X
IECExmarking:ExecIICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2481X
ATEXmarking:1II3DExtcIIICT85°CDc
IECExcertificate:IECExULD22.0019X
IECExmarking:ExtcIIICT85°CDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL)
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G,T4
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB,T85°C
ClassIII,Zone22,GroupIIIA,T85°C
The*-markedlettersofthetypecodeareplaceholdersforversionsofthe
device.
Pepperl+FuchsGroup
Lilienthalstraße200,68307Mannheim,Germany
Internet:www.pepperl-fuchs.com
2. Validity
Specificprocessesandinstructionsinthisinstructionmanualrequire
specialprovisionstoguaranteethesafetyoftheoperatingpersonnel.
3. Target Group, Personnel
Responsibilityforplanning,assembly,commissioning,operation,
maintenance,anddismountinglieswiththeplantoperator.
Thepersonnelmustbeappropriatelytrainedandqualifiedinordertocarry
outmounting,installation,commissioning,operation,maintenance,and
dismountingofthedevice.Thetrainedandqualifiedpersonnelmusthave
readandunderstoodtheinstructionmanual.
4. Reference to Further Documentation
Observelaws,standards,anddirectivesapplicabletotheintendeduse
andtheoperatinglocation.ObserveDirective1999/92/ECinrelationto
hazardousareas.
Thecorrespondingdatasheets,manuals,declarationsofconformity,EU-
typeexaminationcertificates,certificates,andcontroldrawingsif
applicable(seedatasheet)areanintegralpartofthisdocument.Youcan
findthisinformationunderwww.pepperl-fuchs.com.
Forspecificdeviceinformationsuchastheyearofconstruction,
scantheQRcodeonthedevice.Asanalternative,entertheserialnumber
intheserialnumbersearchatwww.pepperl-fuchs.com.
Duetoconstantrevisions,documentationissubjecttopermanentchange.
Pleasereferonlytothemostup-to-dateversion,whichcanbefoundunder
www.pepperl-fuchs.com.
5. Intended Use
Thedeviceisonlyapprovedforappropriateandintendeduse.Ignoring
theseinstructionswillvoidanywarrantyandabsolvethemanufacturer
fromanyliability.
TheVisuNetFLXSystemsaredesignedforZone2/22andnon-Ex
applications.Thedifferentmountingandconfiguringoptionsleadtothe
highestapplicationflexibility.Duetoafullymodulardesign,thenew
platform,whichisgearedtotheneedsofthe(petro-)chemicaland
pharmaceuticalindustries,theHMIscanbeconfiguredtofitexactlyand
enablessimpleandfastadjustmentsinthefield.
Usethedeviceonlywithinthespecifiedambienttemperaturerange.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Taketheintendeduseoftheconnecteddevicesfromthecorresponding
documentation.
Taketheintendeduseoftheinstalleddevicesfromthecorresponding
documentation.
Thedeviceisanelectricalapparatusforhazardousareas.
Thedeviceisnotsuitableforseparatinghazardousareas.
DevicesforwhichspecificconditionsofuseapplyhavetheXmarkingat
theendofthecertificatenumber.
Onlyusethedevicestationary.
6. Improper Use
Protectionofthepersonnelandtheplantisnotensuredifthedeviceisnot
usedaccordingtoitsintendeduse.
Thedeviceisnotsuitabletoseparateintrinsicallysafecircuitsfromnon-
intrinsicallysafecircuits.
Thedeviceisnotsuitableforseparatinghazardousareas.
7. Specific Conditions of Use
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Avoidinadmissiblyhighelectrostaticchargeonthedevice.
Mountthedeviceinalocationwithlowelectrostaticcharge.
Securetheconnectionsofthenon-intrinsicallysafecircuits
againstlooseningbysuitablemeans.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
Someinterfacesofthedevicemustbeclosedduringoperation
intheexplosion-hazardousarea.Ensurethattheseinterfacesareclosed.
For DC Supply
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryII(orbetter)accordingtoIEC/EN60664-1.
Onlyconnectsuppliesthatprovideprotectionagainstelectricshock(e.g.
SELVorPELV).
For AC Supply
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryIII(orbetter)accordingtoIEC/EN60664-1.
8. Mounting and Installation
Priortomounting,installation,andcommissioningofthedeviceyou
shouldmakeyourselffamiliarwiththedeviceandcarefullyreadthe
instructionmanual.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
Usemountingmaterialswhicharesuitabletosecurethedevicesafely.
Usemountingmaterialsthatfitthenatureofthemountingsurface.
Onlyuseaccessoriesspecifiedbythemanufacturer.
DOCT-7048D/2022-06 1/3

Mountthedeviceinaweatherprooflocation.
Ensurethattheoperatinglocationhasasufficientfloorloadcapacity.
Ifmountingtheenclosureonconcreteuseexpansionanchors.When
mountingtheenclosuretoasteelframeworkusevibrationresistant
mountingmaterial.
Ensurethatallfastenersarepresent.
Observethetighteningtorqueofthescrews.
Protectthedeviceagainstlong-termorexcessivemechanicalvibrations.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Thedeviceisheavy.Inordertoavoidpersonalinjuriesorproperty
damage,makeappropriateprovisionsforthemountingprocedure.
Donotmountthedeviceatlocationswhereanaggressiveatmosphere
maybepresent.
Donotdamagethebreatherdrain.
Donotcoverthebreatherdrain.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-14.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-25.
Ifthedevicehasalreadybeenoperatedingeneralelectricalinstallations,
thedevicemaysubsequentlynolongerbeinstalledinelectrical
installationsusedincombinationwithhazardousareas.
Ensurethattheequipotentialbondingconnectionsareingoodcondition,
andarenotdamagedorcorroded.
Ensurethattheterminalsareingoodconditionandarenotdamagedor
corroded.
Whenconnectingintrinsicallysafedeviceswithintrinsicallysafecircuitsof
associatedapparatus,observethemaximumpeakvalueswithregardto
explosionprotection(verificationofintrinsicsafety).Observethe
standardsIEC/EN60079-14orIEC/EN60079-25.
Provideatransientprotection.Ensurethatthepeakvalueofthetransient
protectiondoesnotexceed140%oftheratedvoltage.
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Thedevicemustbedisconnectedfromthepowersupplypriorto
installationandmaintenance.Thepowersupplymaybeactivatedonly
afterallthecircuitsrequiredforoperationhavebeenfullyassembledand
connected.
OnlyconnectadevicethatisinaccordancewithIEC/EN60950-1andis
designedassafetyextra-lowprotectivevoltage(SELV)system.
Protectthecircuitagainstovervoltage(e.g.,lightning).
Thedeviceprovidesagroundingterminaltowhichanequipotential
bondingconductorwithaminimumcrosssectionof4mm2mustbe
connected.
Requirements in Relation to Intrinsic Safety
Securetheconnectionsofthenon-intrinsicallysafecircuits
againstlooseningbysuitablemeans.
IfcircuitswithtypeofprotectionExiareoperatedwithnon-intrinsically
safecircuits,theymustnolongerbeusedascircuitswithtypeof
protectionExi.
Observethemaximumvaluesofthedevice,whenconnectingthedevice
tointrinsicallysafeapparatus.
Keeptheseparationdistancesbetweenallnon-intrinsicallysafecircuits
andintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Observethecomplianceoftheseparationdistancesbetweentwo
adjacentintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Circuitsofintrinsicallysafeapparatuscanbeledintohazardousareas,
wherebyspecialattentionmustbepaidtomaintainingseparation
distancestoallnon-intrinsicallysafecircuitsaccordingtotherequirements
inIEC/EN60079-14.
ObservethegroundingrequirementsfortypeofprotectionExiaccording
toIEC/EN6007914.
Forintrinsicallysafecircuits,thedielectricstrengthoftheinsulationagainst
otherintrinsicallysafecircuitsandagainsttheshieldmustbe
atleast500VaccordingtoIEC/EN60079-14.
Equipotentialbondingmustbeachievedalongtheintrinsicallysafe
circuits.
Requirements for Cable Glands
Installthecablesandthecableglandsinaccordance
withIEC/ENIEC60079-0andIEC/EN60079-14.
Onlyusecablesandconnectionlineswithatemperaturerange
appropriatetotheapplication.
Useonlyoneconnectionlineperopening.
Useonlyoneconductorperterminal.
Adjustthesealingelementofthecableglandtothediameterofthecables
andconnectionlinesused.
Observethetighteningtorqueofthecableglands.
Tightenallcableglandswiththeappropriatetorque.
Ensurethatallcableglandsareingoodconditionandaresecurely
tightened.
Closeallunusedcableglandswiththeappropriatesealingplugs.
Requirements for Cables and Connection Lines
Observethemaximumpermissiblelengthofcablesandconnectionlines.
Thedielectricstrengthoftheinsulationmustbeatleast500Vaccordingto
IEC/EN60079-14.
Observethepermissiblecorecrosssectionoftheconductor.
Theinsulationstrippinglengthmustbeconsidered.
Wheninstallingtheconductorstheinsulationmustreachuptothe
terminal.
Whenusingstrandedconductors,crimpwireendferrulesonthe
conductorends.
Observetheminimumbendingradiusoftheconductors.
Thenominalcorecrosssectionofaconnectedconductoris2.5mm2
(solid,finelystranded,andstranded).
Unusedcablesandconnectionlinesmustbeeitherconnectedtoterminals
orsecurelytieddownandisolated.
Installthecablesandconnectionlinesinsuchawaythattheyare
protectedfromultravioletradiation.
Installcablesandcableglandsinawaythattheyarenotexposedto
mechanicalhazards.
Equipotentialbondingmustbeachievedalongthefieldcircuits.
Requirements in Relation to Electrostatics
Avoidelectrostaticchargeswhichcouldresultinelectrostaticdischarges
whileinstalling,operating,ormaintainingthedevice.
Mountthedeviceinalocationwithlowelectrostaticcharge.
Avoidinadmissiblyhighelectrostaticchargeofthecablesandconnection
lines.
Includethemetalhousingcomponentsintheequipotentialbonding.
Anelectrostaticchargeposesanignitionhazardincaseofdischarge.
Includethefastenersintheequipotentialbonding.
Requirements for Surrounding Enclosures
Ifadditionalsurroundingenclosuresarerequired,thefollowingpointsmust
beconsideredduringinstallation:
lDegreeofprotectionaccordingtoIEC/EN60529
lResistancetolightaccordingtoIEC/EN60079-0
lResistancetoimpactaccordingtoIEC/EN60079-0
lResistancetochemicalagentsaccordingtoIEC/EN60079-0
lThermalenduranceaccordingtoIEC/EN60079-0
lElectrostaticsaccordingtoIEC/EN60079-0
Mountthesurroundingenclosureinawaythatallhousingoutlets,e.g.,
cableglandsandbreatherdrainsfacedownwards.
Whentheenclosurecoverisfitted,ensurethatallfastenersarefully
tightened.
Mountthedevicesothatitcomplieswiththespecifieddegreeof
protectionaccordingtoIEC/EN60529.
Forcableglandsonlyuseincomingcablediametersoftheappropriate
size.
Ensurethatthesurroundingenclosureisnotdamaged,distorted,or
corroded.
Ensurethatallsealsareclean,undamaged,andcorrectlyfitted.
Tightenallscrewsofthesurroundingenclosure/surroundingenclosure
coverwiththeappropriatetorque.
Closeallunusedenclosureholeswiththeappropriatestoppingplugs.
9. Operation, Maintenance, Repair
Priortousingtheproductmakeyourselffamiliarwithit.Readthe
instructionmanualcarefully.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
ObserveIEC/EN60079-17formaintenanceandinspection.
Donotuseadamagedorpolluteddevice.
Ifthereisadefect,thedevicemustberepairedbyPepperl+Fuchs.
Thedevicemustnotberepaired,changed,ormanipulated.Incaseof
failure,alwaysreplacethedevicewithanoriginaldevice.
Observethewarningmarkings.
Donotremovethewarningmarkings.
Ifthedeviceisinstalledinpotentiallyexplosivedustatmosphere,remove
dustlayerswhichexceed5mminregularintervals.
Removethedustbeforeopeningthesurroundingenclosure.
Connectionordisconnectionofenergizednon-intrinsicallysafecircuitsis
onlypermittedintheabsenceofapotentiallyexplosiveatmosphere.
Ifcleaningisnecessarywhilethedeviceislocatedinahazardousarea,in
ordertoavoidelectrostaticchargingonlyuseacleandampcloth.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Thedevicecangetveryhotduringoperation.Toprotectthedevicefrom
excessiveheating,observetherequiredclearancesandsufficient
ventilationwheninstallingthedevice.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
DOCT-7048D/2022-06 2/3

Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
Someinterfacesofthedevicemustbeclosedduringoperation
intheexplosion-hazardousarea.Ensurethattheseinterfacesareclosed.
10. Delivery, Transport, Disposal
Checkthepackagingandcontentsfordamage.
Checkifyouhavereceivedeveryitemandiftheitemsreceivedarethe
onesyouordered.
Keeptheoriginalpackaging.Alwaysstoreandtransportthedeviceinthe
originalpackaging.
Storethedeviceinacleananddryenvironment.Thepermittedambient
conditionsmustbeconsidered,seedatasheet.
Thedevice,built-incomponents,packaging,andanybatteriescontained
withinmustbedisposedincompliancewiththeapplicablelawsand
guidelinesoftherespectivecountry.
DOCT-7048D/2022-06 3/3
This manual suits for next models
1
Other Pepperl+Fuchs Desktop manuals