Plum ecoSTER 200 User manual

Room panel
ecoSTER 200 HARDWARE VERSION 2
FOR ECOMAX CONTROLLERS
OPERATION AND MAINTENANCE MANUAL
ISSUE_EN: 1.1
APPLICABLE TO SOFTWARE: v10.XX.XXX
11-2015


3
1. SAFETY ................................................................ 4
2. PURPOSE............................................................. 4
3. INFORMATION ABOUT DOCUMENTATION......... 4
4. STORAGE OF DOCUMENTATION......................... 4
5. APPLIED SYMBOLS .............................................. 4
6. WEEE 2002/96/EC DIRECTIVE ............................. 4
7. OPERATING MANUAL ......................................... 5
7.1 SWITCHING THE PANEL ON..................................... 5
7.2 SWITCHING THE PANEL OFF .................................... 5
7.3 PANEL BLOCKADE................................................. 5
7.4 OPERATION. ....................................................... 5
7.5 MAIN SCREEN ..................................................... 5
7.6 OPERATION MODES.............................................. 6
7.6.1 Operation mode with a schedule ............... 6
7.6.2 Economic mode .......................................... 6
7.6.3 Comfort mode............................................. 6
7.6.4 "Output" Mode ........................................... 6
7.6.5 Airing mode................................................. 6
7.6.6 Party mode.................................................. 6
7.6.7 Holiday mode.............................................. 7
7.6.8 Anti-freeze mode ........................................ 7
7.7 PROFILES............................................................ 7
7.8 SCHEDULE .......................................................... 7
7.8.1 Programming schedules.............................. 7
7.9 PRESET ROOM TEMPERATURE................................. 8
7.10 ECOMAX BOILER REGULATOR MENU ....................... 8
7.11 SETTINGS ........................................................... 8
7.11.1 Weather sensor .......................................... 8
7.11.2 Thermostat settings.................................... 9
7.11.3 Hysteresis.................................................... 9
7.11.4 Temperature correction ............................. 9
7.11.5 Language change ........................................ 9
7.11.6 Sound alarm................................................ 9
7.11.7 Clock settings .............................................. 9
7.11.8 Brightness screen setting............................ 9
7.11.9 Information................................................. 9
8. INSTRUCTIONS FOR PANEL ASSEMBLY ............... 9
8.1 TECHNICAL DATA ................................................. 9
8.2 STORAGE AND TRANSPORTATION CONDITIONS ......... 10
8.3 ENVIRONMENTAL CONDITIONS ............................. 10
8.4 ASSEMBLY REQUIREMENTS................................... 10
8.5 INSTRUCTIONS FOR ASSEMBLY .............................. 10
8.6 ELECTRICAL CONNECTION TO THE MODULE
CONTROLLERS ECOMAX.................................................. 10
8.6.1 Connection to ecoMAXX800 R2,T2 and
ecoMAX800 P1,P2,D1,D2......................................11
8.6.2 Connection to ecoMAXX800 R3,T3 and
ecoMAX800 P3,D3 ................................................12
8.6.3 Connection to ecoMAX850 P1...................12
8.6.4 Connection to ecoMAX850 P2,R2,D2 ........13
8.6.5 Connection to ecoMAX860 P1,P2,D1,D2...13
8.7 ASSEMBLING SENSORS OF THERMOSTAT 2AND 3......14

4
1. Safety
Incorrect electrical connection of the room
panel with ecoMAX regulator can cause
damage both to the ecoSTER200 room panel
and ecoMAX regulator. Therefore, installation
has to be done by a qualified installer.
Additional protective measures should be
taken in order to prevent results of
malfunction of the regulator or of errors in its
software which could result in a loss of
property or other dangerous consequences,
i.e. freezing of water in hydraulic system.
2. Purpose
EcoSTER200 room panel is a modern
electronic device mainly used as a
programmable room thermostat. The
regulator provides very simple and effective
way to control indoor temperature.
Temperature sensor included in the regulator
enables reading and programming
temperature with the accuracy of 0,1°C.
Regulator can be programmed in a 7-day
cycle with the accuracy of 0,5 hour.
Therefore, there is a possibility of 48
temperature changes per day. User can
preset different time zones for each day of
the week.
After connecting two additional temperature
sensors, the ecoSTER200 room panel
provides temperature control in three
independent rooms.
The ecoSTER200 room panel also has a
function of additional panel for boiler
regulator control.
It can be used in household and similar
facilities, as well as in slightly industrialized
facilities.
3. Information about documentation
The ecoSTER200 room panel manual is a
supplement for the corresponding ecoMAX
regulator. In particular, except for this
manual, the regulator manual should also be
observed. We are not responsible for any
damages caused by failure to observe these
instructions.
4. Storage of documentation
This assembly and operation manual, as well
as any other applicable documentation,
should be stored diligently, so that it was
available at any time. In the case of moving
or selling the device, the attached
documentation should be forwarded to the
new user/owner.
5. Applied symbols
In this manual the following graphic symbols
are used:
- useful information and tips,
- important information; failure to
observe these can cause damage of
property, threat for human and
household animal health and life.
Caution: the symbols indicate important
information, in order to make the manual
more lucid. Yet, this does not exempt the
user and installer from the obligation to
comply with requirements which are not
marked with graphic symbols!
6. WEEE 2002/96/EC Directive
Act on electrical and electronic
equipment
•Recycle the product and the packaging
at the end of the operational use
period in an appropriate recycling
plant,
•Do not dispose of the product together
with normal waste,
•Do not burn the product.

5
7. Operating manual
7.1 Switching the panel on
To switch the panel on, press TOUCH&PLAY
button.
7.2 Switching the panel off
To switch the panel off, push the button in a
main window of one of the thermostats, hold
it for at least 3s and select "Switch off" (from
the list.
Switching the ecoSTER200 room
panel off does not result in
switching the ecoMAX boiler off.
7.3 Panel blockade
In order to lock the panel, push the button in
a main window of one of the thermostats,
hold it for at least 3s and select "Lock" from
the list. When the panel is locked, a key
symbol is displayed in a main window next to
a clock.
In order to unlock the panel, hold the button
for at least 4 seconds.
7.4 Operation.
The panel is equipped with TOUCH&PLAY
button which facilitates the operation. This
button is operated by
turning and pushing.
Push the button
shortly to edit a
particular parameter.
In order to exit the
parameter edition
mode or particular
menu, hold the button
for at least 2s. Modify
the edited value by
turning the button right or left.
The ecoSTER200 panel operation is easy and
intuitive. When the panel displays main
window, turn the button right or left in order
to change displayed main window: 1,
thermostat 2. thermostat 3, boiler. If
temperature sensors of thermostats 2 and 3
are not connected, the mains screens of
thermostats 2 and 3 are not available.
Push the button shortly to display menu.
Type of displayed menu will be according to
a currently displayed main screen. For
example, if you select the room thermostat 1
on the main screen, entering to menu will
result in displaying settings for the first
thermostat and common settings. When the
main window for boiler settings is displayed,
entering to menu will result in displaying
boiler settings, etc.
For example, in order to change
settings of thermostat 3, display
the main screen of thermostat 3 by
turning the button and push the
button shortly in order to enter the
settings menu of this thermostat.
7.5 Main screen
1. Current operation mode of room
thermostat:
- Schedule
- Economic
- Comfort
- Output
- Airing
-Party
- Holiday
- Anti-freeze
- ON
2. Current preset room temperature.
3. Indication of active thermostat
(heating).
4. Clock.
5. Current external temperature (only
available when a weather sensor is
connected to the boiler regulator).
4
5
6
1
9
8
2
3
7

6
6. Currently selected profile.
7. Graphic presentation of programmed
time zones (schedule).
8. Number of thermostat for which this
main screen is displayed.
9. Current, measured room temperature.
7.6 Operation modes
7.6.1 Operation mode with a schedule
In this mode, the regulator presets the
temperature in rooms according to a time
schedule. In the main window, in a place for
displaying operation mode, a clock icon is
displayed. To set this mode, select:
MENU →Operation mode →Schedule
Programming a schedule is described in 7.8.1
7.6.2 Economic mode
In this mode, the regulator works with
constant economic preset temperature, set in
the following parameter:
MENU →Temperature Settings →Night
temperature
In the main window, in a place for displaying
operation mode, a quarter moon icon is
displayed. In order to activate this mode,
select:
MENU →Operation Mode →Economic
7.6.3 Comfort mode
In this mode, the regulator works with
constant comfort preset temperature set in
the following parameter:
MENU →Temperature Settings →Day
temperature
In the main window, in a place for displaying
operation mode, a sun icon is displayed.
In order to activate this mode, select:
MENU →Operation mode →Comfort
7.6.4 "Output" Mode
This mode enables to replace the existing
temperature setting for a period of 1 to 60
hours with an economic temperature set in
the following parameter:
MENU →Temperature Settings →Night
temperature. In order to activate this
mode, enter the MENU and select:
Operation mode →Output
Screen for editing the duration of this mode
will be displayed. After setting the required
duration and confirming by pushing the
button, the "Output" operation mode is
activated; in this mode, the economic
temperature is set to a preset duration.
Note: Time will be counted by full hours. It
means that the first hour will not be a full
hour - it will be a number of minutes left to a
current full hour.
For example, if the manual mode is set to
17:45 for a duration of 4 hours, a real
duration of the party mode will be 3h 15 min.
When a preset time elapses, the regulator
switches to a previous mode. In the main
window, in a place for displaying operation
mode, an open door icon is displayed.
7.6.5 Airing mode
Selecting the airing mode in thermostat 1
will close mixers and switch off central
heating pump in the boiler regulator for 1 to
60 minutes. In order to activate this mode,
enter the MENU and select:
Operation mode →Airing
Screen for editing the duration of this mode
will be displayed. After setting the required
duration and confirming by pushing the
button, the Airing operation mode is
activated.
Note: Time will be counted by full minutes. It
means that the first minute will not be a full
minute - it will be a number of seconds left
to a current full minute.
When a preset time elapses, the regulator
switches to a previous mode. In the main
window, in a place for displaying operation
mode, an open window icon is displayed.
During this mode, a thermostat contact
remains opened.
7.6.6 Party mode
Party mode enables to replace the existing
temperature setting for a period of 1 to 48
hours with any temperature. In order to
activate this mode, enter the MENU and
select:
Operation mode →Party
The preset room temperature edition window
will be displayed. Set the required
temperature by turning the button right or
left. Push the button to confirm and save the

7
set temperature value; the mode duration
time edition window will be displayed. After
setting the required duration and confirming
by pushing the button, the Party operation
mode is activated; in this mode, the
temperature is set to a preset duration.
Note: Time will be counted by full hours. It
means that the first hour will not be a full
hour - it will be a number of minutes left to a
current full hour.
For example, if the manual mode is set to
17:45 for a duration of 4 hours, a real
duration of the party mode will be 3h 15 min.
When a preset time elapses, the regulator
switches to a previous mode. In the main
window, in a place for displaying operation
mode, a glass icon is displayed.
7.6.7 Holiday mode
Holiday mode enables to replace the existing
temperature setting for a period of 1 to 99
days with a constant temperature. This
function is particularly useful in case of
holiday departure:
In order to activate this mode, enter the
MENU and select:
Operation Mode →Holiday
The preset room temperature edition window
will be displayed. Set the required
temperature by turning the button right or
left. Push the button to confirm and save the
set temperature value. Next, the Holiday
mode duration time edition window will be
displayed. After setting the required duration
and confirming by pushing the button, the
Holiday operation mode is activated; in this
mode, the temperature is set to a preset
duration.
Note: Time will be counted by full days. It
means that the first day will not be a full day
- it will be a number of hours left to a current
full day.
For example, if the manual mode is set to
17:45 for a duration of 14 days, a real
duration of the Holiday mode will be 13 days
6 hours and 15 minutes.
When a preset time elapses, the regulator
switches to a previous mode. In the main
window, in a place for displaying operation
mode, a suitcase icon is displayed.
7.6.8 Anti-freeze mode
In this mode, the regulator works with
constant preset temperature, set in the
following parameter:
MENU →Temperature Settings →Anti-
freeze temperature
In the main window, in a place for displaying
operation mode, a snowflake icon is
displayed.
Selecting the anti-freeze mode in thermostat
1 will set the hot utility water temperature in
the ecoMAX boiler regulator to 8°C.
7.7 Profiles
The ecoSTER200 room panel enables
programming four profiles of schedules. The
following set of parameters is recorded for
each profile:
•schedule for all weekdays
•night temperature (economic)
•day temperature (comfort)
•anti-freeze temperature
•hysteresis
Profile changing mechanism is very useful if
there is a need of cyclical changes in
schedule; for example when user works on
various shifts. Then, by selecting a profile,
you can rapidly switch between several
programmed schedules without a necessity
of editing them.
7.8 Schedule
Regulator can be programmed in 7-day cycle
with an accuracy of 0,5 hour. Therefore,
there is a possibility of 48 temperature
changes per day.
Regulator enables programming two levels of
temperature: day (comfort) and night
(economic). Regulator enables programming
various time zones individually for each
weekday.
7.8.1 Programming schedules
In order to program a schedule for a
particular thermostat, display the main
screen of this thermostat (pt. 7.4) and
select: MENU →Schedule
Then, choose a weekday for which you want
to establish or modify a schedule. After
selecting a weekday, a window for editing a
schedule is displayed.

8
1. Preset temperature: comfort or
economic
2. Arrow indicating currently edited time
interval
3. Currently edited time interval.
In order to set required time interval, you
should:
−by turning the button, set the arrow on a
time zone starting hour
−by pushing the button, set the comfort or
economic temperature (it is indicated by
displaying a sun or moon symbol in the
upper left corner of edition window)
−turn the button and set the arrow on a
time zone ending hour
−finish the edition of a particular zone by
pushing the button
−if needed, repeat the steps above for
other time interval - in order to exit a
schedule window, push and hold the
button for at least 2 seconds
After exiting the schedule editing mode, a
window is displayed which enables you to
assign currently edited schedule to any day
of the week.
Select weekdays for which the currently
edited schedule is to be assigned and then,
select "Save and exit".
7.9 Preset room temperature
Preset night (economic) temperature is set
in:
MENU →Temperature settings →Night
temperature
Preset day (comfort) temperature is set in:
MENU →Temperature settings →Day
temperature
Preset anti-freeze temperature is set in:
MENU →Temperature settings →Anti-
freeze temperature
7.10 ecoMAX boiler regulator menu
In order to display the ecoMAX (2) boiler
regulator main screen, turn the button right
when the thermostat main screen is
displayed. Push the button shortly to display
the boiler regulator menu. This menu is
similar as in ecoMAX boiler regulator and
therefore, the instructions of boiler regulator
have to be followed.
The ecoSTER200 room panel displays alarms
reported by the ecoMAX boiler regulator. In
case when generation of sound alarm is
activated (pt. 7.11.6), pushing the button
will result in deactivation of acoustic signal.
However, the alarm will not be cancelled. For
safety reasons it could be done only by the
boiler regulator.
Diagram of cooperation of ecoSTER200 with
ecoMAX, where 1 - ecoSTER200, 2 - ecoMAX
boiler regulator.
7.11 Settings
In order to enter the setting menu, select:
MENU →Settings
7.11.1Weather sensor
This parameter is used only in case when
there is an external temperature (weather)
sensor connected to the boiler regulator. Set
this parameter to display measured external
temperature in the main window of all
thermostats.
1
2
3
Schedule

9
7.11.2Thermostat settings
This parameter enables or disables operation
of particular ecoSTER200 thermostats.
Enabling or disabling thermostat 2
or 3 is possible only in case when
there are additional external
temperature sensors connected to
the ecoSTER200 room panel.
When thermostat 2 or 3 is disabled,
its main screen is not displayed.
7.11.3Hysteresis.
This parameter defines hysteresis of room
temperature. It decides of room temperature
at which the room thermostat will inform the
boiler regulator to heat. The boiler regulator
will start heating when the room temperature
drops under the current preset temperature
minus hysteresis. It will finish heating when
the current preset room temperature is
reached.
7.11.4Temperature correction
This parameter enables to make corrections
of measured thermostat temperature within
a range of -3.0°C to +3.0°C.
Warning! The changes are not
visible immediately. Wait 5 minutes
to adjustment was taken into
account.
7.11.5Language change
In order to change menu language, select:
MENU →Settings →Language
and select required language from the list.
7.11.6Sound alarm
This parameter decided whether during the
alarm there will be a sound signal generated
in the ecoSTER200 panel.
7.11.7Clock settings
In order to set time and date, select:
MENU →Settings →Clock
According to set date, the device will
automatically set an appropriate weekday.
The ecoSTER200 panel is equipped with a
system clock which is independent of the
boiler regulator clock, and therefore both
clocks have to be set on the same hour.
Programmed schedule works
according to the scoSTER200 panel
clock.
7.11.8Brightness screen setting
The panel has the ability to set three
separate levels of screen brightness
separately for day, night and when editing
parameters. To adjust the brightness for the
selected level, go to the MENU →Settings
→Brightness, and then set [%] intensity.
The panel based on the internal
system clock settings independently
activates the programmed level of
brightness in daylight hours and
night.
7.11.9Information
In this window you can obtain information
concerning software version of the
ecoSTER200 panel and connected ecoMAX
boiler regulator.
8. Instructions for panel assembly
8.1 Technical data
Power source
+5V..12VCC
Current consumed by the device
I = 0.1 A
Protection level of the regulator
IP20
Ambient temperature
0...50 °C
Storage temperature
0...65 °C
Temperature measurement range
0...50 °C
Temperature regulation range
5...35 °C
Hysteresis
0.2…5 °C
Relative humidity
5–85% without
condensation
Terminals
Elastic clamps
0.25–2.5mm2
Display
Graphic 128x64
External dimensions
164x90x40 mm
Complete weight
0.2 kg
Standards
PN-EN 60730-2-9
PN-EN 60730-1
Software class
A

10
8.2 Storage and transportation
conditions
Panel cannot be directly exposed to weather
conditions, i.e. rain and solar radiation.
Storage and transportation temperature
should be within a range of -15…65 °C.
During transportation, the panel cannot be
exposed to vibrations which are higher than
typical for normal transporting conditions.
8.3 Environmental conditions
The panel should be installed in a dry
residential compartment.
Moreover, the regulator cannot be used in
condensation conditions and be exposed to
water.
8.4 Assembly requirements
In order to guarantee a maximum operation
efficiency of the regulator, follow the
recommendations concerning a place of
device assembly:
1. The panel is purposed for on-wall
assembly inside rooms.
2. The panel should be assembled on a
height app. 1.5 m over the floor level.
3. Avoid places which are strongly sunlit,
close to heating devices, in direct vicinity
of doors and windows, where a
temperature measurement could be
easily interfered by external conditions.
4. Avoid places with weak air circulation.
The panel should be installed by a qualified
installer.
The manufacturer does not bear any
responsibility for damages caused by failure
to observe this manual.
8.5 Instructions for assembly
Open the casing as shown on the figure
below:
Drill holes in a wall. If a wall is made of
bricks, use rawlplugs. Screw in the screws.
Perform electrical connections between the
ecoSTER200 panel with the ecoMAX
regulator. The ecoSTER200 panel is supplied
by the ecoMAX regulator and does not
require any supply source. Cable can be both
bricked in a wall or routed on a wall surface.
Do not lead connection cable together with
cables of electrical network in the building.
Do not lead the cable in a vicinity of devices
emitting strong electromagnetic field.
Do not mix up cable poles. It can
result in damaging the devices.
Closing the casing. Push the cover in a place
indicated by the red arrow until you hear a
clear click.
8.6 Electrical connection to the module
controllers ecoMAX
ecoSTER200 room panel can be supplied with
+5V or +12V, depending on the module
type ecoMAX. It can be powered directly
from the terminal regulator module or an
external power supply from +5V to +12VDC
/min.200mA, which is not included with the
room panel.
Maximum length of the cable connecting the
room panel with ecoMAX regulator cannot
exceed 30 m, and its cross-section area
cannot be lower than 0.25 mm2; it is
recommended to use 0.5 mm2cable.

11
The length of uninsulated tip of the cable
should be within 8÷10mm. Cable is inserted
into a terminal by pushing a button on this
terminal with a flat screwdriver, inserting the
cable and releasing the button.
Below are the wiring scheme thermostats
with room sensors 2 and 3 type CT7 and the
way VCC panel power module + 5V or + 12V
and an optional external power supply +
5..12VDC.
8.6.1 Connection to ecoMAXX800 R2,T2
and ecoMAX800 P1,P2,D1,D2

12
8.6.2 Connection to ecoMAXX800 R3,T3
and ecoMAX800 P3,D3
8.6.3 Connection to ecoMAX850 P1

13
8.6.4 Connection to ecoMAX850
P2,R2,D2
8.6.5 Connection to ecoMAX860
P1,P2,D1,D2

14
8.7 Assembling sensors of thermostat
2 and 3
After connecting two additional temperature
sensors, the ecoSTER200 room panel
provides independent temperature regulation
in three rooms. Regulator cooperates with
CT7 type room temperature sensors. Use a
cable with a cross-section of at least 0.25
mm2to connect sensors. Recommended
cross-section is 0.5 mm2. Cable should not
be longer than 20 m. Sensor cables should
be separated from power cables (~230V). If
not, incorrect temperature readings can
occur. Minimum distance between sensor
cables and power cables should be at least
10 cm.
In order to guarantee a maximum operation
efficiency of the regulator, follow the
recommendations concerning a place of
sensor assembly:
1. Sensors should be assembled on a
height app. 1.5 m over the floor level.
2. Avoid places which are strongly sunlit,
close to heating devices, in direct
vicinity of doors and windows, where
a temperature measurement could be
easily interfered by external
conditions.
3. Avoid places with weak air circulation,
e.g.: behind furniture.
Fig. 8.1
1
Diagram of cooperation between ecoSTER200 and ecoMAX, where: 1 - ecoSTER200, 2 -
room sensor of thermostat 2 type CT7, 3 - room sensor of thermostat 3 type CT7, 4 –module B
(extends the system by 2 heat circulations), 5 - ecoMAX controller
1
Diagram does not replace a project of installation and can be used only for reference.