Ambirad SmartCom3 User manual

Section
Wiring Diagrams
Single Zone B80, B160, B300 Fan Systems ------------------------ 1
Split-zone B80, B160, B300 Fan Systems--------------------------- 2
Single Zone BH300 Fan Systems-------------------------------------- 3
Split-zone BH300 Fan Systems ---------------------------------------- 4
Schematic Nor-Ray-Vac Multi-zone System ----------------------------- 5
SmartCom³ Commissioning-------------------------------------------------- 6
End Vent Suction Setting Procedure--------------------------------------- 7
SMARTCOM CONTROL PANEL &
NOR-RAY-VAC RADIANT SYSTEM.
3
Warnings
All external wiring MUST comply with the current IEE wiring regulations.
These instruction MUST be used in conjunction with the SmartCom³ user
manual and the appropriate heater manual.
Visit our Support Database
at www.s-i-d.co.uk Part No. 704007
Installation Wiring

1 Single Zone B80, B160, B300 Fan Systems.
THE LOCAL RELAY UNIT houses an inverter. This
converts the 230V single-phase input into a
three-phase 230V output. The inverter provides a
soft start to the motor, which extends the motor life
by minimising the start current.
Inverter
Local Relay
Unit
Supply via Isolator
230V 50Hz 1 Pha
SUPPLY VIA ISOLATOR
ELECTRICAL INPUT
230V 1P 22A
230V 1P 22A
230V 1P 30A
FAN TYPE
B80
B160
B300 Burners
Zone A
LL NNU V W1 342
Drawing No. : 900287 R6
Supply to inline
burners
Exhaust
Fan
4-Core Armoured or
Screened Cable 1.5mm²
FAN MOTOR
230V 3-Phase Supply.
Motor must be wired DELTA
3 Phase
Isolator MPORTANT
For Inverter panels only
(fan types B80 / B160 & B300):
MAXIMUM length of cable between inverter
and fan is 5m (EMC class A building) or
10m (EMC class B building).
N.B. if in doubt, do not exceed 5m.
(HEAT 1 OUTPUT)
(LIVE)
(NEUTRAL)
NOTES:
REMOTE SWITCH INPUTS
should be connected by 6A mains
Max length is 100m.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
Connect to B0 & B2 for remote
OFF (ie door interlock. remote
frost etc).
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
REMOTE SENSOR(s) may be
placed at a max distance of 100m
from the control unit, using
screened 6A mains* cable.
Wiring should be kept separate
from mains wiring to minimise
noise pick up. Set within Engineers
functions for remote sensor.
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
Low Voltage
+15V DC
Black Bulb
Sensor
(FAN CIRCUIT)
(FAN CIRCUIT)
Volt free
Fan Trip
Indication
by others
Note: Connection to the
burners MUST be made
via a 3A fused spur.
!
!
FUSE RATING
!
41 40 95 1/L 2/N 106B1 B0 B2S/R0S/R1
C
SmartCom
Singlezone NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
eg Door
Remote OFF
(where applicable)
Remote ON
(where applicable)
eg B.M.S.

2 Split-zone B80, B160, B300 Fan System.
Burners
Zone A
To other slave
controllers
SmartCom Mulitizone
Supply via Isolator
230V 50Hz 1 Pha
To other slave
controllers
Supply via Isolator
230V 50Hz 1 Pha
(Slave 1)
Drawing No.: 900288 R5
Note: Connection to the
burners MUST be made
via a 3A fused spur.
Burners
Zone B
!
! FUSE RATING
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 14 5 6C925
eg Door Remote OFF
(where applicable)
(COMMON)
(REMOTE OFF)
NEUT
LIVE
Black Bulb
Sensor
SmartCom Mulitizone
(Master)
!
! FUSE RATING
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 78 1456C925
eg B.M.S. eg Door
Remote ON
(where applicable) Remote OFF
(where applicable)
(COMMON)
(REMOTE ON)
(REMOTE OFF)
NEUT
LIVE
Black Bulb
Sensor
Supply to inline
burners
Burners
Zone B
Supply to inline
burners
Burners
Zone A
Inverter
Local
Relay
Unit
SUPPLY VIA ISOLATOR
ELECTRICAL INPUT
230V 1P 22A
230V 1P 22A
230V 1P 30A
FAN TYPE
B80
B160
B300
Exhaust
Fan
LL NNU V W1 342
4-Core Armoured or
Screened Cable 1.5mm²
FAN MOTOR
230V 3-Phase Supply.
Motor must be wired DELTA
3 Phase
Isolator
Low Voltage +15V DC
NOTES:
Controls cables min 0.75mm² cable for up to a distance of 200m.
NETWORK. Master-slave (Network) communication is by screened
twisted pair cable, RS485 compatible such as Belden 9841. Maximum
overall system length of 500m. Connect screen to C0. NOTE: Diagram
shows a master and ONE slave configuration**. Wire further slaves in
parallel.
REMOTE SWITCH INPUTS should be connected by 0.75mm² cable.
Max length is 100m.
Low voltage switching inputs to be normally open (closed circuit
to enable).
Connect to B0 & B1 for remote ON (ie BMS time control).
Connect to B0 & B2 for remote OFF (ie door interlock. remote frost etc).
For Master/Slave networks, remote OFF can be set for individual
zones or total system via the Master.
If individual BMS ON/OFF on master/slaves systems are required,
set all SmartCom programs to 24 hour and use normally closed
contacts across B0 and B2. Set engineers variable.
REMOTE SENSOR(s) may be placed at a max distance of 100m
from the control unit, using screened 0.75mm² cable.
Wiring should be kept separate from mains wiring to minimise noise
pick up. Set within Engineers functions for remote sensor.
THE LOCAL RELAY UNIT houses an inverter. This converts the 230V
single-phase input into a three-phase 230V output. The inverter provides a
soft start to the motor, which extends the motor life by minimising the start
current.
Volt Free Circuit
Fan Trip
Indication
by others

3 Single Zone BH300 Fan System.
Supply via Isolator
230V 50Hz 1 Pha
Burners
Zone A
Drawing No. : 900289 R8
Supply to inline
burners
(HEAT 1 OUTPUT)
(LIVE)
(NEUTRAL)
NOTES:
REMOTE SWITCH INPUTS
should be connected by 6A mains
Max length is 100m.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
Connect to B0 & B2 for remote
OFF (ie door interlock. remote
frost etc).
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
REMOTE SENSOR(s) may be
placed at a max distance of 100m
from the control unit, using
screened 6A mains* cable.
Wiring should be kept separate
from mains wiring to minimise
noise pick up. Set within Engineers
functions for remote sensor.
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
Black Bulb
Sensor
Note: Connection to the
burners MUST be made
via a 3A fused spur.
!
!
FUSE RATING
!
41 40 95 1/L 2/N 106B1 B0 B2S/R0S/R1
C
SmartCom
Singlezone NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
eg Door
Remote OFF
(where applicable)
Remote ON
(where applicable)
eg B.M.S.
4-Core Armoured Cable
FAN MOTOR
415V 3-Phase Supply.
Motor must be wired DELTA
3 Phase
Isolator
Mains Voltage
230V AC
(FAN CIRCUIT)
(FAN CIRCUIT)
SUPPLY VIA ISOLATOR
ELECTRICAL INPUT
415V 3P 25A
FAN TYPE
BH300
L2L3 L1 L1 1
U V W 234
NN
Volt free
Fan Trip
Indication
by others
Local Relay
Unit
THE LOCAL RELAY UNIT houses a 3pha
motor contactor and overload plus any
additional fan logic circuitry.
Exhaust
Fan

4 Split-zone BH300 Fan System.
Burners
Zone A
To other slave
controllers
SmartCom Mulitizone
Supply via Isolator
230V 50Hz 1 Pha
To other slave
controllers
Supply via Isolator
230V 50Hz 1 Pha
(Slave 1)
Drawing No.: 900290 R7
Note: Connection to the
burners MUST be made
via a 3A fused spur.
Burners
Zone B
!
! FUSE RATING
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 14 5 6C925
eg Door
Remote ON
(where applicable) Remote OFF
(where applicable)
(COMMON)
(REMOTE OFF)
NEUT
LIVE
Black Bulb
Sensor
SmartCom Mulitizone
(Master)
!
! FUSE RATING
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 78 1456C925
eg B.M.S. eg Door
Remote ON
(where applicable) Remote OFF
(where applicable)
(COMMON)
(REMOTE ON)
(REMOTE OFF)
NEUT
LIVE
Black Bulb
Sensor
Supply to inline
burners
Burners
Zone B
Supply to inline
burners
Burners
Zone A
Exhaust
Fan
4-Core Armoured Cable
FAN MOTOR
230V 3-Phase Supply.
Motor must be wired DELTA
3 Phase
Isolator
NOTES:
Controls cables min 0.75mm² cable for up to a distance of 200m.
NETWORK. Master-slave (Network) communication is by screened
twisted pair cable, RS485 compatible such as Belden 9841. Maximum
overall system length of 500m. Connect screen to C0. NOTE: Diagram
shows a master and ONE slave configuration**. Wire further slaves in
parallel.
REMOTE SWITCH INPUTS should be connected by 0.75mm² cable.
Max length is 100m.
Low voltage switching inputs to be normally open (closed circuit
to enable).
Connect to B0 & B1 for remote ON (ie BMS time control).
Connect to B0 & B2 for remote OFF (ie door interlock. remote frost etc).
For Master/Slave networks, remote OFF can be set for individual
zones or total system via the Master.
If individual BMS ON/OFF on master/slaves systems are required,
set all SmartCom programs to 24 hour and use normally closed
contacts across B0 and B2. Set engineers variable.
REMOTE SENSOR(s) may be placed at a max distance of 100m
from the control unit, using screened 0.75mm² cable.
Wiring should be kept separate from mains wiring to minimise noise
pick up. Set within Engineers functions for remote sensor.
THE LOCAL RELAY UNIT houses an inverter. This converts the 230V
single-phase input into a three-phase 230V output. The inverter provides a
soft start to the motor, which extends the motor life by minimising the start
current.
Local
Relay
Unit
Mains Voltage 230V AC
SUPPLY VIA ISOLATOR
ELECTRICAL INPUT
415V 3P 25A
FAN TYPE
BH300
Volt Free Circuit
Fan Trip
Indication
by others
L2L3 L1 L1 1
U V W 234
NN

In-line Burner
In-line Burner In-line Burner
In-line Burner
End Vent
Burner
Fused Spur
Fused Spur
Fused Spur
Fused Spur
Fused Spur
End Vent
Module
End Vent
Module
In-line Burner
Fused Spur
End Vent
Module
End Vent
Burner
Fused
Spur
From ‘Power out’ on End Vent
Burner to In-line Burners
From ‘Power out’ on
End Vent Burner to
In-line Burners
To ‘Mains In’ on
End Vent Burner
To ‘Mains In’ on
End Vent Burner
End Vent
Burner From ‘Power out’
on End Vent Burner
to In-line Burners
2nd Branch Zone 1
1st Branch Zone 1
1st Branch Zone 2
Isolator
Tail Pipe
0.75mm²
Screened
Sensor
Zone 2
SmartCom³ no.2
‘Slave’ (SC3-MZ)
230V 50Hz 13A
Mains Supply
0.75mm²
Screened
Cable
Sensor
Zone 1
Isolator
SmartCom³ no.1
‘Master’ (SC3-MZ)
Isolator
230V 50Hz 13A
Mains Supply
Local Relay
Unit / Inverter
Panel
*4 core
Armoured Cable
Networking Cable
Screened pair Beldon
9841 or equiv
* IMPORTANT
For Inverter Panels only
(fan types B80/B160 & B300)
MAXIMUM length of cable between
Inverter and Fan is 5m.
IMPORTANT
Fan types B80/B160 & B300)
MOTOR MUST BE WIRED IN
DELTA.
6 SmartCom³ Commissioning.
For ease and swiftness of initial start-up, the
SmartCom³ range of electronic controllers is
supplied factory pre-set to operate a standard
warm air unit heater. To operate with a Nor
-Ray-Vac system however, the parameters will
have to be changed via the engineers
settings.
Follow the step by step instructions overleaf for
the correct settings. For more detailed
instructions and other engineer settings, refer to
the SmartCom³ user manual GB/
SCOM/120/0309.
5 Schematic Nor-Ray-Vac Multizone System.

MASTER & SLAVE (NETWORK)
When setting up a SmartCom³ Master and
Slave (Network) system, the master controller
will display an error message during
commissioning. This will clear once the
commissioning is complete.
REMOTE SWITCHED INPUTS
SmartCom³ controllers can be operated
remotely via a remote ON or a remote OFF
signal in the following ways:
A. Building Management System
Control (BMS).
SmartCom³ controllers can be operated via a
BMS system, by applying a volt free
connection (ie closed circuit to enable) across
terminals B1 and B0 turns the system on.
Making this connection on a master controller
will turn the entire system on whereas making
this connection on a slave unit will only bring
on that zone.
A I R
M
ARM SET/OK
CONTROL TYPE
I ANTRAD SET/OK
CONTROL TYPE
SET/OKOFF
RAD/NRV/HB SPL
I
T
ON SET/OK
NTERNAL SENSORI
SET/OK0
SLAVE UN I
T
press
press
OFF SET/OK
NTERNAL SENSOR
OFF SET/OK
EXTERNAL SENSOR
SET/OKOFF
NETWORKING
SET/OKON
NETWORKING
SET/OKOFF
MASTER UN I T
SET/OKON
MASTER UN I
T
SET/OK3
SLAVE UN I
T
SET/OK0
SLAVE TOTAL
SET/OK6
SLAVE TOTAL
ON SET/OK
EXTERNAL SENSOR
SET/OKON
RAD/NRV/HB SPL
I
T
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
press
to alter
or press to advance
to accept.
Press to advance
press
I
once.
press
press
press
press
press once if
master
unit
press
press
once for
split zonal
systems
for total
no. of
slaves
once to
turn off
internal
once to
turn off
external
once for
master
slave
press for unique
slave
number
In order to access the engineer functions:
Press and hold in the button and at the same time, press the button.

Document reference number GB/CON/004/1213
The inverter
interface
(door open)
The use of an inverter on the B80, B160, B300
fan system allows the end vent suction to be
adjusted by varying the fan speed.
The description for adjusting the fan speed is
given in the following section. Apart from this
change the commissioning section in the
manual should be followed.
End vent suction (B80, B160, B300 )
For these systems the end vent suction is
adjusted by altering the low speed setting of
the inverter within the local relay unit.
1. Check that the fan damper is fully open
and secure.
2. Ensure the SmartCom³ is in a programmed
ON time.
3. Set the required room temperature above
the actual room temperature.
4. After a 30s delay the fan should run.
5. The fan should now be running and the
inverter should be showing the motor
frequency in the display.
6. Check for correct rotation of fan.
7. Press the mode button 3 times until
‘COnF’ appears on the display.
8. Press the jog dial to enter. Rotate jog dial
until ‘LSP’ is displayed. Press jog dial to
enter. Rotate jog dial to adjust frequency.
Press jog dial to enter new value, causing
the inverter to change its speed. Adjust the
frequency until the appropriate end vent
suction is achieved, this is given in the
table below.
9. Pressing the ESC button twice will return
the inverter to the ’rdY’ display. The
setting procedure is now complete.
End vent suction (BH300 ONLY)
This unit does not feature an inverter, the end
vent suction adjustment is made using the fan
damper, details of this are given in the
Nor-Ray-Vac manual.
7 End Vent Suction Setting Procedure.
1. BMS controlling time only.
Ensure all the programmed ON times in the
SmartCom² are turned off
(i.e. They read “- -:- -”).
2. BMS controlling time and temperature.
Ensure all the programmed ON times in the
SmartCom² are turned off
(i.e. They read “- -:- -”). Set all the required
day temperatures to 30°C.
B. Remote door interlock. SmartCom³
controllers can be connected to a door
interlock, remote frost stat or permanent off
switch via terminals B2 and B0. When a volt
free connection is provided (ie closed circuit to
enable) at these terminals, the controller
reverts to FROST ONLY mode. Refer to the
individual wiring diagrams for wiring
configurations and type.
Escape button:
Exits a menu or
parameter.
Mode button:
Switches between control/
programming modes.
(Only accessible with door
open).
7 segment display
Jog dial:
For navigation when
turned clockwise or
anticlockwise, or
selection/validation
when pressed.
Mode LEDs
The local relay unit
System End vent
pressure
mbar
Standard systems 6.25
Single 32LR End vent only 7.5
Single 38LR End vent only 8.25
Single 46LR End vent only 9.25
Three 46LR in a single branch 5.6
Technical Support:
Tel: 01384 489 250
Fax: 01384 489 707
ambiradsales@nordyne.com
www.ambirad.co.uk
Registered in England No. 1390934. Registered office: 10 Norwich Street, London. EC4 1BD
AmbiRad UK is a registered trademark of AmbiRad Limited. Because of continuous product innovation, AmbiRad reserves the right to change product specification without due notice.
Other manuals for SmartCom3
2
Table of contents
Other Ambirad Control Panel manuals
Popular Control Panel manuals by other brands

Bentel Security
Bentel Security Omnia 8/L manual

Siemens
Siemens FC361 Series Technical manual

SJE Rhombus
SJE Rhombus Installer Friendly Series Installation Instructions and Operation/Troubleshooting Manual

HORNER
HORNER EXL10 OCS user manual

Mirage
Mirage KP-iOS user guide

Kilsen
Kilsen KFP-CE4 Series installation manual

EBARA
EBARA FFJP 1,1 T Instruction for installation and maintenance

SHENZHEN FANHAI SANJIANG ELECTRONICS
SHENZHEN FANHAI SANJIANG ELECTRONICS JB-QBL-9116E user manual

Scantronic
Scantronic 9448+ user guide

Oliver IGD
Oliver IGD TOCSIN 700 Installation and user instructions

Simplex
Simplex 4100ES-S1 Programming guide

X10
X10 MC10A owner's manual