Pixsys PLE500-6AD User manual

PLE500-6AD
PL500 expansion module
Modulo espansione per PL500
User manual / Manuale d’uso


User manual - PLE500 - 3
Table of contents
1 Safety guidelines............................................................................................................................................................. 4
1.1 Organization of safety notices.................................................................................................................. 4
1.2 Safety Precautions ....................................................................................................................................... 4
1.3 Precautions for safe use.............................................................................................................................. 5
1.4 Environmental policy / WEEE .................................................................................................................... 5
2 Model identification ....................................................................................................................................................... 5
3 Model identification ....................................................................................................................................................... 6
4 Technical data.................................................................................................................................................................. 6
4.1 General characteristics ............................................................................................................................... 6
4.2 Hardware characteristics ........................................................................................................................... 6
5 Dimension and installation.......................................................................................................................................... 7
5.1 Mounting sequence of the PL500 and of the PLE500 expansion modules..................................... 7
6 Electric connections ....................................................................................................................................................... 8
6.1 Wiring diagram............................................................................................................................................. 8
6.1.a PLE module power supply............................................................................................................... 9
6.1.b Power supply of digital outputs..................................................................................................... 9
6.1.c Analog inputs AI.0 and AI.1 ............................................................................................................ 9
6.1.d Examples of connection for Volt and mA inputs....................................................................... 9
6.1.e Analog outputs AQ.0 and AQ.1...................................................................................................... 9
6.1.f Digital inputs...................................................................................................................................... 9
6.1.g Digital outputs................................................................................................................................. 10
6.1.h Example of incremental encoder connection.......................................................................... 10
6.1.i Example of mono-directional counter connection................................................................ 10
6.2 Meaning of status lights (LED) ................................................................................................................ 10
7 Configuration parameter table................................................................................................................................. 10
8 Command and operation variable table................................................................................................................ 12
Indice degli argomenti
1 Norme di sicurezza ....................................................................................................................................................... 17
1.1 Organizzazione delle note di sicurezza................................................................................................ 17
1.2 Note di sicurezza......................................................................................................................................... 17
1.3 Precauzioni per l’uso sicuro ..................................................................................................................... 18
1.4 Tutela ambientale e smaltimento dei rifiuti / Direttiva WEEE ......................................................... 18
2 Identificazione del modello........................................................................................................................................ 19
3 Dati tecnici...................................................................................................................................................................... 19
3.1 Caratteristiche generali ............................................................................................................................ 19
3.2 Caratteristiche hardware ......................................................................................................................... 19
4 Dimensioni ed installazione.......................................................................................................................................20
4.1 Sequenza di montaggio del PL500 e dei moduli di espansione PLE500.......................................20
5 Collegamenti elettrici................................................................................................................................................... 21
5.1 Schema di collegamento.......................................................................................................................... 21
5.1.a Alimentazione modulo PLE ..........................................................................................................22
5.1.c Alimentazione uscite digitali........................................................................................................22
5.1.d Ingressi analogici AI.0 e AI.1 .........................................................................................................22
5.1.e Esempi di collegamento per ingressi Volt e mA.......................................................................22
5.1.f Uscite analogiche AQ.0 e AQ.1.....................................................................................................22
5.1.g Ingressi digitali.................................................................................................................................22
5.1.h Uscite digitali....................................................................................................................................23
5.1.i Esempio di collegamento encoder incrementale....................................................................23
5.1.j Esempio di collegamento contatore monodirezionale.........................................................23
5.2 Significato delle spie di stato (led)..........................................................................................................23
6 Tabella parametri di configurazione........................................................................................................................23
7 Tabella variabili di funzionamento e comando....................................................................................................25

4 - PLE500 - User manual
Introduction
Thank you for choosing a Pixsys I/O module.
PLE500-6AD is an expansion device for the PL500 model plc. It integrates digital inputs/outputs,
analog inputs for normalized signals and analog current outputs in a single device. Communication
with the PL500 is via bus on DIN rail, considerably simplifying wiring and the commissioning phase.
1 Safety guidelines
Read carefully the safety guidelines and programming instructions contained in this manual before
connecting/using the device.
Disconnect power supply before proceeding to hardware settings or electrical wirings to avoid risk of
electric shock, fire, malfunction.
Do not install/operate the device in environments with flammable/explosive gases.
This device has been designed and conceived for industrial environments and applications that rely
on proper safety conditions in accordance with national and international regulations on labour
and personal safety. Any application that might lead to serious physical dama ge/ life risk or involve
medical life support devices should be avoided.
Device is not conceived for applications related to nuclear power plants, weapon systems, flight
control, mass transportation systems.
Only qualified personnel should be allowed to use device and/or service it and only in accordance to
technical data listed in this manual.
Do not dismantle/modify/repair any internal component.
Device must be installed and can operate only within the allowed environmental conditions.
Overheating may lead to risk of fire and can shorten the lifecycle of electronic components.
1.1 Organization of safety notices
Safety notices in this manual are organized as follows:
Safety notice Description
Danger! Disregarding these safety guidelines and notices can be life-threatening.
Warning! Disregarding these safety guidelines and notices can result in severe injury or
substantial damage to property.
Information! This information is important for preventing errors.
1.2 Safety Precautions
Danger!
CAUTION - Risk of Fire and Electric Shock
This product is UL listed as Open Type Process Control Equipment. It must be
mounted in an enclosure that does not allow fire to escape externally.
Danger!
If the output relays are used past their life expectancy, contact fusing or burning may
occasionally occur.
Always consider the application conditions and use the output relays within their
rated load and electrical life expectancy. The life expectancy of output relays varies
considerably with the output load and switching conditions.
Warning!
Devices shall be supplied with limited energy according to UL 61010-1 3rd Ed, section
9.4 or LPS in conformance with UL 60950-1 or SELV in conformance with UL 60950-1
or Class 2 in compliance with UL 1310 or UL 1585.
Warning! Loose screws may occasionally result in fire.
For screw terminals, tighten screws to tightening torque is 0.22 Nm
Warning!
A malfunction in the Digital Controller may occasionally make control operations
impossible or prevent alarm outputs, resulting in property damage. To maintain
safety in the event of malfunction of the Digital Controller, take appropriate safety
measures, such as installing a monitoring device on a separate line.

User manual - PLE500 - 5
1.3 Precautions for safe use
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse
affects on the performance and functions of the product. Not doing so may occasionally result in
unexpected events. Do not handle the Digital Controller in ways that exceed the ratings.
• The product is designed for indoor use only. Do not use or store the product outdoors or in any of
the following places.
- Places directly subject to heat radiated from heating equipment.
- Places subject to splashing liquid or oil atmosphere.
- Places subject to direct sunlight.
- Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
- Places subject to intense temperature change.
- Places subject to icing and condensation.
- Places subject to vibration and large shocks.
• Installing two or more controllers in close proximity might lead to increased internal temperature
and this might shorten the life cycle of electronic components. It is strongly recommended to
install cooling fans or other air-conditioning devices inside the control cabinet.
• Always check the terminal names and polarity and be sure to wire properly. Do not wire the
terminals that are not used.
• To avoid inductive noise, keep the controller wiring away from power cables that carry high voltages
or large currents. Also, do not wire power lines together with or parallel to Digital Controller
wiring. Using shielded cables and using separate conduits or ducts is recommended. Attach a
surge suppressor or noise filter to peripheral devices that generate noise (in particular motors,
transformers, solenoids, magnetic coils or other equipment that have an inductance component).
When a noise filter is used at the power supply, first check the voltage or current, and attach the
noise filter as close as possible to the Digital Controller. Allow as much space as possible between
the Digital Controller and devices that generate powerful high frequencies (high-frequency
welders, high-frequency sewing machines, etc.) or surge.
• A switch or circuit breaker must be provided close to device. The switch or circuit breaker must be
within easy reach of the operator, and must be marked as a disconnecting means for the controller.
• Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine,
alcohol, or any cleaners that contain these or other organic solvents. Deformation or discoloration
may occur.
• The number of non-volatile memory write operations is limited. Therefore, use EEprom write mode
when frequently overwriting data, e.g.: through communications.
1.4 Environmental policy / WEEE
Do not dispose electric tools together with household waste material.
According to European Directive 2012/19/EU on waste electrical and electronic equipment and its
implementation in accordance with national law, electric tools that have reached the end of their life
must be collected separately and returned to an environmentally compatible recycling facility.

6 - PLE500 - User manual
2 Model identification
PLE500-6AD
Power supply 12..24 VDC ±15%
16 digital I/O
2 analog inputs
2 analog outputs
3 Technical data
3.1 General characteristics
Operating conditions Temperature: 0-45°C; humidity 35..95 RH% without condensation
Container DIN43880, 54 x 90 x 64 mm
Materials Container: PC UL94V0 self-extinguishing
Front panel: PC UL94V0 self-extinguishing
Protection IP20 (container and terminals)
Weight Approximately 130 g
3.2 Hardware characteristics
Module power supply 12..24 VDC provided by PLE DIN Bus
Digital output power
supply 12..24 VDC ±15% Max. consumption 100 W
Analog inputs
2: AI.0..1 Configurable via software.
V/I input:
0-10V, 0-20 mA, 4-20 mA.
Tolerance (25 °C)
+/-0.3% ±1 digit (on F.s.).
Impedance:
0-10 V: Ri>110 kΩ
0-20 mA: Ri<50 Ω
4-20 mA: Ri<50 Ω
Resolution:
45000 points.
Digital inputs / outputs
16: PNP 12..24 VDC inputs/ 12..24
VDC 700mA MAX static outputs per
output (max. 3 A in total)
Encoder / Counter inputs 4: inputs superimposed to the digital
inputs (max. 80KHz each)
Analog outputs 2: 4..20 mA or 0..20 mA.
Can be configured via software.
Resolution:
45000 points.

User manual - PLE500 - 7
4 Dimension and installation
64 mm
Attacco a guida DIN EN50022
Din rail mounting guide EN50022
PLE500-6AD
54 mm
90 mm
.4
.5
.6
.7
.3
.2
.1
.0
.4
.5
.6
.7
.3
.2
.1
.0
+0
+1
1 2 34567 8 9 10 12
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
13 14 15 16 17 18 19 20 21 22 23 24
AGND
(0V)
AI0
L+0
AI1
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
L+1
AQ.0
AQ.1
AGND
(0V)
4.1 Mounting sequence of the PL500 and of the PLE500
expansion modules
The PL500 with the relevant I/O modules requires mounting and connection via the specific bus
lodged in the hollow of the DIN rail. The I/O modules (series PLE500-xAD) will be automatically
numbered at each power-on, assigning the number 1 to the first I/O module connected to the right
of the PL500, the number 2 to the following one and so on, always moving towards the right side.
The position of the various modules shall thus reflect the sequence set in the LogicLab project in the
definition of the PLCEXP network. For the numbering procedure to work correctly, removing devices
from the network is not allowed by releasing them from their own bus and leaving some empty
modules (slot bus) between one module and the other. All the connection/disconnection operations
must be carried out with power off.
Clik!
Couple all the buses by pushing them towards the DIN
rail, making sure that the male connection faces left
and the female one faces right.
Couple the buses together by sliding them along the
DIN rail.
Insert the various modules in the slots of the buses
starting from the PL500 and continuing to the right
with the I/O modules.

8 - PLE500 - User manual
.4
.5
.6
.7
.3
.2
.1
.0
.4
.5
.6
.7
.3
.2
.1
.0
+0
+1
1 2 34567 8 9 10 12
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
13 14 15 16 17 18 19 20 21 22 23 24
AGND
(0V)
AI0
L+0
AI1
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
L+1
AQ.0
AQ.1
AGND
(0V)
10 11 12
1 2 3
10 11 12
1 2 3
Proceed with mounting all the modules according to
the requested order until the plc is completely formed.
.4
.5
.6
.7
.3
.2
.1
.0
.4
.5
.6
.7
.3
.2
.1
.0
+0
+1
1 2 34567 8 9 10 12
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
13 14 15 16 17 18 19 20 21 22 23 24
AGND
(0V)
AI0
L+0
AI1
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
L+1
AQ.0
AQ.1
AGND
(0V)
10 11 12
1 2 3
It is not possible to leave free slots in the bus between
one module and another.
5 Electric connections
This instrument was designed and built in compliance with the Low Voltage Directives 2006/95/
CE, 2014/35/EU (LVD) and Electromagnetic compatibility 2004/108/EC and 2014/30/EU (EMC). For
installation in industrial environments it is a good rule to follow the precautions below:
• Distinguish the power supply line from the power lines.
• Avoid the proximity with contactor units, electromagnetic contactors, high power motors and use
filters in any event.
• Avoid the proximity with power units, particularly if with phase control.
• The use of network filters is recommended on the power supply of the machine in which the
instrument will be installed, particular in case of 230 VAC power supply.
The instrument is devised to be assembled with other machines. Therefore, the EC marking of
the instrument does not exempt the manufacturer of the system from the safety and conformity
obligations imposed for the machine as a whole.
• Wiring of pins use crimped tube terminals or flexible/rigid copper wire with diameter 0.25 to 1.5
mm2 (min. AWG28, max. AWG16, operating temperature: min. 70°C). Cable stripping lenght 7 to 8
mm.
5.1 Wiring diagram
1 2 3456 7 8 9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
AGND
(0V)
AI0
L+0
AI1
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
L+1
AQ.0
AQ.1
AGND
(0V)
PLE500-6AD

User manual - PLE500 - 9
5.1.a PLE module power supply
12..24 VDC provided by PLE DIN Bus
5.1.b Power supply of digital outputs
Power supply of outputs 12..24 VDC ±15% – 100 VA.
On these clips connected the power supply positive of the digital outputs.
5.1.c Analog inputs AI.0 and AI.1
AI.0 AI.1
15
13
+
–
AI V
mA
Shield / Schermo
14
13
For normalized current and voltage signals.
• Respect the polarity.
When using a shielded cable, the shielding must be connected to
earth at one end only
5.1.d Examples of connection for Volt and mA inputs
PRESSURE TRANSMITTER /
SENSORE DI PRESSIONE
B
C
A
4...20mA
-
13
14
+
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33VDC
External supply /
Alimentazione esterna
AI.0
13
15
AI.1
For 0/4..20 mA normalized current examples with three wire sensor.
Respect the polarity:
C = Sensor output
B = Sensor mass
A = Power supply (12..24 VDC)
External supply /
Alimentazione esterna
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33V DC
PRESSURE TRANSMITTER /
SENSORE DI PRESSIONE
C
B
4...20mA
13
14
AI.0
13
15
AI.1 For 0/4..20 mA normalized current examples with external power
supply sensor.
Respect the polarity:
C = Sensor output
B = Sensor mass
P :0...100mbar
Pmax :3bar
T :0..70°C
OUT : 4...20mA
IN :9...33V DC
C
A
PRESSURE TRANSMITTER /
SENSORE DI PRESSIONE
4...20mA
External supply /
Alimentazione esterna
14
AI.0
15
AI.1
For 0/4..20 mA normalized current examples with two wire sensor.
Respect the polarity:
C = Sensor output
A = Power supply (12..24 VDC)
5.1.e Analog outputs AQ.0 and AQ.1
2
+
–
0/4..20mA
AQ.0
1
3
AQ.1
1
Analog outputs that can be configured according to the parameter as
4..20mA or 0..20mA outputs.
5.1.f Digital inputs
12..24 VDC QI.0 QI.7 QI.7QI.0
17 24 -.. 512..
PNP inputs (to activate the input, connect a positive signal to the
corresponding clip)
VIL = 4.3 V
VIL = 8.0 V

10 - PLE500 - User manual
5.1.g Digital outputs
QI.0 QI.7 QI.7QI.0
17 24 -.. 512.. 12..24 VDC ± 15% digital output (based on the power supply of the
outputs)/ 700mA (Max 3A in total)
5.1.h Example of incremental encoder connection
ENC2
7
ENC3
9
ENC4
11
A
B
Z
+
-
SUPPLY
ENC1
5
810 12
6
18 19 20
17
ENCODER
Use push-pull encoders
Max. frequency 80KHz
5.1.i Example of mono-directional counter connection
CNT2
7
CNT3
9
CNT4
11
+
-SUPPLY
CNT1
5PNP type input (VIH = 8.0 V).
Max. frequency 80KHz
5.2 Meaning of status lights (LED)
RUN
• Slow flashing of 40msec every 1.2sec: during the program start
phase.
• Fixed on: normal operation of the module with PLC in run.
• Fast 50 ms flashing: it indicates that an anomaly was found during
the network node numbering procedure.
I/O • It indicates that the corresponding input or output are active (high
logic level)
6 Configuration parameter table
1 AI.0 type sensor
2 AI.1 type sensor
Sensor selection / analog input configuration
0 0-10 V 1 4-20 mA 2 0-20 mA
3 AI.0 input lower limit
4 AI.1 input lower limit
Analog input lower limit for normalized signals. E.g.: with input 4..20 mA V this parameter assumes
the value associated to 4 mA
-32767..+32767, Default: 0.
5 AI.0 input upper limit
6 AI.1 input upper limit
Analog input upper limit for normalized signals. E.g.: with input 4..20 mA V this parameter assumes
the value associated to 20 mA
-32767. .+32767. Default:1000
7 Linear input beyond limits AI.0
8 Linear input beyond limits AI.1
In case of linear input it allows the process to exceed the minimum and maximum numeric limits
set in parameters 3, 4, 5 and 6.
0 Disabled (Default)
1 Enabled

User manual - PLE500 - 11
9 AI.0 offset calibration
10 AI.1 offset calibration
Offset calibration Value added to or taken from the process displayed.
-10000..+10000 [digit]. Default 0.
11 AI.0 gain calibration
12 AI.1 gain calibration
Gain calibration. Value to be multiplied by the process in order to calibrate on the operating point.
E.g.: to correct the 0..1000 operating scale that displays 0..1010, set the parameter to -1.0
-1000 (100.0%)...+1000 (+100.0%), Default: 0.0.
13 AI.0 latch-On function
14 AI.1 latch-On function
Function available from software version 2.00
15 AI.0 input filter
16 AI.1 input filter
Analog input reading filter: increases process stability. It indicates the number of samples to
average in the process calculation.
1...30. (Default: 10)
17 AO.0 type output
18 AO.1 type output
Selects the operating mode of the analog output.
0 4-20 mA (Default)
1 0-20 mA.
2 Proportional time (
available from software version 1.01
)
19 AO.0 output lower limit
20 AO.1 output lower limit
Continuous output range lower limit (value associated to 4mA / 0 mA).
-32767..+32767 [digit], Default: 0.
21 AO.0 output upper limit
22 AO.1 output upper limit
Continuous output range lower limit (value associated to 20 mA).
-32767..+32767 [digit], Default: 1000.
23 AO.0 output cycle time
24 AO.1 output cycle time
Determines the cycle time in managing the analog output in proportional time mode (
available
in software version 1.01
).
1..600 [s], Default: 10.
25 Digital input filter
Defines the time during which the digital input must remain stable before being considered valid.
0..250 [ms], Default: 5 ms.

12 - PLE500 - User manual
26 Encoder/Counter setup 1
27 Encoder/Counter setup 2
28 Encoder/Counter setup 3
29 Encoder/Counter setup 4
Determines the mode of operation of the encoder input or mono-directional counter.
0 Disabled (Default).
1 Encoder X2 phase A-B (calculation on the fronts of signal A).
2 Encoder X4 phase A-B (calculation on the fronts of signal A and B).
3 Encoder X2 phase A-B-Z (calculation on the fronts of signal A).
4 Encoder X4 phase A-B-Z (calculation on the fronts of signal A and B).
5 Counter Up.
6 Counter Down.
30 Encoder/Counter 1 setup value
32 Encoder/Counter 2 setup value
34 Encoder/Counter 3 setup value
36 Encoder/Counter 4 setup value
Determines the value that will be loaded in the register of the calculations for the encoder or
counter when the loading command is given. The register value is 32 bit (see paragraph “Encoder
/ Counter commands”).
-2147483648..+2147483647 [digit], Default: 0.
7 Command and operation variable table
I 0 block digital input status
I 1 block digital input status
Reading of these variables lets you recover the status of digital inputs of the device. Each bit of
these variables corresponds to a precise digital input according to the order below:
I 0 block digital input status
bit 0 Digital input status I0.0
...
bit 7 Digital input status I0.7
...
I 1 block digital input status
bit 0 Digital input status I1.0
...
bit 7 Digital input status I1.7
...
Q 0 block digital output value
Q 1 block digital output value
Writing these variables lets you set the value of the digital outputs. Each bit of these variables
corresponds to a precise digital output according to the order below:
Q 0 block digital output value
bit 0 Q0.0 digital output value
...
bit 7 Q0.7 digital output value
Q 1 block digital output value
bit 0 Q1.0 digital output value
...
bit 7 Q1.7 digital output value
Default: 0.
AI.0 analog input value
AI.1 analog input value
Reading these variables lets you recover the value assumed by the corresponding normalized
analog input.
AQ.0 analog output value
AQ.1 analog output value
Writing these variables lets you set the value of the corresponding analog output. The value
passed to this variable should range between the minimum and the maximum limit declared for
the output (parameters from 13..20 and 21..22).
Default: 0.

User manual - PLE500 - 13
Encoder/Counter commands 1
Encoder/Counter commands 2
Encoder/Counter commands 3
Encoder/Counter commands 4
These variables are used to send the commands to the encoder/counter inputs. When writing the
suitable value, the following commands can be executed.
0 No command (Default)
1 Loading the counter with the preset value.
2 Loading the counter with the preset value at the next front of the Z signal.
Once the operation specified by the command has been executed, the variable is taken back to
0 automatically.
Encoder/Counter calculations 1
Encoder/Counter calculations 2
Encoder/Counter calculations 3
Encoder/Counter calculations 4
These variables contain the value of the calculations detected by the encoder/counter inputs. The
calculation is maintained also in the absence of power supply and is updated automatically. The
value of this register is a 32 bit value.
Calculations at second encoder/counter 1
Calculations at second encoder/counter 2
Calculations at second encoder/counter 3
Calculations at second encoder/counter 4
These variables contain the number of calculations recored in the last second by the inputs
connected to the encoders/counters. These variables are updated automatically every second.
Calculations at the tenth/second encoder/counter 1
Calculations at the tenth/second encoder/counter 2
Calculations at the tenth/second encoder/counter 3
Calculations at the tenth/second encoder/counter 4
These variables contain the number of calculations recored in the last 100 ms by the inputs
connected to the encoders/counters. These variables are updated automatically every 100 ms.
Action in case of communication error
Use this variable to set the action carried out by the PLE module in case of interrupted
communication with the PL500.
0 Module stop (Default)
1 No action
Mask of status for digital outputs in error Q 0 block
Mask of status for digital outputs in error Q 1 block
These two variables let you set the methods to manage each individual digital output in case
of error. Each bit corresponds to one of the digital outputs. By setting the bit to 1, in case of
communication error, the corresponding output will assume the value indicated by the
corresponding bit in the variable “Q 0..1 block digital output value”. When you set the bit to 0, the
output will maintain its current value.
bit 0 Q0.0 output status / Q1.0 output status ...
bit 7 Q0.7 output status / Q1.7 output status ...
Default: 0xFF.

14 - PLE500 - User manual
Value of digital outputs in error Q 0 block
Value of digital outputs in error Q 1 block
These two variables let you set the status of each individual digital output in case of
communication error. Each bit corresponds to one of the digital outputs. By setting the bit to 1, in
case of communication error, the output will be activated if the corresponding bit in the variable
“Mask of status for digital outputs in error Q 0..1 block” is set to 1. By setting the bit to 0, in case
of communication error, the output will be deactivated if the corresponding bit in the variable
“Mask of status for digital outputs in error Q 0..1 block” is set to 1. If the bit in the variable “Mask
of status for digital outputs in error Q 0..1 block” is set to 0, the bit value of this variable will have
no impact.
Default: 0x00.
AQ.0 analog output in error mode
AQ.1 analog output in error mode
These two variables let you set the operating mode of each individual analog output in case of
communication error.
0 The output maintains its current value (Default)
1 The output assumes the value indicated by the variable “Analog output in error value“
(Default).
AQ.0 analog output in error value
AQ.1 analog output in error value
These two variables let you set the value of each individual analog output in case of communication
error.
Default: 0x00.
Notes / Updates

User manual - PLE500 - 15
Table of configuration parameters
1 AI.0 type sensor 10
2 AI.1 type sensor 10
3 AI.0 input lower limit 10
4 AI.1 input lower limit 10
5 AI.0 input upper limit 10
6 AI.1 input upper limit 10
7 Linear input beyond limits AI.0 10
8 Linear input beyond limits AI.1 10
9 AI.0 offset calibration 11
10 AI.1 offset calibration 11
11 AI.0 gain calibration 11
12 AI.1 gain calibration 11
13 AI.0 latch-On function 11
14 AI.1 latch-On function 11
15 AI.0 input filter 11
16 AI.1 input filter 11
17 AO.0 type output 11
18 AO.1 type output 11
19 AO.0 output lower limit 11
20 AO.1 output lower limit 11
21 AO.0 output upper limit 11
22 AO.1 output upper limit 11
23 AO.0 output cycle time 11
24 AO.1 output cycle time 11
25 Digital input filter 11
26 Encoder/Counter setup 1 12
27 Encoder/Counter setup 2 12
28 Encoder/Counter setup 3 12
29 Encoder/Counter setup 4 12
30 Encoder/Counter 1 setup value 12
32 Encoder/Counter 2 setup value 12
34 Encoder/Counter 3 setup value 12
36 Encoder/Counter 4 setup value 12
I 0 block digital input status 12
I 1 block digital input status 12
Q 0 block digital output value 12
Q 1 block digital output value 12
AI.0 analog input value 12
AI.1 analog input value 12
AQ.0 analog output value 12
AQ.1 analog output value 12
Encoder/Counter commands 1 13
Encoder/Counter commands 2 13
Encoder/Counter commands 3 13

16 - PLE500 - User manual
Encoder/Counter commands 4 13
Encoder/Counter calculations 1 13
Encoder/Counter calculations 2 13
Encoder/Counter calculations 3 13
Encoder/Counter calculations 4 13
Calculations at second encoder/counter 1 13
Calculations at second encoder/counter 2 13
Calculations at second encoder/counter 3 13
Calculations at second encoder/counter 4 13
Calculations at the tenth/second encoder/counter 1 13
Calculations at the tenth/second encoder/counter 2 13
Calculations at the tenth/second encoder/counter 3 13
Calculations at the tenth/second encoder/counter 4 13
Action in case of communication error 13
Mask of status for digital outputs in error Q 0 block 13
Mask of status for digital outputs in error Q 1 block 13
Value of digital outputs in error Q 0 block 14
Value of digital outputs in error Q 1 block 14
AQ.0 analog output in error mode 14
AQ.1 analog output in error mode 14
AQ.0 analog output in error value 14
AQ.1 analog output in error value 14

Manuale d’uso - PLE500 17
Introduzione
Grazie per aver scelto un modulo di I/O Pixsys.
Il PLE500-6AD nasce come dispositivo di espansione per il plc modello PL500. Esso integra un un
unico dispositivo ingressi/uscite digitali, ingressi analogici per segnali normalizzati e uscite analogiche
in corrente. La comunicazione con il PL500 avviene tramite il bus su barra DIN, il che semplifica
notevolmente il cablaggio e la fase di messa in servizio.
1 Norme di sicurezza
Prima di utilizzare il dispositivo leggere con attenzione le istruzioni e le misure di sicurezza contenute in
questo manuale. Disconnettere l’alimentazione prima di qualsiasi intervento su connessioni elettriche
o settaggi hardware al fine di prevenire il rischio di scosse elettriche, incendio o malfunzionamenti.
Non installare e non mettere in funzione lo strumento in ambienti con sostanze infiammabili, gas o
esplosivi. Questo strumento è stato progettato e realizzato per l’utilizzo convenzionale in ambienti
industriali e per applicazioni che prevedano condizioni di sicurezza in accordo con la normativa
nazionale e internazionale sulla tutela della delle persone e la sicurezza dei luoghi di lavoro. Deve
essere evitata qualsiasi applicazione che comporti gravi rischi per l’incolumità delle persone o sia
correlata a dispositivi medici salvavita. Lo strumento non è progettato e realizzato per installazione in
centrali nucleari, armamenti, sistemi di controllo del traffico aereo o della sicurezza in volo, sistemi di
trasporto di massa.
L’utilizzo/manutenzione è riservato a personale qualificato ed è da intendersi unicamente nel rispetto
delle specifiche tecniche dichiarate in questo manuale.
Non smontare, modificare o riparare il prodotto né toccare nessuna delle parti interne.
Lo strumento va installato e utilizzato esclusivamente nei limiti delle condizioni ambientali dichiarate.
Un eventuale surriscaldamento può comportare rischi di incendio e abbreviare il ciclo di vita dei
componenti elettronici.
1.1 Organizzazione delle note di sicurezza
Le note sulla sicurezza in questo manuale sono organizzate come segue:
Note di sicurezza Descrizione
Danger! La mancata osservanza di queste linee guida e avvisi di sicurezza
può essere potenzialmente mortale.
Warning! La mancata osservanza di queste linee guida e avvisi di sicurezza
può comportare lesioni gravi o danni sostanziali alla proprietà.
Information! Tali informazioni sono importanti per prevenire errori.
1.2 Note di sicurezza
Danger!
ATTENZIONE - Rischio di incendio e scosse elettriche
Questo prodotto è classificato come apparecchiatura di controllo del processo di tipo
aperto. Deve essere montato in un involucro che non permetta al fuoco di fuoriuscire
esternamente.
Danger!
Se i relè di uscita vengono utilizzati oltre la loro aspettativa di vita, possono verificarsi
occasionalmente fusioni o bruciature dei contatti.
Considerare sempre le condizioni di applicazione e utilizzare i relè di uscita entro il loro
carico nominale e l’aspettativa di vita elettrica. L’aspettativa di vita dei relè di uscita varia
notevolmente con il carico in uscita e le condizioni di commutazione.
Warning!
I dispositivi devono essere alimentati a energia limitata secondo UL 61010-1 3rd Ed,
sezione 9.4 o LPS in conformità con UL 60950-1 o SELV in conformità con UL 60950-1 o
Classe 2 in conformità con UL 1310 o UL 1585.
Warning! Per i morsetti a vite, serrare le viti alla coppia di serraggio di 0,22 Nm

18 PLE500 - Manuale d’uso
Warning!
Un malfunzionamento nel controllore digitale può occasionalmente rendere impossibili
le operazioni di controllo o bloccare le uscite di allarme, con conseguenti danni
materiali. Per mantenere la sicurezza, in caso di malfunzionamento, adottare misure di
sicurezza appropriate; ad esempio con l’installazione di un dispositivo di monitoraggio
indipendente e su una linea separata.
1.3 Precauzioni per l’uso sicuro
Assicurarsi di osservare le seguenti precauzioni per evitare errori, malfunzionamenti o effetti negativi
sulle prestazioni e le funzioni del prodotto. In caso contrario, occasionalmente potrebbero verificarsi
eventi imprevisti. Non utilizzare il controller digitale oltre i valori nominali.
• Il prodotto è progettato solo per uso interno. Non utilizzare o conservare il prodotto all’aperto o in
nessuno dei seguenti posti:
- Luoghi direttamente soggetti a calore irradiato da apparecchiature di riscaldamento.
- Luoghi soggetti a spruzzi di liquido o atmosfera di petrolio.
- Luoghi soggetti alla luce solare diretta.
- Luoghi soggetti a polvere o gas corrosivi (in particolare gas di solfuro e gas di ammoniaca).
- Luoghi soggetti a forti sbalzi di temperatura.
- Luoghi soggetti a formazione di ghiaccio e condensa.
- Luoghi soggetti a vibrazioni e forti urti.
• L’utilizzo di due o più controller affiancati o uno sopra l’altro possono causare un incremento di
calore interno che ne riduce il ciclo di vita. In questo caso si raccomanda l’uso di ventole per il
raffreddamento forzato o altri dispositivi di condizionamento della temperatura interno quadro.
• Controllare sempre i nomi dei terminali e la polarità e assicurarsi di effettuare una cablatura corretta.
Non collegare i terminali non utilizzati.
• Per evitare disturbi induttivi, mantenere il cablaggio dello strumento lontano da cavi di
potenza con tensioni o corren ti elevate. Inoltre, non collegare linee di potenza insieme o in
parallelo al cablaggio del controller digitale. Si consiglia l’uso di cavi schermati e condotti
separati. Collegare un limitatore di sovratensione o un filtro antirumore ai dispositivi che
generano rumore (in particolare motori, trasformatori, solenoidi, bobine o altre apparecchia-
ture con componenti induttivi). Quando si utilizzano filtri antidisturbo sull’alimentazione,
controllare tensione e corrente e collegare il filtro il più vicino possibile allo strumento.
Lasciare più spazio possibile tra il controller e dispositivi di potenza che generano alte frequenze
(saldatrici ad alta frequenza, macchine per cucire ad alta frequenza, ecc.) o sovratensioni.
• Un interruttore o un sezionatore deve essere posizionato vicino al regolatore. L’interruttore o il
sezionatore deve essere facilmente raggiungibile dall’operatore e deve essere contrassegnato
come mezzo di disconnessione per il controller.
• Rimuovere lo sporco dallo strumento con un panno morbido e asciutto. Non usare mai diluenti,
benzina, alcool o detergenti che contengano questi o altri solventi organici. Possono verificarsi
deformazioni o scolorimento.
• Il numero di operazioni di scrittura della memoria non volatile è limitato. Tenere conto di questo
quando si utilizza la modalità di scrittura in EEprom ad esempio nella variazione dei dati durante le
comunicazioni seriali.
1.4 Tutela ambientale e smaltimento dei rifiuti / Direttiva
WEEE
Non smaltire le apparecchiature elettriche ed elettroniche tra i rifiuti domestici.
Secondo al Direttiva Europea 2012/19/EU le apparecchiature esauste devono essere raccolte
separatamente al fine di essere reimpiegate o riciclate in modo eco-compatibile.

Manuale d’uso - PLE500 19
2 Identificazione del modello
PLE500-6AD
Alimentazione 12..24 VDC ±15%
16 I/O digitali
2 ingressi analogici
2 uscite analogiche
3 Dati tecnici
3.1 Caratteristiche generali
Condizioni operative Temperatura: 0-45°C; umidità 35..95 RH% senza condensa
Contenitore DIN43880, 54 x 90 x 64 mm
Materiali Contenitore: PC UL94V0 auto-estinguente
Pannello frontale: PC UL94V0 auto-estinguente
Protezione IP20 (contenitore e terminali)
Peso Circa 130 g
3.2 Caratteristiche hardware
Alimentazione modulo 12..24 VDC fornito da PLE DIN Bus
Alimentazione delle
uscite digitali 12..24 VDC ±15% Consumo max. 100 W
Ingressi analogici
2: AI.0..1 Configurabili via software.
Ingresso V/I:
0-10V, 0-20 mA, 4-20 mA.
Tolleranza (25 °C)
+/-0.3% ±1 digit (su F.s.).
Impedenza:
0-10 V: Ri>110 kΩ
0-20 mA: Ri<50 Ω
4-20 mA: Ri<50 Ω
Risoluzione:
45000 punti.
Ingressi / Uscite digitali
16: ingressi PNP 12..24 VDC/ uscite
statiche 12..24 VDC 700mA MAX per
uscita (max. 3 A totali)
Ingressi Encoder /
Contatore
4: ingressi sovrapposti agli ingressi
digitali (max. 80KHz cadauno)
Uscite analogiche 2: 4..20 mA o 0..20 mA.
Configurabili via software
Risoluzione:
45000 punti.

20 PLE500 - Manuale d’uso
4 Dimensioni ed installazione
64 mm
Attacco a guida DIN EN50022
Din rail mounting guide EN50022
PLE500-6AD
54 mm
90 mm
.4
.5
.6
.7
.3
.2
.1
.0
.4
.5
.6
.7
.3
.2
.1
.0
+0
+1
1 2 34567 8 9 10 12
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
13 14 15 16 17 18 19 20 21 22 23 24
AGND
(0V)
AI0
L+0
AI1
QI.0
QI.1
QI.2
QI.3
QI.4
QI.5
QI.6
QI.7
L+1
AQ.0
AQ.1
AGND
(0V)
4.1 Sequenza di montaggio del PL500 e dei moduli di
espansione PLE500
Il PL500 con i relativi moduli di I/O prevede il montaggio e la connessione tramite apposito bus
alloggiato nell’incavo della barra DIN. I moduli di I/O (serie PLE500-xAD) verranno automaticamente
numerati ad ogni accensione, assegnando il numero 1 al primo modulo I/O collegato alla destra
del PL500, il numero 2 a quello seguente e così via, procedendo sempre verso destra. La posizione
dei vari moduli dovrà quindi rispecchiare la sequenza impostata nel progetto di LogicLab nella
definizione della rete PLCEXP. Perché la procedura di numerazione possa funzionare correttamente,
non è consentito rimuovere dispositivi dalla rete sganciandoli dal proprio bus e lasciando dei moduli
vuoti (slot bus) tra un modulo e l’altro. Tutte le operazioni di connessione /sconnessione devono essere
effettuate in assenza di tensione.
Clik!
Agganciare tutti i bus premendoli verso la barra DIN,
prestando attenzione che la connessione maschio sia a
rivolta verso sinistra e la femmina verso destra.
Agganciare tutti i bus tra loro facendoli scorrere sulla
barra DIN.
Inserire negli slot dei bus i vari moduli, iniziando dal
PL500 e proseguendo verso destra con i moduli di I/O.
Table of contents
Languages:
Other Pixsys Control Unit manuals