Phason Plus Touch Series User manual


Copyright Phason Inc. Printed in Canada
All rights reserved. 34340001

iii
Table of contents
Chapter 1: Introducing Plus Touch.....................................................................................5
Getting to know Plus Touch ......................................................................................................................5
Features .................................................................................................................................................6
Becoming familiar with Plus Touch ...........................................................................................................7
Unlocking the screen.............................................................................................................................8
Chapter 2: Installing the Plus Touch...................................................................................9
What you need to know before installing the Plus Touch .........................................................................9
Understanding power surges and surge suppression ..........................................................................9
Reducing electrical noise using filters .................................................................................................10
Electrical ratings ..................................................................................................................................11
Using power contactors to increase the capacity of relays.................................................................11
Bottom layout.......................................................................................................................................12
Cover layout.........................................................................................................................................13
Mounting the Plus Touch.....................................................................................................................14
Connecting equipment to the Plus Touch...............................................................................................14
Connecting actuators ..........................................................................................................................14
Connecting curtain machines..............................................................................................................16
Connecting cooling, heating, and duty cycle equipment to relays.....................................................17
Connecting variable heating or cooling equipment ............................................................................18
Using three-phase power ....................................................................................................................19
Connecting an alarm system...............................................................................................................20
Connecting Phason 3K temperature sensors .....................................................................................21
Connecting DOL sensors ....................................................................................................................22
Connecting the power source .............................................................................................................23
Finishing the installation ..........................................................................................................................23
Chapter 3: Configuring your Plus Touch ..........................................................................25
What you need to know before configuring ............................................................................................25
Configuring the main control functions ...................................................................................................26
Setting the clock ..................................................................................................................................26
Selecting the units of measure ............................................................................................................27
Configuring hysteresis.........................................................................................................................27
Configuring relay stagger ....................................................................................................................28
Configuring alarm silencing.................................................................................................................28
Configuring the zone control mode.....................................................................................................29
Configuring sensor inputs .......................................................................................................................30
Configuring equipment............................................................................................................................32
Configuring variable stages.................................................................................................................32
Configuring relays................................................................................................................................33
Configuring relays for inlet actuators or curtains ................................................................................33
Calibrating inlet actuators....................................................................................................................34
Configuring relays for heating, cooling, or duty cycle ........................................................................35

iv
Chapter 4: Programming the Plus Touch .........................................................................37
Before you program the Plus Touch .......................................................................................................37
Programming zone settings ....................................................................................................................38
Programming the master set point ......................................................................................................38
Programming growth curves ...............................................................................................................39
Programming minimum ventilation curves..........................................................................................41
Programming modifiers .......................................................................................................................43
Programming alarms ...........................................................................................................................45
Programming equipment settings ...........................................................................................................48
Programming merged ventilation ........................................................................................................48
Programming variable cooling stages.................................................................................................49
Programming variable heating stages.................................................................................................51
Programming inlet actuators ...............................................................................................................53
Programming curtain control relays ....................................................................................................54
Programming relay stages ..................................................................................................................56
Programming duty cycles....................................................................................................................57
Using settings groups..............................................................................................................................59
Chapter 5: Monitoring and maintaining your Plus Touch ................................................61
Monitoring the Status screen...................................................................................................................61
Widgets ................................................................................................................................................62
Acknowledging alarms ........................................................................................................................63
Testing sensors and equipment ..............................................................................................................63
Using manual override.........................................................................................................................63
Testing a zone’s sensors and equipment ...........................................................................................64
Using screen lock security ......................................................................................................................65
Servicing and maintaining your Plus Touch............................................................................................66
Restoring the factory defaults..............................................................................................................66
Saving and restoring settings ..............................................................................................................66
Displaying the firmware version...........................................................................................................67
Updating the firmware .........................................................................................................................68
Replacement kits and optional accessories........................................................................................69
Appendixes ........................................................................................................................72
Appendix A: Troubleshooting ..................................................................................................................72
Possible causes and solutions ............................................................................................................72
Determining correct actuator feedback wiring ....................................................................................75
Appendix B: Factory defaults ..................................................................................................................76
Appendix C: Installation worksheet .........................................................................................................77
Appendix D: Configuration worksheets...................................................................................................79
Main control function worksheet .........................................................................................................79
Variable stage configuration worksheet ..............................................................................................80
Relay configuration worksheet ............................................................................................................81
Appendix E: Settings worksheets............................................................................................................82
Growth curve worksheet......................................................................................................................82
Variable stage settings worksheet .......................................................................................................83
Inlet actuators settings worksheet .......................................................................................................83
Curtain worksheet................................................................................................................................85
Heating, cooling, and duty cycle relay worksheet ..............................................................................85
Alarm settings worksheet ....................................................................................................................86
Appendix F: Motor curves .......................................................................................................................87
Index ........................................................................................................................................................89

5
Chapter 1: Introducing Plus Touch
Getting to know Plus Touch
Plus Touch brings a wealth of features that make it a powerful, versatile, and easy to use control.
Plus Touch has two variable AC stages and six relays to automatically control temperatures by
operating ventilation, heating, and cooling equipment according to your programmed settings.
Plus Touch is more than a temperature-based control; it can use other environmental conditions to
influence how it controls equipment. For example, if the humidity is too high in the zone, Plus
Touch can switch heaters on or increase ventilation to reduce it.
In addition to traditional staged control, Plus Touch offers VentGrid™ merged mode. Merged mode
has up to four steps, with the benefit that merged mode can provide smoother transitions between
steps than staged mode can between stages.
The growth and ventilation curves are powerful features that allow you to automatically change the
temperature set point and minimum ventilation rate over time to adjust to requirements as your
animals grow.
Plus Touch is ideal for swine, poultry, dairy, greenhouse, and light-industrial buildings, and is
compatible with most ventilation strategies.
Easy to program, manage, and monitor
The touchscreen display allows you to easily configure, program, and check the status of zones and
equipment. From the status screen, you can easily access configuration, settings, and more. Every
powerful feature is never more than a few taps away. This makes the Plus Touch one of the easiest-
to-use and user-friendly controls.
Security and peace of mind
Plus Touch has a screen lock security system. While screen lock is enabled, users must enter the PIN
before they can access any of the control’s functions, except the main status screen.
Plus Touch is compatible with most alarm systems. You can connect the control to an alarm siren or
other external alarm system. Customizable alarm settings allow you to choose which alarm
conditions you want to be notified about.

Chapter 1: Introducing Plus Touch
6
Features
Automatic two-zone temperature control, range: -13 to 125°F (-25 to 51°C)
VentGrid merged ventilation mode
Traditional staged ventilation mode
Two variable AC stages
Six pluggable general-purpose relays
Four 0 to 10 V signal outputs (optional)
Relay staggering for distributing startup loads
One alarm relay (for external siren or alarm system)
Sensor inputs:
5× Phason 3K Temperature
1× DOL-114 Temperature and Humidity
3× inputs for compatible DOL sensors
Intuitive user experience
Touchscreen display (5 inches)
Many control options:
Variable and fixed-stage ventilation
Variable and fixed-stage heating
Cooling equipment
Duty cycles
Growth and minimum ventilation curves
Secondary control modifiers
Easily updatable by USB
Onboard diagnostics and self-tests
CSA approval
NEMA 4X enclosure (corrosion resistant, water resistant, and fire retardant)
Limited warranty (2 years)

Becoming familiar with Plus Touch
7
Becoming familiar with Plus Touch
The Status screen is the “home” screen. The status screen is where you can find all basic
information at a quick glance.
From the status screen, you can easily access configuration, settings, and more by pressing the menu
in the top left corner. Every powerful feature is never more than a few taps away. This makes the
Plus Touch one of the easiest-to-use and user-friendly controls. For more information about the
status screen, read Monitoring the Status screen on page 61.
Icons
Here is a list of common icons you will use to interact with your Plus Touch.
HOME
Go to the status screen.
SAVE
Save changes.
MENU
Go to Manual Override, Settings, Configuration,
Administration, Screen Lock, and About Menus.
CANCEL
Discard changes and return to the previous screen.
BACK
Go to the previous screen.
PLAY
Play / resume the status screen.
UP/DOWN
Increase / decrease values.
PAUSE
Pause the status screen.
LEFT / RIGHT
Move / scroll through zones, equipment, or sensors.
ALARM
View the active alarm condition.
UNLOCK
Enter the PIN to unlock the screen.

Chapter 1: Introducing Plus Touch
8
Menu layout
If you leave the control in a menu or screen other than Status, the control returns
to the Status screen after five minutes without any key presses.
Unlocking the screen
Screen lock security is a feature you can use to control who makes changes to the controls settings.
By default, screen lock is not enabled.
While screen lock is enabled, users must enter the PIN before they can access the any of the
controls functions except the main status screen. For more information, read Using screen lock
security on page 65.
To unlock the screen
1. Press the Lock and then enter the four-digit PIN.
2. Press Unlock Screen.
MANUAL OVERRIDE SCREEN LOCK ABOUT
Staged ventilation
Relay stages
Ventilation curve
Actuator settings
Variable stages
Duty cycles
Curtain settings
Merged ventilation
Master set point
Growth curve
Heating
Relay stages
Duty cycles
Variable heat
Alarms
Modifiers
Configure settings groups
SETTINGS
Equipment
Sensors
Hysteresis
Units
Relay stagger
Date and time
Zone control mode
Alarm silencing
CONFIGURATION
Configuring lock
Restart control
Restore defaults
Show diagnostics
Saved to USB
Load from USB
Update firmware
Show version
ADMINISTRATION

9
Chapter 2: Installing the Plus Touch
What you need to know before installing the Plus Touch
1. Read Understanding power surges and surge suppression below.
If you do not install external surge suppression devices, you risk damage to
the electronics inside the Plus Touch, which may cause the Plus Touch to
fail.
Because it is not possible to completely protect this product internally from
the effects of power surges and other transients, we highly recommend that
you install external surge suppression devices. For specific
recommendations, see your electrical contractor.
If you do not take these precautions, you acknowledge your willingness to
accept the risk of loss or injury.
2. List all the equipment you want to control using this Plus Touch on the Installation worksheet
on page 77. Install the equipment and make your electrical connections according to the sheet.
3. Use the Configuration worksheets starting on page 79. List which relays and variable stages you
want to use for each piece of equipment, and how you want the equipment configured.
You can connect more than one piece of equipment to a single relay or stage as long as the total
current draw does not exceed the relay or stage’s limit. For more information, see the electrical
ratings on page 11.
Understanding power surges and surge suppression
Power surges can be caused by external influences (influences outside the barn; for example,
lightning or utility distribution problems) or they can be caused internally (inside the barn; for
example, starting and stopping inductive loads such as motors).
One of the most common causes of power surges is lightning. When lightning strikes the ground, it
produces an enormously powerful electromagnetic field. This field affects nearby power lines, which
transmit a surge to any device connected to it, such as lights, computers, or environmental controls
like the Plus Touch. Lightning does not have to actually strike a power line to transmit a surge.
Surge suppression devices offer some protection from power surges. Because it is not possible to
internally protect this product completely from the effects of power surges and other transients,
Phason highly recommend that you install external surge suppression devices. For specific
recommendations, see your electrical contractor. If you do not take these precautions, you
acknowledge your willingness to accept the risk of loss or injury.

Chapter 2: Installing the Plus Touch
10
Reducing electrical noise using filters
Electrical noise is caused by high voltage transients created when inductive loads, such as power
contactors, are switched on or off. The strength of the transients can be over 1000 volts and can
vary with the type of equipment and wiring, as well as several other factors.
Visible symptoms of electrical noise include erratic control operation, cycling inlets, communication
problems, and more. However, the effects of electrical noise are not always visible. Over time,
electrical noise can cause electronic circuits, relay contacts, and power contactors to deteriorate.
Installing filters helps extend the life of equipment
Filters help prevent electrical noise problems by absorbing the transient energy. Even if you do not
have visible symptoms of electrical noise, filters help keep controls operating reliably and can extend
the life of the controls and equipment connected to them.
Phason’s snubber filters (model 127-0) are for use with solenoids, timer relays, DC motors, furnaces,
and other equipment connected to the control’s relays. You can also use the filters with loads
connected to power contactors..
Do not use Snubber filters with variable stages.
Some power contactors include snubber filters. For more information, read
Using power contactors to increase the capacity of relays on page 11.
For more information about snubber filters or other Phason accessories, see
your dealer or visit www.phason.ca.

What you need to know before installing the Plus Touch
11
Electrical ratings
Input power
120/230 VAC, 50/60 Hz
Variable stages (2: VARI-1, VARI-2)
Fuses (2: F1and F2)
10 A at 120/230 VAC, general-purpose (resistive)
7 FLA at 120/230 VAC, PSC motor
1/2 HP at 120 VAC, 1 HP at 230 VAC, PSC motor
15 A, 250 VAC ABC-type ceramic
Relay stages (6: STG-1 to STG-6)
10 A at 120/230 VAC, general-purpose (resistive)
1/3 HP at 120 VAC, 1/2 HP at 230 VAC
360 W tungsten at 120 VAC
Alarm relay
0.4 A at 125 VAC; 2 A at 30 VDC, resistive load
0.2 A at 125 VAC; 1 A at 30 VDC, inductive load
You can connect more than one piece of equipment to a variable stage or relay as long as they are the same type (for
example, two fans) and the total current draw does not exceed the stage’s limit.
The FLA (full load ampere) rating accounts for the increase in motor current draw
when the motor operates at less than full speed. Make sure the motor/equipment
connected to the variable stage does not draw more than 7 FLA.
Using power contactors to increase the capacity of relays
Phason’s Manual Override Box (model MOB-4) has four 240-volt power contactors that allow you to
increase the load handling capability of control relays. Manual Override Box is ideal for secondary
ventilation fans and electric heaters.
MOB-4 electrical ratings
Coil: 10.2 mA at 240 VAC
Contact: 25 A at 240 VAC; resistive
2 HP at 240 VAC, 1 HP at 120 VAC; motor, power factor 0.4
1300 W at 120 VAC; tungsten
For more information, read Replacement kits and optional accessories on page 69 .

Chapter 2: Installing the Plus Touch
12
Bottom layout
Voltage selection switch –set this switch to the correct voltage before installing the Plus Touch.
Variable stage fuses (F1, F2) –15 A, 250 VAC ABC-type ceramic; F1 VAR 1, F2 for VAR 2.
Variable stage terminals (VAR1, VAR2) –connect variable speed fans to these terminals.
Relay terminals (RLY1 to RLY6) –connect single stage (on/off) equipment to these terminals. You can configure
these relays as heat, cool, duty cycle, inlet, or to follow another variable or relay.
Incoming power terminal –connect the incoming power (120/230 VAC, 50/60 Hz) to this terminal.
Alarm relay terminal –connect an external alarm system or alarm siren to this terminal.
Actuator feedback terminals (ACT1 and ACT2) –connect the feedback from the actuators to these is terminals.
Phason 3K temperature sensor terminals (TEMP1 to TEMP4) –connect the sensors to these terminals.
Display cable –make sure the ribbon cable from the display is properly connected to the socket.
1
2
3
4
5
6
7
8
9
4
3
6
7
8
9
1
2
5

What you need to know before installing the Plus Touch
13
Cover layout
USB –connect a USB drive when saving or loading settings, or updating firmware.
OUTDOOR –connect a Phason 3K Temperature Sensor for measuring outdoor temperature.
+5V –can provide +5 VDC
DOL (AUX1 to AUX3) –connect DOL 19 Carbon Dioxide or DOL 53 Ammonia Sensors.
Place the jumpers on the correct pins.
DOL 114 (TEMP / HUM) –connect a DOL 114 Temperature and Humidity Sensor.
Place the jumpers on the correct pins.
Pulse counter (COUNT) –not available, used for future development
1
2
3
4
5
6
4
5
6
4
2
5
1
3

Chapter 2: Installing the Plus Touch
14
Mounting the Plus Touch
1. Select a location for the Plus Touch. Make sure you have
enough cable and wire to reach all the equipment (fans,
heaters, misters, curtains, etc.) that you want to control.
2. Remove the screws from the front cover and then gently lift
it off.
3. Mount the enclosure to a wall using the four screws provided
with the control. Insert the screws into the large holes in each
corner of the box and tighten.
Connecting equipment to the Plus Touch
Follow these instructions when installing the Plus Touch and connecting equipment to it.
Use the electrical knockouts for bringing wires or cables into or out of the Plus
Touch enclosure. Do not make additional holes in the enclosure; this can damage
the watertight seal or control components and void the warranty.
Plus Touch test modes are useful for testing your equipment after installing and
configuring it. For more information, read Testing sensors and equipment on
page 63.
Refer to Appendix C: Installation worksheet on page 77 and Appendix D:
Configuration worksheets on page 79 when installing equipment.
Connecting actuators
You can connect up to two actuators to a Plus Touch. Actuators are used for equipment that is not
OFF or ON, but instead varies by a percentage. For example, inlets can be open various distances
from 0 percent to 100 percent.
Linear actuators are usually connected directly to inlets, or using cables and pulleys. Inlets are
generally located in the ceiling or walls. Inlet systems are usually spring loaded to aid in closing the
inlet, or counter weighted to aid in opening the inlets.
Each actuator you connect requires two relays: one for opening, and one for closing. Actuators must
be connected in the following combinations.
Actuator 1: Relay 1 –open Actuator 2: Relay 3 –open
Relay 2 –close Relay 4 –close

Connecting equipment to the Plus Touch
15
Actuators can be connected to relay pairs 1 and 2 or 3 and 4 only. Actuators
cannot be connected to any other combination of relays. For example, you cannot
connect an actuator to relays 1 and 3.
In Plus Touch, actuators are considered “inlets with feedback”. If yours does not
require feedback, it is considered a curtain, or, “inlet without feedback”. For more
information, read Configuring relays for inlet actuators or curtains on page 33.
Feedback potentiometers
Each actuator you connect must have a feedback potentiometer. The feedback potentiometer, which
you connect to one of the Plus Touch’two corresponding feedback terminals, lets the control know
how far the actuator’s arm is extended.
Most linear actuators are available with potentiometer feedback and internal adjustable limit
switches. A 10,000 ohm, 10 turn feedback potentiometer is preferred, but the internal feedback
potentiometer can range between 1000 and 20,000 ohms. Potentiometers outside of this range will
affect the precision to which the Plus Touch can control the actuator.
A system operates more precisely when using the largest amount of stroke that
is feasible with the actuator. The stroke is the distance the actuator arm
extends or retracts.
If you are unsure of the potentiometer wiring for your actuator, read
Determining correct actuator feedback wiring on page 75.
When routing the actuator feedback wires, do not run them in or along the
same conduit as AC-power lines. Follow the guidelines in the Control
fundamentals guide.
If you are measuring AC power with a digital multimeter (DMM), note that if a
limit switch opens the circuit, the DMM measures voltage after the relay switch
even if the relay is open.
The ratings of the actuator must not exceed the ratings of the Plus Touch.
Plus Touch relay ratings: 10 A at 120/230 VAC, general-purpose (resistive)
1/3 HP at 120 VAC, 1/2 HP at 230 VAC
360 W tungsten at 120 VAC

Chapter 2: Installing the Plus Touch
16
To connect actuators
Connect actuators to the Plus Touch as shown below. Refer to your actuator’s installation guide for
information about its power supply requirements.
Connecting curtain machines
Curtains are usually controlled by equipment called curtain machines (sometimes referred to as
winches). Curtains are opened and closed to let in more air or less air, the idea being more air cools
the building.
You can connect up to two curtain machines to the Plus Touch. Each curtain machine you connect
requires two relays: one for opening the curtain, and one for closing the curtain. Curtains must be
connected in the following combinations.
Curtain 1: Relay 1 –open Curtain 2: Relay 3 –open
Relay 2 –close Relay 4 –close
In Plus Touch, curtains are considered “inlets without feedback”. If yours does
require feedback, it is considered an actuator, or, “inlet with feedback”. For more
information, read Configuring relays for inlet actuators or curtains on page 33.
The ratings of the equipment must not exceed the ratings of the Plus Touch relays.
Plus Touch relay ratings
10 A at 120/230 VAC, general-purpose (resistive)
1/3 HP at 120 VAC, 1/2 HP at 230 VAC
360 W tungsten at 120 VAC
AC-powered actuators
DC-powered actuators

Connecting equipment to the Plus Touch
17
To connect curtain machines
Connect curtain machines to the Plus Touch as shown.
Connecting cooling, heating, and duty cycle equipment to relays
Heating or cooling equipment includes electric heaters, furnaces, single-speed fans, and any other
equipment that is either on or off.
The ratings of the equipment must not exceed the ratings of the Plus Touch relays.
Plus Touch relay ratings: 10 A at 120/230 VAC, general-purpose (resistive)
1/3 HP at 120 VAC, 1/2 HP at 230 VAC
360 W tungsten at 120 VAC
Gas furnaces using hot-surface ignition or glow plug can draw more current than
indicated on their nameplate and require power contactors. For more information,
read your furnace dealer.

Chapter 2: Installing the Plus Touch
18
To connect equipment to relays
Connect equipment as shown below.
Connecting variable heating or cooling equipment
Variable cooling equipment includes equipment such as variable-speed fans. Variable heating
equipment includes equipment such as heat mats and heat lamps.
Only permanent split capacitor motors appropriate for variable speed control, or
shaded pole motors, can be used on the variable stages.
If you are using three-phase power, connect the Plus Touch and the variable
cooling equipment to the same phase. For more information, read Using three-
phase power on page 19.
The ratings of the equipment must not exceed the ratings of the Plus Touch’
variable stages.
Variable stage ratings
10 A at 120/230 VAC, general-purpose (resistive)
7 FLA at 120/230 VAC, PSC motor
1/2 HP at 120 VAC, 1 HP at 230 VAC, PSC motor
Variable stage fuses
15 A, 250 VAC ABC-type ceramic
Gas-fired furnace or brooder
All other single-speed heating or cooling elements

Connecting equipment to the Plus Touch
19
To connect equipment to variable stages
Connect variable heating or cooling equipment to the Plus Touch as shown below.
Using three-phase power
If you are connecting the Plus Touch to a three-phase system, make sure to connect the control
power and the variable cooling equipment to the same phase.
The Plus Touch must be powered from the same phases that supply the equipment. If the Plus
Touch power and the variable stages are wired to different phases, the equipment will operate
erratically.
Correct three-phase wiring
Incorrect three-phase wiring

Chapter 2: Installing the Plus Touch
20
Connecting an alarm system
You can connect an alarm system to the Plus Touch’alarm terminal. An alarm system can be a siren,
alarm panel, or auto-dialer. Read your system’s installation guide for installation instructions and
information about the type of system: normally open or normally closed. Below are the descriptions
for the alarm terminal.
COMM: common connection
N/O: normally open; closes during alarm conditions
N/C: normally closed; opens during alarm conditions
For the alarm system to sound (or dial out) during an alarm condition, you must enable the alarms.
For more information, read Programming alarms on page 45.
The ratings of the siren or alarm system must not exceed the ratings of the Plus
Touch’alarm relay.
Alarm relay ratings: 0.4 A at 125 VAC; 2 A at 30 VDC, resistive load
0.2 A at 125 VAC; 1 A at 30 VDC, inductive load
To connect a normally open alarm system
If you are connecting the alarm system to a network of Plus
Touch controls and your system uses a normally open connection
(closes on alarm), connect the system as shown in the normally
open diagram.
Join all the COMM connections together and all the N/O
connections together. The Plus Touch alarm relays must be in
parallel with each other so any Plus Touch can trigger the alarm
system when an alarm condition occurs.
To connect a normally closed alarm system
If you are connecting the alarm system to a network of Plus
Touch controls and your system uses a normally closed connection
(opens on alarm), connect the system as shown in the normally
closed diagram.
Join the alarm relays in a continuous loop. The Plus Touch alarm
relays must be in series with each other so any Plus Touch can
trigger the alarm system when an alarm condition occurs.
Table of contents
Other Phason Control Unit manuals
Popular Control Unit manuals by other brands

Danfoss
Danfoss Icon Master Application guide

Allen-Bradley
Allen-Bradley ControlLogix DeviceNet 1756-DNB Configuration manual

Samson
Samson 2405 Series Mounting and operating instruction

Sonder
Sonder TELKAN 4 GSM 3G Manual of installation and use

Burkert
Burkert 6650 operating instructions

Spirax Sarco
Spirax Sarco Spira-trol KE73 Installation and maintenance instructions