Powell BriteSpot Fiber-Opc User manual

1- Mounng Fixture and Opcal Fiber Installaon
Required for Installaon
A - Secure the Mounng Fixture to Busbar and Connect Fiber
Tools for Fiber Mounng:
Adjustable Wrench
1.5 mm Allen Key
Guillone Cuer
Components for Hardware Installaon:
B - Route the Fiber to Low-Voltage Cabinet
I. Insert the screw with the washer through the
fixture and busbar.
II. Insert the washers and secure it with a nut.
Ensure the hole for fiber inseron is pointed in
the direcon of the fiber roung.
Installaon of the BriteSpot Fiber-Opc Temperature Sensor has been engineered to be simple and straighorward. The
following manual will describe in detail the 3 steps needed for installaon. No specialized knowledge of fiber opcs is
necessary. A basic understanding of switchgear topology and mounng methods is required.
35 mm DIN rail (6"-8") and mounng
hardware
CAT5 Ethernet cable (if connecng to SCADA or
computer.
Quick Start Guide
G3
BriteSpot
Temperature Monitoring
Powell Canada Inc,
Suite 201, 55 Gosck Place
North Vancouver, BC, V7M 3N2
- MAX 100ºC
Sensor Tip - MAX 120ºC
Fiber
R
Do NOT bend fiber ghter
than 12 mm (1/2") radius
Do not fasten or aach ANY
mounng hardware (e-wraps,
etc.) to at least a 30 cm (12")
length of fiber between the
poron of the probe at high
v o l t a g e a n d i t s fi r s t n o n -
energized point of contact.
Keep away from sources of
excessive heat when ever
possible. Fiber probe shall not
be aached to surfaces with
temp e rat u res exc e eding
100ºC or 200ºF.
! !
Voltage: 12-24 VDC (0.12A@24VDC)
Power: 3 Was (Max)
Power Supply Requirements:
III. Insert fiber into the holding fixture and secure it
with a 1.5 mm hex screwdriver.
Avoid running fibers In the
direcon of the fold of the boot to
minimize bending and damage of
the fiber.
!

B - Insert the Opcal Fibers
2 - Hardware Installaon
D - Typical Network Connecons
C - Connect Network and Power Wiring
Star Topology (Ethernet)
Typical Serial Topology (MODBUS RTU)
(within cabinet) or connecng with twisted pair cables (cabinet to cabinet)
I. Loosen the connectors by
screwing them counter
clockwise.
A - Mount on 35 mm DIN Rail
Installing Removing
1
2
Input Voltage
Negave
Input Voltage
Negave
Input Voltage Posive Input Voltage Posive
Inverng, 2-wire, RS-
485 Chassis Grounding
Non-Inverng, 2-wire,
RS-485
Shielding of
Communicaon Pair
Relay:
Common Terminal
Relay:
Normally Open
Terminals 1-5 Terminals 6-10
Terminal
Terminal
Number Number
Name Name
Funcon Funcon
6V-
V-
Rx-
Shd
7 V+
V+
Tx+
8PE
9COM
10 NO
1
2
3
4
5
6 7 8 9 10
1 2 3 4 5
10/100
STAT
RST ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK
COM
SYS
4 5 6
7 8 9
1 2 3
10/100
STAT
RST ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK
COM
SYS
4 5 6
7 8 9
1 2 3
HMI PLC G3 Slave Device 1-31
10/100
STAT
RST ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK
COM
SYS
4 5 6
7 8 9
1 2 3
10/100
STAT
RST ID#:
BriteSpot
G3
BS3
BS2
BS1
LINK
COM
SYS
4 5 6
7 8 9
1 2 3
HMI/Master Hub
G3 Slave Devices
1
2
Note that terminals 1 and 6, as well as 2 and 7, are connected internally.
If a light remains red, ensure the probe is inserted
properly and the fiber cut is clean. Recut if necessary.
View LEDs above the connectors to determine if a
connecon has been established.
BS3
BS2
BS1
7 8
1
III. Secure fiber retenon nuts
by screwing them clockwise.
BS3
BS2
BS1
4
7 8
1
BS3
BS2
BS1
4
7 8 9
1
II. Insert the opcal fibers
unl they come to a hard
stop. Do NOT apply excessive
force.
Quick Start Guide
G3
BriteSpot
Temperature Monitoring
Powell Canada Inc,
Suite 201, 55 Gosck Place
North Vancouver, BC, V7M 3N2
Wiring Interface

3 - Configure the Communicaon Sengs
A - Connect to the Device
B - Factory Reset
I.
Connect a CAT5 Ethernet Cable directly
between the Ethernet ports on the
router and G3 to be configured.
II.
Ensure the power is connected to the
device and a link is established, indicated
by the LEDs.
III.
Type in the IP address in the browser
(default: 192.168.1.50). A field has been
provided on the back scker in case it has
been changed
IV.
From the home page you can navigate
throughout the rest of the site by using
the navigaon bar on the le.
To perform a factory reset:
I. Insert an object, such as the end of a probe, into the hole labelled "RST" in the
top le corner of the device and depress the concealed buon while applying
power to the device. Keep the buon depressed unl both the "SYS" and "COM"
LEDs stay green (about 5 seconds).
II. Release the buon and the device will restart with its default values.
Quick Start Guide
G3
BriteSpot
Temperature Monitoring
Powell Canada Inc,
Suite 201, 55 Gosck Place
North Vancouver, BC, V7M 3N2
Note that if connecng via Ethernet to a computer directly, the Internet Protocol Version 4 IP address must be set in the
network seng on the computer.
The first 3 numbers (separated by periods) of the Internet Protocol Version 4 IP address
should match that of the BSG3 being used, while the last number remains different. For
example, if the BSG3 IP address is the default 192.168.1.50, the Internet Protocol
Version 4 IP address can be set to 192.168.1.3.
To do this, open Network and Sharing Center on the computer. Open the Ethernet
Connecon (or Local Area Connecon) labelled “Unidenfied network”, then
open Properes. From the List, select Internet Protocol Version 4 and then click
Properes, where the IP address can be set.

PRESS BOTH BUTTONS
AT THE SAME TIME
1
SCROLL UP UNTIL THE
STAR IS PLACED ON
THE LEFT SIDE OF THE
UPPER TITLE
2
USE UP AND DOWN BUTTONS TO SCROLL
U P A N D DO W N T H R O U G H T H E
DIFFERENT SCREENS
USE UP AND DOWN BUTTONS TO SCROLL
UP AND DOWN THROUGH THE DIFFERENT
SCREEN PARAMETERS
USE UP AND DOWN BUTTONS TO MODIFY
THE SELECTED PARAMETER
UPPER LEVEL MENU SUBMENU PARAMETER
MODIFICATION
* DEVICE PARAMETERS
DEGREE: C
LOG RATE: 1 MIN
MOD PORT: 502
SLAVE ID: 7
BAUD: 19200
* IP PARAMETERS
MAC A4:3B:FA:24:93:E2
GATE 169.254. 1. 1
MASK 255.255. 0. 0
IP 169.254. 1. 1
* TEMPERATURE ( C )
25 27 24
25 26 24
28 24 22
* BSG3.9S INFO
FW: 30036:0.00.21
HW: 10121
S/N: 300002
15:17:11 17/03/2014
DEVICE PARAMETERS
DEGREE: C
LOG RATE: 1 MIN
MOD PORT: 502
SLAVE ID: 7
BAUD: 19200
DEVICE PARAMETERS
DEGREE: C
LOG RATE: 1 MIN
MOD PORT: 502
SLAVE ID: 7
BAUD: 19200
*
>
1
21
* FIBER POWER
0 9 0
9 9 9
0 9 0
* ALARM STATUS
- E -
A - W
- - -
* BRITEALERT
STATUS: WARNING
ERROR NUM 1
01 05
* ALERT CONFIG
SOUND: OFF
* SET THRESHOLD (C)
WARNING: 90
ALARM: 105
BRITEALERT
STATUS: WARNING
*ERROR NUM 1
01 05
1
2
BRITEALERT
STATUS: WARNING
>ERROR NUM 1
01 05
ALERT CONFIG
*SOUND: OFF
1
2
ALERT CONFIG
>SOUND: ON
SET THRESHOLD (C)
WARNING: 90
*ALARM: 105
SET THRESHOLD (C)
WARNING: 90
>ALARM: 105
1
2
Quick Start Guide
The BSG3 is equipped with a simple LCD display and a set of buons which allow for navigaon as well as basic data display and
configuraon as shown below.
Navigaon Map
G3
BriteSpot
Temperature Monitoring
Powell Canada Inc,
Suite 201, 55 Gosck Place
North Vancouver, BC, V7M 3N2
Popular Temperature Controllers manuals by other brands

LumaSense technologies
LumaSense technologies LumaSmart quick start guide

S+S Regeltechnik
S+S Regeltechnik THERMASGARD RTM 1-Modbus Operating and mounting instructions

KELD
KELD KLTX3 Specification and operating instructions

IBEST
IBEST TCL SERIES user manual

meitav-tec
meitav-tec ETN-Z100 owner's manual

LaserLiner
LaserLiner ThermoSensor Clamp operating instructions