Pitco MGII Service manual

L22-236 Rev 0 (04/03)
Technical Service and Exploded Parts
For Gas Fryers
Covering Models
MGII, MG2 Full and Split
Pitco Frialator, Inc., P.O. Box 501, Jct I-89 & I-93 Concord, NH 03302-0501 • 509 Route 3A, Bow, NH 03304
(800)258-3708•(603)225-6684•FAX(603)225-8497 www.pitco.com
FRANCAIS
US
CAN

L22-236 Rev 0 (04/03)
WARNING! FIRE HAZARD
THE OIL LEVEL SHOULD NOT FALL BELOW THE MINIMUM INDICATED LEVEL AT ANY
TIME. THE USE OF OLD OIL CAN BE DANGEROUS AS IT WILL HAVE A REDUCED FLASH-
POINT AND BE MORE PRONE TO SURGE BOILING.
WARNING
INSTALLATION AND ALL CONNECTIONS MUST BE MADE ACCORDING TO NATIONAL
AND LOCAL REGULATIONS AND CODES IN FORCE.
WARNING
A COUNTRY APPROVED ALL POLE CIRCUIT BREAKER WITH A MINIMUM OPEN CON-
TACT GAP OF 3mm MUST BE USED FOR PROPER INSTALLATION.
WARNING
THE FRYER IS NOT JET STREAM APPROVED. DO NOT CLEAN THE APPLIANCE WITH A
WATER JET.
NOTICE
INSTALLATION SHOULD ONLY BE DONE BY A COMPETENT SERVICE TECHNICIAN. THE
MODEL & SERIAL NUMBER, AND ELECTRICAL REQUIREMENTS STAMPED INTO THE
DATA PLATE, LOCATED ON THE INSIDE PANEL OF THE DOOR.
NOTICE
THIS APPLIANCE IS INTENDED FOR PROFESSIONAL USE ONLY, AND AS SUCH,
SHOULD BE OPERATED BY FULLY TRAINED PERSONNEL.
NOTICE
IT IS RECOMMENDED THAT THIS MACHINE BE INSPECTED BY A QUALIFIED TECHNI-
CIAN ON A YEARLY BASIS.
WARNING
THE POWER SUPPLY MUST BE DISCONNECTED SERVICING OR CLEANING THE UNIT.
WARNING
SHORTENING, WHEN IT IS AT OPERATING TEMPERATURES, IS VERY HOT AND
DANGEROUS! USE EXTREME CAUTION WHEN HANDLING! USE PROPER PROTEC-
TIVE GEAR SUCH AS INSULATED GLOVES, APRONS, FACE SHIELD, AND SLEEVES
WHEN HANDLING HOT SHORTENING. DO NOT ATTEMP TO MOVE MACHINE THAT HAS
HOT OIL IN IT. ALLOW TO COOLTO ROOM TEMPERATURE OR DRAIN THE OIL INTO A
SUITABLE CONTAINER BEFORE MOVING THE FRYER.
4/7/03-1

L22-236 Rev 0 (04/03)
Table of Contents
How Does It Work? ........................................................... 4
Component Troubleshooting.............................................. 4
Temperature Probe Resistance Chart ................................. 5
Basic Trouble Shooting ...................................................... 8
Relay Board Component Explanation ................................ 10
Ladder Diagram .................................................................. 13
Schematics ......................................................................... 14-19
Basic Parts List................................................................... 20
Exploded Drawings ............................................................ 20-31
Front Panel and Tank Components .................................... 22
Pump Box and Drain Manifold........................................... 24
Main Entrance Box and Gas Components ......................... 26
Pump Assembly and Filter Pan .......................................... 28
Wire Harness’ ..................................................................... 30
US
CAN
GB

L22-236 Rev 0 (04/03) 4
Chapter 1: HOW DOES IT WORK?
The McDonalds Gas II fryer components function in
specific order of operation. Knowing and understanding
the sequence of fryer and components operation will
enable you to diagnose equipment failure more
accurately.
Heating System
Power to the machine is turned ON:
• If Fuse F1 on the Relay board is good, the A.C.
indicator will illuminate and the controller will be
supplied with 24 VAC and, if the drain valve handle
is closed, the proximity switch will supply 24 VAC
to the DVI (drain valve interlock) input at the
controller.
• The computer control is turned ON:
• The side on relay will be energized, closing the
circuit and the S.O. indicator on the Relay Board
will illuminate. If the hi limit is NOT tripped the
ignition module will receive 24VAC at terminal 6 (24
VAC).
• The ignition module will have a 24 VAC output from
terminal 3(PV) to the PV terminal on the gas valve
and the ignitor will spark. When the pilot has lit and
the module has proven the pilot flame, it will have a
24 VAC output at terminal 1(MV) and put 24 VAC
on pin #2 at connection J/P32 on the relay board.
The heat demand relay on the relay board will
interrupt the 24 VAC supply to the gas valve until
the controller calls for heat.
Note: When the controller is on, the pilot should
always remain lit.
• Controller calls for heat:
• The heat demand relay will energize supplying the
gas valve with 24 VAC and the H.D. indicator on
the Relay Board will illuminate. This will also supply
the computer with a heat feedback signal.
Hi Limit System:
• If the hi limit trips, it interupts the 24 VAC supply to
the ignition module. When the controller calls for
heat, it will not receive a 24 VAC heat feed back.
With approximately 90 seconds of heat feed back
loss, the controller will indicate an ignition failure or
heat failure.After the hi limit is reset (unit cools to
400°F + 20°F) the computer will have to be turned
off and back on for the unit to heat.
Hood Relay System: U.S./Canada units only
• There is one Hood Relay (K6) per "battery" of
fryers (located on rear bottom brace of left hand
fryer), it is wired in parallel to every computer
(both sides of a twin). When any side of any
computer is turned on this relay energizes
(turning on the hood) and will stay energized
until all of the computers are turned off.
Filter System:
• Opening the RED return valve handle will close
the proximity switch causing the "pump run" relay
to be energized. The pump motor will begin to
run.Closing the return valve handle will de-ener-
gize the relay and the pump motor will stop run-
ning.
• The pump system is equipped with a circuit breaker
which will de-energize the system and the heat tape
in the event of over current. The circuit breaker
switch must be in the ON position for the pump
and heat tape to operate.
• The return piping system may be equipped with
optional heat tape to prevent solidification of solid
shortening. The heat tape is low wattage and is on
constantly to maintain liquid shortening in the line.
Chapter 2: COMPONENT
TROUBLESHOOTING:
Probe:
The resistance of the probe will change as the tem-
perature changes. The resistance will decrease as the
temperature rises.
If the probe is suspect, check its resistance and the oil
temperature at which it was taken. Compare these
values on the probe resistance chart.
If the probe returns an open circuit or 0 Ohms read-
ing, it should be replaced. If the resistance varies more
than 30 Ohms when being checked between 325-
375°F the probe will give a false temperature reading
on the computer and should be calibrated (up to 10°F)
or replaced. However, it will continue to operate at a
slightly higher or lower temperature.
Allow the oil to cool and check the probe resistance

5L22-236 Rev 0 (04/03)
at a lower temperature. As can be seen from the chart a
greater variation can be tolerated at a lower tempera-
ture.
Gas Valve:
The gas valve has a dual 24 VAC operator and will
open when the correct voltage is supplied to the
operator. With 24 VAC applied to the PV (24 VAC)
connection, the pilot valve operator will open, allowing
gas to flow to the pilot.
With 24 VAC applied to the MV (24 VAC)
connection, the main valve operator will open,
allowing gas to flow to the main burners.
Hi Limit:
The hi - limit switch is a normally closed switch until
the temperature at the hi-limit bulb reaches 450°F ±
15°F.
WARNING!
This test should be performed by a qualified
technician only! Monitor the fryer closely. This
test will cause the oil to heat past the normal
operating temperature and can cause damage
to the machine and its operator if care is not
taken.
WARNING!
This test will cause the burners to run
continuously.
In order to test this switch it will be necessary to utilize
the temperature control hi-limit feature. Refer to PM
Card FR015 for instructions on how to perform this
test.
If the switch does not trip between the prescribed limits
it is defective and should be replaced. Once tripped, the
switch cannot be reset until the oil has cooled to
approximately 400°F + 20°F. If the switch does not
reset after oil has cooled it is defective.
Drain Valve & Return Valve Switches:
These switches are a magnetically operated proximity
switches. When the Drain Valve handle is moved to the
open position, the Actuator will move away from the
switch causing the switch to open. When the Drain Valve
is closed the switch will close.
Opening the RED return valve handle will close the
proximity switch causing the "pump on" relay to be
energized. The pump will begin to pump. Closing
the return valve handle will open the proximity switch
causing the relay to de-energize and the pump will stop
pumping. These switches can also be checked with an
Ohm meter. When the switch is closed, you should have
continuity. The normal gap between theActuator and the
Sensor switch on the valve handle is 1/8" - 1/4" (3 -
6mm).
Transformer:
The transformer is a multiple AC input voltage 24 VAC
output voltage and can be checked by reading the input
and output voltages. A quick check for 24 VAC can be
done at the relay board behind the front panel. TheAC
indicator will be illuminated if the F1 fuse is good and the
board is receiving 24 VAC.
Ignition Module:
With a 24 VAC input at pin #6, the ignition module will
have a 24 VAC output from terminal 3(PV) and the ignitor
will spark until the module senses pilot flame or for ap-
proximately 90 seconds at which time the module will lock
out, whichever occurs first. When the module has proven
the pilot flame, it will have a 24 VAC output at terminal
1(MV) and put 24 VAC to pin 2 at connection J/P32 on
the relay board. The relay board will interrupt the 24 VAC
to the gas valve until the controller calls for heat.

L22-236 Rev 0 (04/03) 6
Note: When the controller is on, the pilot should
always remain lit.
Relay Board:
Note: J connectors are marked on the relay board.
•With 24 VAC supplied to pin #2 at connector J35 and a
good F1 fuse, the relay board will have a 24 VAC output
at pin #2 on connectors J33 and J34 and the A.C. indi-
cator will be illuminated.
Note: The fryer is equipped with a computer con-
troller, at connection J33 there will be a jumper from
pin #2 to pin #10 to supply 24 VAC to pin # 2 at
connection J31 to supply the controller with 24VAC.
•When the board receives a 24 VDC side on input at pin
#7 on connectors J31 or J33, the S.O. indicator will illu-
minate, the side on relay (S.O.) will energize and there
will be a 24 VAC output at pin #4 on connector J32.
•When the board receives a 24 VDC heat demand input
at pin #6 on connectors J31 or J33, the H.D. indicator
will illuminate, the heat demand relay (H.D.) will energize
and there will be continuity between pin #1 and pin #2 at
connector J32.
Computer Control:
Note:All controller test points are at connector P/J1 (clos-
est connector to the controller).
•With 24 VAC supplied to pin #1(24VAC supply) and
pin # 5(24VAC input from DVI), the display should read
"OFF".
•With the controller turned on, there will be a 24 VDC
output at pin #9 (side on).
•When the controller calls for heat, there will be a 24
VDC output at pin #8 (heat demand) and a 24 VAC in-
put at pin #6 (heat feed back). If the controller does not
receive the 24 VAC input at pin #6 in approximately 90
seconds, the controller will display "HEAT FAIL" or "IG-
NITION FAILURE". This would indicate a break in the
heat demand or heat feed back circuit.
1. Check the hi-limit switch (is it open or tripped).
2. Check the ignition module (sensing pilot flame,
locked out, 24 VAC at MV terminal).
3. Check the heat demand relay (H.D.) on the relay
board (is heat demand relay energized, continuity
through COM and NO contacts).
•If display reads "PROBE OP" "OPEN", ohm test the
temperature probe. Check the wires and connectors be-
tween the probe and controller for continuity.
•If display reads "SYSTEM" "FAILURE", test the tem-
perature probe and the wires and connectors between the
probe and controller for a short.
•If display reads "DRAINING" "TURN OFF", verify that
the drain valve is closed, check the proximity switch on
the drain valve, turn the fryer off, then turn the fryer on.

7L22-236 Rev 0 (04/03)
CONVERSION INSTRUCTIONS FOR SG
MODEL FRYERS
1) Following the Fryer Start-up and Shut Down
instructionsfollowing inthismanual, shutthe appliance
off and allow the appliance to cool to room temperature.
Insure that gas supply shut-off valve (located on the gas
supply pipe before the fryer operating gas valve) is in the
“OFF”position.Remove main burners.
2) Remove all burner orifices and replace them with the
appropriate orifices for the new gas type (refer to Table
1 for proper orifice size, that will match gas type conver-
sion). Make sure that an approved gas sealant is
appliedtothe orifice threads before installingtheorifices
tothemainburnermanifold(removeburners if neces-
sary to replace orifices).
3). Burners must also be replaced if changing from LP
to NAT or NAT to LP according to the chart below.
Any gas type marked as NAT uses burner part
#B8037303 vertical slotted face burner, any gas type
marked as LP uses part #B80320001 screen mesh face
burner.
NOTE: If unit is being converted from LP to
Natural gas or Natural to LP gas, the pilot orifice
and regulator (on gas valve) must also be re-
placed with appropriate orifice and gas type regula-
tor.
4) If burners were removed, reinstall them and turn gas
supply shut-off valve to the “ON” position. Refer to
lightinginstructions andrelightthe appliance. With
burners on, check for any gas leakage around the
orifices.
5) Withmainburnersoperating,checkburnermanifold
pressure and insure that proper gas pressure is supplied
to the burner system (refer to Table 2 for pressure
settings). Adjustifnecessary.
6) Finally, apply the gas type conversion label, pro-
vided with the conversion kit, just below the fryer data
plate on the fryer door inside panel.
G20 G31
MG2 #46 #55
MG2S #46 #55
NAT LP
MG2 #46 #55
MG2S #46 #55
NAT LP
MG2 4.0 10.0
MG2S 4.0 10.0
Model Gas Type
Model Gas Type Model Gas Pressure
(in W.C.)
Model Gas Pressure
(mbar)
G20 G31
MG2 10 25.4
MG2S 10 25.4
Table 1 Orifice Tips Table 2 Burner Pressure
CE COUNTRIES CE COUNTRIES
NON-CE COUNTRIES NON-CE COUNTRIES
Applicable
Country(s) GB, IE
GB-GreatBritan,IE-Ireland
Appliance
Model
Number
Nat G20 I
2H
21.1 20 10 #46 N22 YES 2.2
LP G31 I
3P
21.5 50/37 25.4 #55 LP16 YES 0.9
Nat G20 I
2H
21.1 20 10 #46 N22 YES 2.2
LP G31 I
3P
21.5 50/37 25.4 #55 LP16 YES 0.9
Nom rate (m
3
/hr)
Gas
Burner Pressure (mbar)
Burner Orifice
Pilot Orifice (code)
Governor
Appliance Category
Input (Gross) kW
Input (Net) kW
Supply Pressure (mbar)
MGII 23.4
MGIIT 23.4

L22-236 Rev 0 (04/03) 8
Fryer Trouble Shooting
PROBLEM POSSIBLE CAUSE ACTION
C ontro ller will N O T turn O N
Disp lay do es N O T light
A. No power to the machine
B. F1 Fuse blown
C. T1 Transformer
A. Check building circuit breaker, verify
power cord is plugged in
B. Check F1 Fuse. Replace if defective
C. Check voltage in and out of T1
Controller indicates "IGNITION
FAILURE" or "HEAT FAIL" and
machine does NOT heat.
A. Hi limit tripped
B. Heat demand relay
C. Relay board
A. Once the oil temp has gone below
400°F + 20°, the Hi- limit sho uld reset
auto matically, if not, re place Hi- limit
B. Check & replace if defective
C. Check & replace if defective
Machine is heating slowly A. Gas vavle not turned fully to the on
position
B. Gas shut-off (yellow handle) not fully
open
C. Quick disconnect not connected
properly
D. Low gas pressure
A. Verify that the gas valve is in the on
position
B. Ve rify that the ye llow handle is fully
open (inline with the gas line)
C. Verify that quick disconnect is properly
connected
D. Call a qualified gas technicain
Oil is hotter or colder than computer
/co ntroller displa ys
A. Temperature calibration
B. Probe
C. Probe wiring terminals
A. Adjust temperature offset up to +10°F
B. Check & replace if defective
C. Clean or repair terminals
C ontro ller will no t turn on o r displays
"DRAINING" or "TURN OFF"
A. Blue drain valve not fully closed
B. Sensor switch
C . Inco rr ect switch gap/a lignment
A. Check position of handle
B. Switch may be loose or have loose
wires, replace if defective
C. Check gap/alignment, replace if defective
Controller heat demand lights are lit,
machine does not heat. HD & SO
lights on relay board are lit.
A. K1 relay (relay board)
B. Gas valve
C. Ignition module
A. Check & replace if defective
B. Check & replace if defective
C. Check & replace if defective
Computer displays "PROBE
FAILURE"
A. Shorted probe
B. Open probe
C. Probe wiring terminals
A. Check probe & replace if defective
B. Check probe & replace if defective
C. Clean or repair terminals

9L22-236 Rev 0 (04/03)
Filter Trouble Shooting
PROBLEM POSSIBLE CAUSE ACTION
Red return handle is pulled out, but no
pump sound can be heard
A. Red return handle not completly
open
B. Filter circuit breaker may be tripped
or in the off position
C . F ilter moto r thermal o verload may
be tripped
D. Sensor switch may be loose or
defective
E. Power cord unplugged or loose
A. Pull on red return handle to make sure
valve is completly open
B. Reset the circuit breaker or press it to
the on position
C. Push the red reset button on the end of
the motor
D. Check that the switch is tight and that it
has the correct gap. Replace if defective
E. Check the power cord at the fryer
entrance box and at the pump box and
make sure that the power cords are plugged
in and /or pushed in all the way
Drain valve is closed, computer has
been reset, but computer still displays
"DRAIN ING"
A. Blue drain valve not fully closed
B. Sensor switch
C. Incorrect switch gap/alignment
A. Check position of handle
B. Switch may be loose or have loose
wires, replace if defective
C. Check gap/alignment, replace if defective
Oil is returning to the vat slowly or not
at all
A. Dirty filter paper
B. Strainer cap dirty
C. Filter pan not pushed in completely
D. O-rings not sealing on pick up tube
A. Change filter paper
B. Remove strainer cap and clean it
C. P ush filter pan in
D. Check & replace if defective
Air bubbles are in the oil being returned
to the vat
A. Strainer cap not tight
B. Stainer cap not in pick up tube
C. Filter pan not pushed in completely
D. O-rings not sealing on pick up tube
A. Tighten strainer cap
B. Install strainer cap
C. P ush filter pan in
D. Check & replace if defective
Drain valve is open, the oil is draining
slowly or not at all
A. Drain valve is not fully open
B. Drain line is plugged with debris
A. Apply a little more pressure to the drain
valve handle to check that the drain valve is
fully open
B. Use the clean out rod to clear the drain
valve opening. If this does not clear the
blockage, close the drain valve, and call for
service

L22-236 Rev 0 (04/03) 10
10 1
61
12 1
PITCO# 60127301A
DATE: MMDDYY
A.C.
H.D. S.O.
F1 FUSE
15
71
K1
HEAT
DEM ON
SIDE
K3
J32
J34
J35
J31
J33
Fuse:
F1 -
Trouble Shooting Lights:
A
.C. -
S.O. -
H.D. -
Relays:
K1 -
K3 -
Connectors:
J31 -
J32 -
J33 -
J34 -
J35 -
If fuse is blown, A.C. will not be lit.
When lit, F1 Fuse and T1 Transformer are good.
When lit, A1 Computer is on and K10 Contactor should be energized.
When lit, A1 Computer is on and calling for heat, K11 Contactor should be energized
Heat Demand Relay, will be energized when A1 Computer calls for heat and when H.D. is lit.
Side On Relay, will be energized when A1 Computer is on and A.C. is lit.
Connects to A1 Computer
To Side On and Heat Demand Contactors and Heat Feed Back.
To 24VAC jumper harness.
To Drain Switch and optional Basketlifts
Input voltage from transformer
Relay Board:
Note:
Note: If the fryer is equipped with a
computer or solid state digital, at
connection J33 there will be a
jumper from pin #2 to pin #10 to
supply 24 VAC to pin # 2 at
connection J31 to supply the
controller with 24VAC.
J connectors are marked on the
relay board.
•With 24 VAC supplied to pin #2 at
connector J35 and a good F1 fuse, the
relay board will have a 24 VAC output
at pin #2 on connectors J33 and J34
and the A.C. indicator will be
illuminated.
•When the board receives a 24 VDC
side on input at pin #7 on connectors
J31 or J33, the S.O. indicator will
illuminate, the side on relay (S.O.) will
energize and there will be a 24 VAC
output at pin #4 on connector J32.
•When the board receives a 24 VDC
heat demand input at pin #6 on
connectors J31 or J33, the H.D.
indicator will illuminate, the heat
demand relay (H.D.) will energize and
there should continuity between pin #1
and pin #2 at connector J32.
Relay Board Component Explanation

11 L22-236 Rev 0 (04/03)
OR FLOAT
TO DRAIN
SWITCH
2
1
5
6
3
4
LIFT OPTION
TO BASKET
J34
1
AC POWER
6
4
5
3
HEAT DEM
K1
2
1
K3
SIDE ON
4
24VAC
F1
3
21
24VCOM
5
TRANSFORMER
24VA
C
FR
O
M A
C
LA
S
S
2
2
3
7
5
4
8
9
6
12
10
11
HEAT FEED BACK
TO RESET SWITCH IF REQUIRED
24VAC RETURN
TO HIGH LIMIT
BACK-UP
HEAT DEMAND ENABLE
HEAT DEMAND
TO
DRAIN OR
FLOAT SWITCH
24VACH
1
3
NONE
BASKET LIFT R
BASKET LIFT L
SIDE ON (DC)
HEAT DEMAND
24VDC RETURN
24VAC RETURN
HEAT FEEDBACK
6
2
4
5
7
8
10
9
TEMPERATURE
TO
PRIMARY
COOKING
CONTROLLER
FUSE
SIDE ON
K3
K1
HEAT
DEMAND
HEAT FEED BACK
24VACH POWER
24VACN RETURN
DRAIN OR FLOAT SWITCH
24VAC POWER SWITCHED
HEAT DEMAND
NONE
NONE
SIDE ON
DC RETURN
NONE
NONE
7
DC COMMON
BASKET LIFT LEFT
BASKET LIFT RIGHT
(DC)(DC)
CONTROL (OPT
)
OR NO OPTION
JUMPER BLOCK
J31
J34
60127301
J35
J32
J34
J33
Relay Board

12
L22-236 Rev 0 (04/03)
Schematics

1
2
3
4
6
7
5
1
2
3
4
6
7
5
ABC
DE
FGH
I
J
13 L22-236 Rev 0 (04/03)
24 VAC +
DVI
INPUT
24 VDC
COMMON
PROBE
INPUT
ON/OFF
(SIDE ON)
OUTPUT
HEAT DEMAND
OUTPUT
HEAT
FEEDBACK
INPUT
24 VAC
INPUT
24 VAC
COMMON
TRANSFORMER
DRAIN
SWITCH
HI LIMIT
SWITCH
NC
GAS VALVE
MAIN VALVE
OPERATOR
PILOT VALVE
OPERATOR
IGNITOR
IGNITION MODULE
MV OUT
PV OUT
SPARK FLAME
SENSE
RELAY BOARD
SIDE ON
F1 FUSE
SO
HEAT
DEMAND
HD
AC
24 VA
C
COMMON
24 VAC JUMPER
AT J3 3
J33, PIN
2 AND 10
24 VAC +
24 VAC COMMON

14
L22-236 Rev 0 (04/03)
LEFT SIDEI/O TYPE RIGHT SIDE
DRAIN VALVE(DVI)
24VACH
24VAC COM
(FRAME GND)
DC RETURN
HEAT FEED BACK
NONE
SIDE ON
NONE
NONE
HEAT DEMAND
PROBE -
PROBE +
AC POWER
24VAC INPUT
24VAC INPUT
24VDC COM
24VDC OUT
24VDC OUT
TEMPERATURE
NONE
NONE
PROBE +
PROBE -
DRAIN VALVE(DVI)
HEAT FEED BACK
DC RETURN
HEAT DEMAND
NONE
NONE
SIDE ON
NONE
TABLE 2: (A1) McDONALDS CONTROLLER CONNECTIONS
PIN#
5
10
11
12
9
8
7
6
4
3
2
1
FRYER REPLACEMENT PARTS
REF DESCRIPTION PART NO.
SWITCH, HIGH LIMIT
XFMR, 120-208-240/24VAC 80VA CLASS 2
PROBE, NTC THERMISTOR GAS
IGNITION MODULE
COMPUTER COOKING CNTRL SINGLE/DUAL McDS
IGNITION MODULE
SWITCH ACTUATOR MAGNETIC
SWITCH PROXIMITY MAGNETIC
EI PILOT AND HOOD ASSEMBLY PROPANE
EI PILOT AND HOOD ASSEMBLY NATURAL
FUSE 1.5A 250V TIME DELAY CERAMIC
VALVE, GAS FAST OPEN 24VAC PROPANE
VALVE, GAS FAST OPEN 24VAC PROPANE UNREG
VALVE, GAS FAST OPEN 24VAC PROPANE
VALVE, GAS FAST OPEN 24VAC NATURAL
VALVE, GAS FAST OPEN 24VAC NATURAL
V1 (DOMESTIC)
V1 (CE & EXPORT)
F1
E2
RT1,2
T1
LS1 (TYPICAL)
HL1
A1
60113501
60113502
60113505
60113504
60113503
PP10263
60130901
60130902
60132702
PP10429
PP10084
PP10262
60025301
60137701
60132501
60108601
A2 (DOMESTIC)
A2 (CE EXPORT)
CORD BOX DOMESTIC WITH NEMA L21-20P PLUG MDG B1824301
A11 CORD BOX EXPORT CE W/IEC1302 PLUG MDG B1824302
CORD BOX EXPORT NO PLUG B1824303
A4 CNTRL, RELAY BOARD 24V CLASS 2 60127301
K6 RELAY SPST-NO 30A/250VAC, 24VDC COIL 60137301
CORD BOX DOMESTIC NO HOOD CNTRL 115V MDG B1824304
LOCATION
SHEET 2, J7
SHEET 2, C6
SHEET 2, C6
SHEET 2, G4
SHEET 2, E6
SHEET 2, F2
SHEET 2, G7
SHEET 2, I4
SHEET 2, I4
SHEET 2, B6
SHEET 2, B6
SHEET 2, D4
SHEET 2, A6
SHEET 2, A6
SHEET 2, A6
SHEET 2, A6
SHEET 2, A6
SHEET 6, D3
SHEET 6
SHEET 6
SHEET 6
SHEET 6
SCHEMATIC 700334, SHEET 1

1
2
3
4
6
7
5
1
2
3
4
6
7
5
ABC
DE
FGH
I
J
15 L22-236 Rev 0 (04/03)
RELAY BOARD
TEMPERATURE CONTROL (LEFT SIDE CONNECTIONS)
A1
A4
ENTRANCE BOX
A2
MATCHLESS
VALVE
GAS
V1
IGNITION
CONTROL ENCLOSURE
A10
24VAC
AC POWER
TEMP
PROBE
L
N
BLU
2
BLU
RED
6
VIOL
HEAT DEM
WIRE HARNESS B6750801 LEFT
NONE
2
1
J/P41
4
PROBE-
PROBE+ 3
BLK
10
12
SIDE ON
8
9
11
NONE
YEL
VIOL/W
BLK
J/P31
1
2
J/P7
RT1
9
10
8
7
D4
240 V
208 V
120 V
SELECT SW1
AC VOLTAGE
DRAIN VALVE
TO NEXT
L N
GND
16 AWG
SJTO
G
N
C
B
A
N
L
G
L
J13
W
B
G
FRAME
2
6
HFB
DC COM 7
24VACH
24VAC
1
ORG
RED
WHT
BLU/W
J/P1
INPUT 5BRN
HFB
4
5
3
2
K1
K3
1
(60127301)
WHT
BRN
3
5
FRAME
T1
80VA
10
WHT
J/P35
1.5 A TD
F1
1
FUSE
23
1WHT
NOT USED
1
GND
GRN-16
WHT-16
BLK-16
BLK-16
WHT-16
GRN-16
1
BLK
5
3
AB C
2
SW1
84 6
J11
L N G
J12
VIOL/W
71
ORG
2
24 VAC
6
W/BRN
3
2
NOT USED
RED
CONTROL
VIOL/W
3
6
P8
21
W/BRN
RED/W
J/P10
4
5
FROM J34
HOOD
J/P33
1
3
CONTROL
TO P10 HOOD
W/BRN
VIOL/W
RED/W
67 435
J/P34
AC 5
6HFB
HEAT FEED BACK
ORG
WHT
P/J5
2
HL1
BLU
BLK9
P/J2
7
8
BLU GRN/Y
24VG
SPARK
GND
PV
E2
IGNITOR
1
5
PILOT
GY
HIGH LIMIT
24VAC
K3
SIDE ON
4
3
HEAT DEM
K1
2
1
J/P32
YEL/W
YEL
1
BRN/W
3
4
YEL
2
BRN
RED
7
24VAC COM
5
4
3
2
5
4
6
1
10
UL 1213 AWM TEFLON
RED
W/BLK
MV/PV
24VAC
MV
6
P/J2
MAIN
2
3
GAS
VALVE
P17
B6747001
BLK/W
2
P43
1
J/P4
1
2
J/P34
1
2
BRN
BLU
FRYPOT
NOTE 6
DRAIN
OR FLOAT
SWITCH
LS1 24VAC
AC COM
AC COM
AC
COM
COM
TO CORD AND
HOOD RELAY
BOX PG 3
D5
OR FROM PREVIOUS
SHEET 4
FROM J101
B
6
7
50
7
0
1 RI
G
HT
COM
ENTRANCE BOX
AT LEFT
NOTE 6
*
*
*
LEFT CONNECTION ONLY
SCHEMATIC 700334, SHEET 2

16
L22-236 Rev 0 (04/03)
FILTER PUMP REPLACEMENT PARTS
DESCRIPTION
ITEM VOLTAGE PART NO.
MOTOR AND PUMP 1/3HP 5GPM
MOTOR AND PUMP 1/3HP 5GPM
MOTOR AND PUMP 1/3HP 5GPM
CKT BRKR, 5 AMP TWO POLE
XFMR, 120/24VAC 5VA
XFMR, 240/24 VAC 5VA
CKT BRKR,10 AMP SINGLE POLE
RELAY, 24VAC, 30A DPST
FILTER, PUMP BOX ASSEMBLY
RELAY, 24VAC, 30A SPST
FUSE HOLDER, IN LINE, .25 X 1.25
FUSE 0.2A 250V TIME DELAY CERAMIC
A5
120V-50/60Hz
240V-50Hz
230V-50/60Hz
CB1
K5
F2
FH2
T3
M1
230V-50/60Hz
120V-50/60Hz
240V-50Hz
230V-50/60Hz
ALL
240V/50Hz
240V-50Hz
230V-50/60Hz
120V-50/60Hz
240V/50Hz
120V-50/60Hz
230V-50/60Hz
120V-50/60Hz
208V-50/60Hz
B6673002
B6673001
60130810
60130806
60077901
60130807
60130301
60130302
60078502
60104701
PP10765
60132701
PP11058
SHORTENING HEATER OPTIONS REPLACEMENT PARTS
ITEM VOLTAGE DESCRIPTION PART NO.
120-50/60Hz HEATER TAPE 1/2X 72", 50W
HEATER TAPE 1/2X 33", 25W
HEATER TAPE 1/2X 33", 25W
HEATER TAPE 1/2X 72", 50W
240/50Hz
120-50/60Hz
240/50Hz
230-50/60Hz
230-50/60Hz
HTR2,3
HTR1
60133501
60133502
60133503
60133504
LOCATION
SHEET 4, E6
SHEET 4, E4
SHEET 4, J4
SHEET 4, J6
SHEET 4, C3
SHEET 4, H3
SHEET 4, C3
SHEET 4, H3
SHEET 4, B4
SHEET 4, G4
SHEET 4, G2
SHEET 4, G2
SHEET 4, D4
SHEET 4, H2
SCHEMATIC 700334, SHEET 3

1
2
3
4
6
7
5
1
2
3
4
6
7
5
ABC
DE
FGH
I
J
17 L22-236 Rev 0 (04/03)
CB1
T3
LS4
M1 M1
K5
HTR3HTR2
HTR1
208, 220-230V/50-60HZ OR 240V/50HZ (EXPORT AND CE)
A5
PUMP BOX
WHT-16
WHT-16
BLK-16
BLK-16
P1
GRN-16
IF SHORTENING OPTION IS SUPPLIED.
*ADD .15 AMPS PER HEAT TAPE
230 VAC/ 50-60Hz / 3.6-4.2 FLA *
240 VAC/ 50HZ / 4.3 FLA *
16/3 AWG SJTO CORD
WHT-16
BLK-16
240V
FRAME
(RESET)
ON/OFF
BLK
ORG
0.2A TD
BLU
F2
BLU
5VA
21
J/P30 J/P31
12
VIOLWHT
21
J/P22
AS SHOWN.
VALVE OPEN
OR FLUSH HOSE.
TYPICAL
RETURN VALVE
VALVE
TO NEXT
VIOL
WHT
21
J20
VIOL
WHT
G
T5
GRN-16
G
T5
T2
T3
T4T8 P2
P1
WHT-16
BLK-16
T4T8
PUMP MOTOR
230V 50/60HZ
PUMP MOTOR
240V 50HZ
RUN
N02
C2
N01
C1
W/BRN
YEL
240V/ 25W
FLUSH HOSE 2
HEATER OPTION
240V/ 25W
FLUSH HOSE 1
HEATER OPTION
P18
3
2
1
3
1
2
P19
J18
213 213 1
J18 J19
23
P51
1
3
2
LINE
PUMP RETURN
240V/ 50W
B6748001
12
P52
B6748103
B6748102
B6748101
3 1
P52
SHORTENING HEATER OPTIONS
B6748104
23
1
2
3
J52
1
2
3
J51
WHT-18
BLK-18
L
L GN NG
J71
L
GND
SJTO
16 AWG
N
NL
GND
16 AWG
SJTO
J72
T1
24V
P102
A11
FROM
CORD BOX
M1
LS4
CB1
T3 K5
115V/60HZ (DOMESTIC)
HTR3HTR2
HTR1
A5 PUMP BOX
*ADD .3 AMPS PER HEAT TAPE
115VAC 50-60 Hz/7.3 FLA*
IS SUPPLIED.
IF SHORTENING OPTION
16/3 AWG SJTO CORD
GRN-16
G
T5
115V 50/60HZ
P1
WHT-16
BLK-16
P2
T3
T4T8 T2
PUMP MOTOR
FRAME
WHT
WHT
115V
RUN
SHORTENING HEATER OPTIONS
WHT-18
WHT-16
BLK-16
BLK-16
BLK
ON/OFF
(RESET) BLK-18
N01
C1
5VA
1
J/P30
BLU
212
W/BRN
YEL
J/P31
VIOL AS SHOWN.
VALVE OPEN
OR FLUSH HOSE.
RETURN VALVE
TYPICAL
VALVE
TO NEXT
21
VIOL
WHT
VIOL
WHT
115V/ 2 5W
HEATER OPTION
FLUSH HOSE 2
P19
2
1
3
1
2
3
P18
115V/ 2 5W
HEATER OPTION
FLUSH HOSE 1
3
2
1
J52
J51
3
2
1
2
3
1115V/ 5 0W
PUMP RETURN
LINE
P51
1
B6748101
B6748102
B6748103
B6748104
P52 P52
321 321
B6748001
23
J18
213
J19 J18
123
J/P22
12
G
GL NLN
16 AWG
SJTO
N
J71
GND
L
SJTO
16 AWG
J72
L N
GND
J20
24V
P102
CORD BOX
FROM
A11
M1
T4T8
WHT-16
BLK-16
GRN-16
G
T1
T2
T3
T5
PUMP MOTOR
208V 50-60HZ
SCHEMATIC 700334, SHEET 4

18
L22-236 Rev 0 (04/03)
FRYER REPLACEMENT PARTS
REF DESCRIPTION PART NO.
SWITCH, HIGH LIMIT
XFMR, 120-208-240/24VAC 80VA CLASS 2
PROBE, NTC THERMISTOR GAS
IGNITION MODULE
COMPUTER COOKING CNTRL SINGLE/DUAL McDS
IGNITION MODULE
SWITCH ACTUATOR MAGNETIC
SWITCH PROXIMITY MAGNETIC
EI PILOT AND HOOD ASSEMBLY PROPANE
EI PILOT AND HOOD ASSEMBLY NATURAL
FUSE 1.5A 250V TIME DELAY CERAMIC
VALVE, GAS FAST OPEN 24VAC PROPANE
VALVE, GAS FAST OPEN 24VAC PROPANE UNREG
VALVE, GAS FAST OPEN 24VAC PROPANE
VALVE, GAS FAST OPEN 24VAC NATURAL
VALVE, GAS FAST OPEN 24VAC NATURAL
V1 (DOMESTIC)
V1 (CE & EXPORT)
F1
E2
RT1,2
T1
LS1 (TYPICAL)
HL1
A1
60113501
60113502
60113505
60113504
60113503
PP10263
60130901
60130902
60132702
PP10429
PP10084
PP10262
60025301
60137701
60132501
60108601
A2 (DOMESTIC)
A2 (CE EXPORT)
CORD BOX DOMESTIC WITH NEMA L21-20P PLUG MDG B1824301
A11 CORD BOX EXPORT CE W/IEC1302 PLUG MDG B1824302
CORD BOX EXPORT NO PLUG B1824303
A4 CNTRL, RELAY BOARD 24V CLASS 2 60127301
K6 RELAY SPST-NO 30A/250VAC, 24VDC COIL 60137301
CORD BOX DOMESTIC NO HOOD CNTRL 115V MDG B1824304
LOCATION
SHEET 2, J7
SHEET 2, C6
SHEET 2, C6
SHEET 2, G4
SHEET 2, E6
SHEET 2, F2
SHEET 2, G7
SHEET 2, I4
SHEET 2, I4
SHEET 2, B6
SHEET 2, B6
SHEET 2, D4
SHEET 2, A6
SHEET 2, A6
SHEET 2, A6
SHEET 2, A6
SHEET 2, A6
SHEET 6, D3
SHEET 6
SHEET 6
SHEET 6
SHEET 6
SCHEMATIC 700334, SHEET
5

1
2
3
4
6
7
5
1
2
3
4
6
7
5
ABC
DE
FGH
I
J
19 L22-236 Rev 0 (04/03)
K6
CORD AND HOOD RELAY BOX
14T TYPICAL TYPICAL
14, 14R, 18
CORD BOX EXPORT
CORD BOX EXPORT
A11A11
120V
A10A10A10
240V
CORD BOX NO HOOD CONTROL
A11
CORD BOX DOMESTIC
DOMESTIC ONLY
DOMESTIC ONLY
CORD BOX WITH HOOD CONTROL
NO HOOD CONTROL
RIGHT
J12
INSTALLEDPWITH
HOODPOPTION ONLY
J103
J103
13
VIOL
RED
VIOL
RED
N01
C1
YEL
HOOD
P103
W/BRN
2
321
TO NEXT
ENTRANCE BOX
OR
J103
P12
321
TO NEXT
ENTRANCE
231
INSTALLEDPWITH
HOOD POPTIO N ONLY
RED
VIOL
RED
VIOL
321
P103
213
P12
LEFT
J12
P12L
213
J12
LEFT
CORD BOX
12 3
IN FAR
LEFT CABINET
P104
GW Z XY
GRN WHT ORG RED BLK
TO HOOD MOTOR
CONTROL CKT.
20A/208 VAC MAX
GNEUT L
120VAC/15A
CORDSETP#6013
7201
CUSTOMER SUPPLIED EQUIPMENT
NEMA L21-20P120/208
VAC P 3P H AS E
GND NEUT L 1 L2 LOAD
J102
L
BLK-14
WHT-14
GRN-14
SEE SHEET 2
TO PUMP BOX N
G
BLK-12
RED-12
ORG-12
WHT-12
GRN-12
L
J101
G
N
230VAC/1PH/10A MIN SERVICE
J103
P104
TO PUMP BOX
SEE SHEET 2
J101
CORDSETP#6013
7401
L
G/Y-14
BRN-14
BLU-14
N
G
G
WHT-14
G/Y-14
L
N
BLK-14
12 3
NOT USED
RELAY
J102
CORDSETP#60137
402
PLUG
SUPPLIED
BY OTHERS
EXPORTPC
E
EXPORTPNO
N CE
B1824302 OR B1824303
B1824301
B67450901 (2X)
B67450901 SIN GLE
ALL A10 LOCATIONS
SWITCH SET FOR
VOLTAGE SELECTOR
120V POSITION AT
240V POSITION AT
VOLTAGE SELECTOR
SWITCH SET FOR
ALL A 10 L OCATION S
115VAC/1PH/50-60Hz/15A MIN SERVICE
PLUG
NEMA 5-15P
TO PUMP BOX
SEE SHEET 2
J102
GRN-14
BLU-14
BRN-14
L
N
G
G
WHT-14
GRN-14
L
N
BLK-14
J101
J103
NOT USED
12 3
B1824304
BOX
12 3
12 3
L- BRN
N- BLUE
G- G/Y
MG2 AND ME2
TO FIRST FRYER
ENTRANCE BOX
TO FIRST FRYER
ENTRANCE BOX
MG2 AND ME2
TO FIRST FRYER
ENTRANCE BOX
MG2 AND ME2
SCHEMATIC 700334, SHEET 6

20
L22-236 Rev 0 (04/03)
Exploded Drawings and Parts Lists
Other manuals for MGII
1
This manual suits for next models
2
Table of contents
Other Pitco Fryer manuals

Pitco
Pitco SSHLV184 Series User manual

Pitco
Pitco SG18S User manual

Pitco
Pitco SELV14 User manual

Pitco
Pitco Frialator SG 18 User manual

Pitco
Pitco 14 User manual

Pitco
Pitco SGH50 User manual

Pitco
Pitco W14S-S WF User manual

Pitco
Pitco SELV Series User manual

Pitco
Pitco 24RUFM User manual

Pitco
Pitco MG14S-C/MFD User manual
Popular Fryer manuals by other brands

Lincat
Lincat Silverlink 600 User, installation and servicing instructions

Living & Co
Living & Co JBQ-088 instruction manual

Chefman
Chefman RJ38-V2-35 user manual

Chefman
Chefman RJ07-M-SS user manual

ROBERT IRVINE
ROBERT IRVINE K54474 user guide

Outdoor Gourmet
Outdoor Gourmet FSOGBG4302 Assembly instructions & user manual