6
Both chimney and flue pipe must be accessible for cleaning and if ALL parts of the chim-
ney cannot be reached through the stove, a soot door must be fitted to enable this this
to be done.
The Primary Air Sealing Plate is located on the front of the grate. To locate in position,
slacken the two screws beneath the grate and pull forward, then close the door fully,
open door and tighten screws.
POSITIONING OF APPLIANCE
The stove can be recessed in a suitable sized fireplace but a permanent free air gap of
at least 100mm must be left around the sides and top to obtain maximum heat output
and for access to the rear of the stove. There should not be any combustible material
within a distance of 500mm from the rear of the stove and 300mm from the side of the
stove. Furniture and general soft furnishings should not be within 900mm of any of the
stove surfaces including the stove pipe. In all instances the stove should be positioned
on a non-combustible hearth. Allow an apron of at least 300mm at the front of the stove
and 150mm on either side. The hearth on which the stove is to be placed should not be
less than 125mm thick if the floor is made of combustible material, and care should be
taken to level the stove and secure the hearth. If existing floors do not have adequate
load bearing capacity then suitable modifications to load bearing plates must be adopt-
ed.
When the stove is desired position mark hearth through holes in feet, remove stove drill
and plug hearth for securing stove and levelling. See typical flue connection methods
illustrated.
Ensure all parts are fitted in accordance with the instructions. On completion of the in-
stallation allow a suitable period of time for any fire cement and mortar to dry out, before
lighting the stove. Once the stove is under fire check all seals for soundness and check
that the flue is functioning correctly and that all products of combustion are vented safely
to atmosphere via the chimney terminal.
Care should be taken that all flues, hearths, and combustion air supplies are in
accordance with the current Building Regulations, Local Authority By-laws, British
Standards and Codes of Practice. Depending on the particular installation
circumstances it may be necessary to fit permanent ventilation. Please refer to approved
document J for detailed guidance. Care should be taken that these openings can not
become obstructed. Considerations and provisions must be made for any other appli-
ances requiring ventilation. An extractor fan must not be used in the same location as
the appliance. This appliance is not to be used with a shared chimney.
COMMISSIONING OF APPLIANCE
On completion of the installation and commissioning ensure that the operating
instructions for the stove are left with the customer. Ensure to advise the customer on
the correct use of the appliance and warn them to use only the recommended fuel for
the stove. Advise the user what to do should smoke or fumes be emitted from the
stove. The customer should be warned to use a fireguard to BS 8423:2002 in the
presence of children, aged and/or infirm persons.