Phoenix R250 Manual

USEPHOENIX.COM | 800-533-7533
1
Installation, Operation & Service Instructions
- READ AND SAVE THESE INSTRUCTIONS -
Specifications subject to change without notice.
R250 | LGR Dehumidifier
Electro-Mechanical Controls
This manual is provided to acquaint you with
the R250 dehumidifier so that installation,
operation and maintenance can proceed
successfully. Ultimate satisfaction depends
on the quality of installation and a thorough
understanding of this equipment. The R250
dehumidifier is built around tested engineering
principles and has passed a thorough
inspection for quality of workmanship and
function.
R250 LGR DEHUMIDIFIER
• Coated Coils
• The Phoenix R250 removes 135 pints per day at AHAM,
(80°F/60%RH).
• 310 CFM, 8.3 amps
• Operating Temperatures - up to 110°F
• Heavy-Duty Condensate Pump
• Compact Design
• Telescoping Handle
• Patented ByPass™ Technology
PHOENIX R250
PN 4043400
Patent: thermastor.com/patents
TS-1250 1/23 Rev. A

USEPHOENIX.COM | 800-533-7533
2
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
Table of Contents
1 Specifications
2 Important Safety Instructions
3 Operation
3.1 Transporting the Phoenix R250...................................
3.2 Location.......................................................................
3.3 Electrical Requirements..............................................
3.4 Condensate Removal...................................................
3.5 Ducting.........................................................................
3.6 Defrost Cycle................................................................
3.7 Power Switch................................................................
3.8 Pump Purge Switch......................................................
3.9 Hour Meter...................................................................
3.10 Bypass Control..........................................................
4 Maintenance
4.1 Air Filter........................................................................
4.2 Storage and Freeze Protection....................................
4.3 Service.........................................................................
5 Service
5.1 Technical Description...................................................
5.2 Troubleshooting............................................................
5.3 Air Mover.......................................................................
5.4 Condensate Pump........................................................
5.5 Float Safety Switch......................................................
6 Option & Accessories
7 Wiring Diagram
8 Service Parts
9 Warranty
Serial No.__________________________________
Purchase Date_____________________________
Dealer’s Name_____________________________
Read the operation and maintenance instructions carefully before using this unit. Proper adherence
to these instructions is essential to obtain maximum benefit from your Phoenix R250 dehumidifier.
WARNING
• It is designed to be used INDOORS ONLY.
• If used in a wet area, plug it into a GROUND FAULT INTERRUPTER.
• DO NOT use the Phoenix R250 as a bench or table.
• It must always be used in the upright position.

USEPHOENIX.COM | 800-533-7533
3
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
1 SAFETY CERTIFICATIONS
The Phoenix R250 conforms to unified standard UL 60335-
2-40.
2 SPECIFICATIONS
Part No. 4043400
Power 8.3 amps, 120 VAC, Grounded
Water 135 pints/day @ AHAM (80°F, 60%)
Removal
Blower 310 CFM without external ducting
Cord Length 25ft
Refrigerant 2 lb, 0 oz. R-410A
Charge
Operating 51°F to 110°F
Range
Filters 12” x 12” x 1” Pleated Media MERV-11
Duct Inlet – 12” Flex-Duct
Options Outlet – 10” Lay-Flat
Warranty Five years;
1st year 100% of Parts and Labor
2nd-3rd 100% pump part only
2nd-5th year 100% of sealed refrigeration system parts
Dimensions Width 20”
Height 33.5”
Depth 20”
Weight 109 lbs.

USEPHOENIX.COM | 800-533-7533
4
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
3 OPERATION
Place dehumidifier inside structure, place condensate hose into a drain,
or a large water tight container, and turn on. To decrease drying times,
make sure all windows and doors are closed to the outside and seal off
the affected wet areas from unaffected areas.
Optimum performance will be observed between the temperatures of
70°F and
95°F.
3.1 TRANSPORTING
The Phoenix R250 must always be upright when transported by vehicle. It may be
tipped on to its handle and back for loading and moving by hand.
If the unit is transported on its side, let it sit upright at least 30 minutes before use.
3.2 LOCATION
Note the following precautions when locating the Phoenix R250:
• It is designed to be used INDOORS ONLY.
• If used in a wet area, plug it into a GROUND FAULT INTERRUPTER.
• DO NOT use the Phoenix R250 as a bench or table.
• It must always be used in the upright position.
3.3 ELECTRICAL REQUIREMENTS
The Phoenix R250 plugs into a common grounded outlet on a 15 amp circuit. It
draws 8.3 amps at 80°F, 60% RH. If used in a wet area, a ground fault interrupter
(GFI) is required. If an extension cord is required, it must have a minimum of 14
gauge conductors if 25 feet long or less and 12 gauge conductors if greater than 25
feet long.
3.4 CONDENSATE REMOVAL
The Phoenix R250 is equipped with an internal condensate pump to remove the
water that is condensed during dehumidification. This pump allows the condensate
to be pumped 23 feet above the unit with the attached hose. If the condensate must
be pumped more than 23 feet above the unit, a relay pump must be added. Use the
PURGE button to empty reservoir prior to transport and storage. If the water in the
reservoir fails to be evacuated, the float safety switch will turn off the compressor.
Figure 1: Stacked
Phoenix R250

USEPHOENIX.COM | 800-533-7533
5
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
3.5 DUCTING
A wire duct collar is supplied to allow 10” lay-flat duct to be attached to the Phoenix
R250 outlet. Lay-flat plastic ducting is available (see accessories in section 6).
Attach ducting to the wire duct collar by inserting the plastic duct end through the
collar center and rolling the duct end outward to overlap the outside of the collar.
The duct and collar may then be quickly attached to the Phoenix R250 by snapping
the collar over the four plastic exhaust tabs.
If the R250 is located in the unaffected area, the intake can be ducted with 12” flex
duct (see accessories in section 6). Attach the flex duct to the top cover by hooking
the spiral wire under the four tabs. Tape the duct to the top cover for a complete
seal.
3.6 DEFROST CYCLE
When the Phoenix R250 is used in a cool area, or the dewpoint is below 50°,
frost will form on the cooling coil as it dehumidifies. When enough frost forms, the
defrost thermostat will initiate the defrost cycle. The cycle periodically turns off the
compressor while allowing the blower to run. The frost is melted by the air that the
blower draws through the cooling coil.
Figure 2: Phoenix
R250 with lay-flat
duct.

USEPHOENIX.COM | 800-533-7533
6
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
3.7 POWER SWITCH
The power switch (right of hour meter) lights up when the unit is turned on. The
unit will continue to run in all conditions until the switch is turned off; there is no
dehumidistat.
3.8 PUMP PURGE SWITCH
This switch (left of hour meter) minimizes the water left in the condensate pump
reservoir for moving or storage. Pressing and holding the pump purge switch will
cause the condensate pump to run. Hold the switch in until the flow from the
condensate hose stops.
Always manually purge the water reservoir before transport or storage. Turn off the
power and allow the plugged in dehumidifier to rest 15 minutes before the final
purge.
3.9 HOUR METER
The digital hour meter measures the cumulative time that the unit is turned on to
tenths of an hour. It stores its total when the unit is unplugged; the previous total
will be displayed when the unit is next turned on. It resets to zero after 99,999.9
hours of operation.

USEPHOENIX.COM | 800-533-7533
7
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
3.10 BYPASS CONTROL
Below 90°F - When the Phoenix R250 is used in normal dehumidifier operating
temperatures (below 90°F), the bypass cover must close the bypass openings,
figure 4. This maximizes performance by increasing the amount of air that is
dehumidified across the evaporator. This temperature range is often found during
the first 24 hours of a drying job.
Above 90°F - When the Phoenix R250 is used in high temperature conditions above
90°F, reposition the bypass cover to open the bypass holes, figure 5. This improves
dehumidifier efficiency by increasing the amount of airflow over the condenser and
lowering the refrigerant pressure. Simultaneously, this slows the airflow across
the evaporator allowing the air temperature to be lowered to the dew point and
increases dehumidifier capacity. These higher temperatures are often found after
the first 24 hours.
4 MAINTENANCE
4.1 AIR FILTER
The Phoenix R250 is equipped with a pleated media air filter that must be checked
regularly. The standard filter is a MERV-11 high efficiency filter. Operating the unit
with a dirty filter will reduce the dehumidifier’s capacity and efficiency and may force
the unit into defrost causing the compressor to cycle “off” and “on” unnecessarily.
The filter can generally be vacuumed clean several times before needing
replacement. Replacement filters can be ordered from the distributor or purchased
locally if available.
Figure 4: Below 90° (Normal)
Figure 6: Remove filter, snap Bypass
cover into position shown, and
replace filter.
Figure 5: At or above 90°

USEPHOENIX.COM | 800-533-7533
8
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
IMPORTANT
IMPORTANT: DO NOT operate the unit without the filter or with a less effective filter
as the heat exchanger and coils inside the unit could become clogged and require
disassembly to clean.
4.2 STORAGE AND FREEZE PROTECTION
There are two issues to consider when the Phoenix R250 is stored between uses
and both pertain to water trapped in the unit. The first is biological growth and
the second is damage caused by freezing. The effects of the trapped water can
be greatly reduced if precautions are taken to remove as much as possible before
storage.
1. Use the pump PURGE button to reduce the water level in the reservoir.
2. Stretch the hose flat to drain it completely. Raise one end above your head
and spool hose while draining water out the other end.
3. To reduce biological growth flush the unit with a bio-fungicide that is approved
for use with copper,aluminum and polyethylene. To flush:
a. Run the hose to a drain.
b. Plug in the unit but do not turn it on.
c. Remove the air filter. Slowly pour a quart of the antimicrobial through the
heat exchanger.
d. Hold in the pump purge switch to reduce the water level in the reservoir.
e. Flush with water.
4. If the unit will be exposed to freezing temperatures, after purging, pull back
the filter and pour 1 cup (8oz) of a alcohol based windshield washer fluid
through the heat exchanger. It will flow down into the pump reservoir. Do NOT
purge the solution out of the unit.
5. Dirty filters should be changed prior to long term storage to prevent biological
growth on the filter.
5 SERVICE
WARNING
WARNING: Servicing the Phoenix R250 with its high pressure refrigerant system and
high voltage circuitry presents a health hazard which could result in death, serious
bodily injury, and/or property damage. Only qualified service people should service
this unit.
CAUTION
CAUTION: Do not operate unit without the front housing in place.

USEPHOENIX.COM | 800-533-7533
9
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
5.1 TECHNICAL DESCRIPTION
The Phoenix R250 uses a refrigeration system similar to an air conditioner’s to
remove heat and moisture from incoming air and to add heat to the air that is
discharged.
Hot, high pressure refrigerant gas is routed from the compressor to the condenser
coil. The refrigerant is cooled and condensed by giving up its heat to the air
that is about to be discharged from the unit. The refrigerant liquid then passes
through a filter/drier and capillary tubing which cause the refrigerant pressure and
temperature to drop. It next enters the evaporator coil where it absorbs heat from
the incoming air and evaporates.
The evaporator operates in a flooded condition, which means that all the evaporator
tubes contain liquid refrigerant during normal operation. A flooded evaporator
should maintain constant pressure and temperature across the entire coil, from
inlet to outlet.
The mixture of gas and liquid refrigerant enter the accumulator after leaving the
evaporator coil. The accumulator prevents any liquid refrigerant from reaching
the compressor. The compressor evacuates the cool refrigerant gas from the
accumulator and compresses it to a high pressure and temperature to repeat the
process.
Figure 7:
Refrigeration
system

USEPHOENIX.COM | 800-533-7533
10
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
5.2 TROUBLESHOOTING
No dehumidification, neither air mover or compressor run and power switch does
not light when ON.
1. Unit unplugged or no power to outlet.
2. Power switch defective.
3. Loose connection in internal wiring.
No dehumidification, neither air mover nor compressor run with power switch ON
& lit.
1. Power switch defective.
2. Loose connection in interanal wiring
Some dehumidification, air mover runs continuously but compressor only runs
sporadically.
1. Unit is in defrost cycle.
2. Defrost thermostat defective.
3. Loose connection in compressor circuit.
4. Defective compressor overload.
5. Defective compressor.
6. Defective relay.
7. Low refrigerant charge.
No dehumidification, air mover runs but compressor does not.
1. Bad connection in compressor circuit.
2. Pump safety switch open.
3. Defective compressor capacitor.
4. Defective compressor overload.
5. Defective compressor.
6. Defective relay.
7. Low refrigerant charge.
8. Open high pressure switch.
Air mover does not run. Compressor runs briefly but cycles on & off.
1. Loose connection in air mover circuit.
2. Obstruction prevents impeller rotation.
3. Defective air mover.

USEPHOENIX.COM | 800-533-7533
11
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
Unit removes some water but not as much as expected.
1. Air temperature and/or humidity have dropped.
2. Humidity meter and/or thermometer used are out of calibration.
3. Unit has entered defrost cycle.
4. Air filter dirty.
5. Defective defrost thermostat
6. Low refrigerant charge.
7. Air leak such as loose front cover.
8. Defective compressor.
9. Restrictive exhaust ducting.
10.Faulty defrost thermostat
Unit runs but does not pump water.
1. Hose kinked or plugged.
2. Pump defective.
3. Bad connection in pump circuit.
4. Hose disconnected internally.
Unit pumps water automatically but not when purge switch is pushed.
1. Bad connection in purge switch circuit.
2. Defective purge switch.
Evaporator coil frosted continuously, low dehumidifying capacity.
1. Defrost thermostat loose or defective.
2. Low refrigerant charge.
3. Dirty air filter or air flow restricted.
Compressor runs with power switch OFF.
1. Defective relay.
2. Defective power switch.
5.3 AIR MOVER
The motorized impeller has a PSC motor and internal thermal overload protection. If
defective, the complete assembly must be replaced.
1. Unplug power cord
2. Remove the four screws attaching the bottom plate to the lower housing
3. Disconnect the impeller leads
4. Remove the four screws holding the impeller to the bottom plate
5. Reassemble the new impeller using the above procedure in reverse

USEPHOENIX.COM | 800-533-7533
12
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
5.4 CONDENSATE PUMP
The internal condensate pump removes water that collects in the reservoir.
To replace the condensate pump:
1. Unplug the unit
2. Remove the front housing
3. Unplug the pump wires from the wire harness
4. Remove the condensate hose and the two nuts attaching the pump to the
bracket
5. Replace the pump, hose, wiring, bolts, and housing in the reverse order
5.5 FLOAT SAFETY SWITCH
The float safety switch activates when the water rises too high in the condensate
reservoir. The float safety switch turns off the compressor until the water level lowers
and disengages the switch.
To replace the float safety switch
1. Unplug the dehumidifier
2. Remove the front housing
3. Unplug the float safety switch wires from the wire harness
4. Slide out the float switch from under the compressor support
5. Remove the one screw attaching the float switch bracket to the compressor
support
6. Replace the float, pump, wiring, bolts and housing in the reverse order
6 OPTIONS & ACCESSORIES
4025568 Air Filter, Pleated 12” x 12” x 1” MERV-11
4024750 Inlet Flex Duct 12” x 25” Metallize Polyester
4024935 Lay-Flat Duct 10” Round x 250’ Roll
4026309-02 10” Duct Ring
To order, contact your local distributor.

USEPHOENIX.COM | 800-533-7533
13
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
7 WIRING DIAGRAM

USEPHOENIX.COM | 800-533-7533
14
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
8 SERVICE PARTS
Part No. Description
4039458 Top Cover
4026979 Top Cover Catch
4026978 Top Cover Hinge
1154019 Hex Bolts, 1/4”–20 x 4” 4
1154014 Hex Bolts, 1/4”–20 x 1.75”
4026344 Handle Weldment
4026851 Wheel, 12”
1284404 Cotter Pin
4025568 Filter, 12” x 12” x 1”
4024916 Hose (1/4” ID x 33’ long)
4043208 Coupling Body, 1/4” Tube
4043234 Coupling Insert, 1/4” Tube
4037038 Cord
4028795 Hour Meter
4021822 Power Switch
4021796 Purge Switch
4033032-07 Capacitor, Compressor, 55 μF
4038235-07 Capacitor, Impeller, 15 μF
4026350 Handle Lever
40399981 Compressor
4033995-02 Evaporator Coil
4033996 Condenser Coil
4039769-01 Condensate Pump
4043186 Float Safety Switch
4026657 Impeller, Air Mover
4026308 Exhaust Grill
4026309-02 Wire Duct Collar
1154006 Impeller Plate Bolt
4041848 Defrost Thermostat
4043187 Compressor Relay

USEPHOENIX.COM | 800-533-7533
15
R250| LGR Dehumidifier Installation, Operation, and Maintenance Instructions
LIMITED WARRANTY
Warrantor:
Therma-Stor LLC
4201 Lien Rd
Madison, WI 53704
Telephone: 1-800-533-7533
Who Is Covered: This warranty extends only to the original end-user of the Phoenix R250 dehumidifier and
may not be assigned or transferred.
Year One: Therma-Stor LLC warrants that, for one (1) year the Phoenix R250 dehumidifier will operate free
from any defects in materials and workmanship, or Therma-Stor LLC will, at its option, repair or replace the
defective part(s), free of any charge.
Condensate pump: Units manufactured with the rotary style condensate pump have a three-year warranty
on this pump. Therma-Stor LLC warrants that, for three (3) years the condensate pump will operate
free from any defects in materials and workmanship, will repair or replace the defective part(s), provided
that all labor and transportation charges for the part(s) shall be borne by the end-user.
Year(s) Two Through Five: Therma-Stor LLC further warrants that for a period of five (5) years, the
condenser, evaporator, and compressor of the Phoenix R250 dehumidifier will operate free of any defects in
material or workmanship, or Therma-Stor LLC, at its option, will repair or replace the defective part(s), provided
that all labor and transportation charges for the part(s) shall be borne by the end-user.
Year(s) One Through Seven: Materials and workmanship of the housing are covered.
End-User Responsibilities: Warranty service must be performed by a Servicer authorized by Therma-Stor
LLC. If the end-user is unable to locate or obtain warranty service from an authorized Servicer, he should call
Therma-Stor LLC at the above number and ask for the Therma-Stor Service Department, which will then arrange
for covered warranty service. Warranty service will be performed during normal working hours.
The end-user must present proof of purchase (lease) upon request, by use of the warranty card or other
reasonable and reliable means. The end-user is responsible for normal care. This warranty does not cover any
defect, malfunction, etc. resulting from misuse, abuse, lack of normal care, corrosion, freezing, tampering,
modification, unauthorized or improper repair or installation, accident, acts of nature or any other cause beyond
Therma-Stor LLC’s reasonable control.
Limitations and Exclusions: If any Phoenix R250 Dehumidifier part is repaired or replaced, the new part
shall be warranted for only the remainder of the original warranty period applicable thereto (but all warranty
periods will be extended by the period of time, if any, that the Phoenix R250 Dehumidifier is out of service while
awaiting covered warranty service).
UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE PHOENIX R250 DEHUMIDIFIER
OR ANY PART THEREOF, ALL OTHER WARRANTIES IMPLIED BY LAW, INCLUDING MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE, SHALL ALSO EXPIRE. ALL WARRANTIES MADE BY THERMA-STOR LLC
ARE SET FORTH HEREIN, AND NO CLAIM MAY BE MADE AGAINST THERMA-STOR LLC BASED ON ANY ORAL
WARRANTY. IN NO EVENT SHALL THERMASTOR LLC, IN CONNECTION WITH THE SALE, INSTALLATION, USE,
REPAIR OR REPLACEMENT OF ANY PHOENIX R250 DEHUMIDIFIER OR PART THEREOF BE LIABLE UNDER ANY
LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION
WATER DAMAGE (THE END-USER SHOULD TAKE PRECAUTIONS AGAINST SAME), LOST PROFITS, DELAY, OR LOSS
OF USE OR DAMAGE TO ANY REAL OR PERSONAL PROPERTY.
Some states do not allow limitations on how long an implied warranty lasts, and some do not allow the
exclusion or limitation of incidental or consequential damages, so one or both of these limitations may not apply
to you.
Legal Rights: This warranty gives you specific legal rights, and you may also have other rights which vary
from state to state.
9 WARRANTY
Other manuals for R250
1
Table of contents
Other Phoenix Dehumidifier manuals

Phoenix
Phoenix R125 LGR Operation manual

Phoenix
Phoenix R200 LGR User manual

Phoenix
Phoenix R150 LGR User manual

Phoenix
Phoenix 200 MAX LGR User manual

Phoenix
Phoenix D385 User manual

Phoenix
Phoenix R125 User manual

Phoenix
Phoenix 4800 E User manual

Phoenix
Phoenix DryMAX XL User manual

Phoenix
Phoenix TS-332 User manual

Phoenix
Phoenix R250 User manual