Polyaire Zonemaster User manual

SINGLE ZONE
CLIMATE ZONING
SYSTEM
Technical Manual
Polyaire™ Pty Ltd
11-13 White Road
GEPPS CROSS
South Australia, 5094
Tel: (08) 8349 8466
Fax: (08) 8349 8446
www.polyaire.com.au


CONTENTS
Features 1
Application 1
Components 2
Connection Diagram 3
Installation 3
Commissioning Instruction 5
1. Initiating and Exit Setting Process 5
2. Room Temperature Sensor 5
3. Minimum Ventilation 5
4. Damper on/off Test 6
Trouble Shooting Guide 6
User Manual 7
Programming Mode 8
Appendix A - Specications 14
Appendix B - Single VAV Product Code 15
Liability
Please read the instructions before installing this Zonemaster System.
Polyaire Pty Ltd does not accept any responsibility for loss or damage that
may occur as a result of the installation of this System.

FEATURES
• Manual and programmable zone temperature control.
• Maintains room temperature within ±1°C using an onboard sensor.
• LCD indicator for zone status and parameter display.
• User-friendly temperature and program setting.
• Real time clock with battery backup.
• 5-1-1 programmable temperature setting and start time.
• Returns to last setting after power drop.
• Programmable minimum ventilation.
• Max (or fully open) control.
APPLICATION
Zonemaster single VAV system is a fully featured and engineered system
that is well suited to all ducted, reverse cycle, heating and evaporative
air conditioning systems for light commercial, residential or apartment
applications. It is especially designed for an area with dynamic heat loads,
and where a constant or exact temperature is required.
Page 1

COMPONENTS
1) Touchpad
User can input control commands from the touchpad to turn a
zone on/off and set temperature. The LCD on the touchpad
displays clock, room temperature and zone status.
2) Damper Motor (Yellow)
Damper Motor drives the blade of the damper to modulate
the air from ducting to the zone.
3) Supply Air Sensor
Supply air sensor measures the temperature of the supply air
for cooling/ heating mode detection.
4) Power Supply
The 24VAC transformer provides power to the touchpad
and damper.
5) Battery
3.6 V rechargeable battery for real time clock backup.
6) Central Latch Triple Adaptor
Connects the touchpad to the damper motor and power supply
7) Mounting Bracket
8) Control Cable Premade 7m
Page 2

Page 3
CONNECTION DIAGRAM
The cabling of the Zonemaster single VAV system is straightforward.
The touchpad connects the damper motor and power supply in serial via
an adaptor, and the temperature sensor can be plugged into the socket on
the back of the touchpad, as shown in Figure 1.
Figure 1. Wiring Diagram
INSTALLATION
1) Plug the 24VAC power supply
into the power-in port and
a pre-tested control cable
into the touchpad port in the
adaptor. Plug the adaptor into
the damper.
Warning
- Zonemaster components
are not compatible with
other motors.

Page 4
2) Connect the pre-tested
cable to the touchpad.
3) When power is applied,
the LCD screen on the
touchpad should show
clock time and the
temperature where the
touchpad is located.
Otherwise, check the
power supply and the
cable.
4) Turn off the power and disconnect the
touchpad. Position the touchpad at the right
place. Ideally, its position is approximately
1.6M off the oor on the wall. Fit the cable
through the wall cavity and connect the
touchpad again.
Please note that the touchpad should not be exposed
to directs sunlight and other heat sources.
5) Mount the supply air sensor in the supply air
duct upstream from the motorised dampers.
Fit the sensor cable through the wall cavity
and plug into the socket on the back of the
touchpad.
6) Connect the battery by plugging into the socket
on the back of the touchpad.
7) Mount the touchpad onto the bracket in the wall
cavity. Connect the cable to the 24VAC power
supply. The LCD should show clock time and
temperature.

COMMISSIONING INSTRUCTION
The Zonemaster single VAV has two parameters, room temperature and
minimum ventilation, that should be set in the commissioning stage.
1. Initiating and Exit Setting Process
1) Hold down both and buttons for
about 5 seconds until the LCD displays ‘Setting’
on the top line of the LCD screen.
2) At the setting mode, pressing button at
any time will return to the normal operation
mode.
2. Room Temperature Sensor
The touchpad has an onboard sensor for temperature control. The sensor
can be calibrated to provide more accurate temperature control as follows.
1) Using an accurate probe to measure the
temperature of the area you want to calibrate
and record the value.
2) At the setting mode, press button until
the LCD displays the ‘Sensor’ screen.
3) Press or button to adjust the
displayed value to the value recorded.
3. Minimum Ventilation
Customers may prefer minimum ventilation during the climate control. This
ventilation allows a minimum airow into the zone that is switched on. The
amount of ventilation can be set from 0 to 30% open with a default of 0%.
1) At the setting mode, press button until
the LCD displays the ‘Min Vent’ screen.
2) Press or button to adjust the
percent value of the minimum ventilation as
desired.
Page 5

Page 6
4. Damper on/off Test
1) Switch on the air conditioner.
2) Press button to turn the zone on or off to check if the damper is
correctly connected by feeling the air at the outlet. Refer to User’s
manual for the operation.
TROUBLE SHOOTING GUIDE
Problem Suggested Action
Nothing is showing
on touchpad LCD.
• Check the power supply.
• Check the cable and plug to the touchpad.
Touchpad display is
not normal.
• First disconnect the battery.
• Reset the touchpad by turning the power
supply off and on. If the display is normal, plug
in the battery again.
No response from
dampers when
turning on or off.
• Check the connection between the touchpad
and the damper motor.
• Check the 24V AC power supply.
Temperature is
beyond ±1°C range.
• Air Conditioner does not have enough capacity
for the area.
• Too much air coming from other areas.
Please contact distributors for any other
problems not listed as above.

Page 7
USER MANUAL
The single VAV touchpad has an LCD screen and six buttons, as shown in
Figure 2. In normal operation mode, the LCD screen will display clock time
and the temperature at the location of the touchpad.
Figure 5. Layout of the single VAV Touchpad
Zone On/Off Control
1) In ‘on’ status, the LCD of the touchpad displays
the zone temperature or setpoint. Press
button once to turn off the zone and the
second line of the screen will display ‘off’.
2) In ‘off’ status, pressing button once will
turn on the zone and the second line of the
LCD screen will display the setpoint of the
zone for 15 seconds, and then will return to the
normal display of the zone temperature.

Page 8
Zone Temperature Setting
1) In ‘on’ status, press or button
once to allow the setpoint of the zone to be
displayed on the second line of the LCD.
2) Press or button again to adjust
the setpoint to the desired value.
3) The screen will return to zone temperature
display in 15 seconds with no key being
pressed.
Maximum Damper
1) Press button once, the barrel damper
will be fully opened and the screen will display
‘MAX’ on the second line.
2) In MAX status, press button again to
return to the normal operation mode.
Programming Mode
Programmable zone temperature control is an important feature of
the Zonemaster single VAV system. This system has a 5-1-1 program
capability which means the system has an individual program for
weekdays (Monday to Friday), Saturday and Sunday respectively. Each
program has 4 programmable events per day: Wake, Day, Back and
Sleep, which can be turned on or off individually. For these events, the
user can adjust the start times and the cooling/heating temperature setting.
In order to use the program, the user has to enable the program during the
setup.
The Zonemaster single VAV system provides a battery backup real time
clock to support the programming mode. The program is set in default
mode from the factory with the settings listed in the following table.

Program Wake Day Back Sleep
Monday
to
Friday
Start time 6.30AM 8.00AM 5.30PM 10.00PM
Set cool 24°C off 24°C 30°C
Set heat 21°C off 21°C 17°C
Saturday
Start time 7.30AM 12.30PM 6.00PM 11.30PM
Set cool 24°C 24°C 24°C 30°C
Set heat 21°C 21°C 21°C 17°C
Sunday
Start time 7.30AM 12.30PM 6.00PM 11.30PM
Set cool 24°C 24°C 24°C 30°C
Set heat 21°C 21°C 21°C 17°C
The above default settings are explained as follows;
Monday to Friday:
6:30AM Wake, the zone turns on with a setpoint of 24°C for cooling mode
and 21°C for heating mode.
8:00AM Day, the zone turns off.
5:30PM Back, the zone turns on again with a setpoint of 24°C for cooling
mode, and 21°C for heating mode.
10:00PM Sleep, the zone’s temperature setpoint is set to 30°C for cooling
mode and 17°C for heating mode.
Page 9

Page 10
Saturday:
7:30AM Wake, the zone turns on with a setpoint of 24°C for cooling mode
and 21°C for heating mode.
12:30PM Day, the zone’ s temperature setpoint is set to 24°C for cooling
mode and 21°C for heating mode.
6:00PM Back, the zone’ s temperature setpoint is set to 24°C for cooling
mode and 21°C for heating mode.
11.30PM Sleep, the zone’ s temperature setpoint is set to 30°C for cooling
mode and 17°C for heating mode.
Sunday:
The program is the same as Saturday’s.
Setting Clock and Week
1) Press button once to select the clock
and week setting.
2) Use or button to change the
ashing hours to the desired value.
3) Press button once more to select the
minutes to be ashing.
4) Use or button to change the
ashing minute to the desired value.
5) Press button again to select week to
set.
6) Use or button to change the
weekday to the desired day.
7) It will return to the normal operation mode itself
in 15 seconds with no key being pressed.

Adjust Program Time
1) Press button twice, the LCD shows
the program status.
2) Factory default status of the program is
disabled that means no program control.
Pressing button once will enable the
program.
3) In enable status, pressing button will
select each of the program data to be adjusted.
At the rst screen, it shows the start time of the
Wake event of the program for Monday to
Friday.
4) Use or button to change the
ashing hours to the desired value.
5) Press button once to select minutes,
and repeat step 4) to change the minutes.
6) If you do not want the event to happen press
button to disable it.
7) Press button again, the LCD will show
the temperature setpoint for cooling mode of
the event.
8) Use or button to change the
setpoint in cooling mode to the desired value
or press button to turn off the zone at
the start time in cooling mode.
9) Press button again, the LCD will show
the temperature setpoint for heating mode of
the event.
10) Use or button to change the
setpoint in heating mode to the desired value
or press button to turn off the zone at
the start time in heating mode.
Page 11

11) Press button again, the LCD will show
the start time of the Day event of the program
for Monday to Friday.
12) Follow step 4) to 10) to set the start time and
cooling/heating setpoint of Day event or
disable the event.
13) Press button again, the LCD will show
the start time of the Back event of the program
for Monday to Friday.
14) Follow step 4) to 10) to set the start time and
cooling/heating setpoint of Back event or
disable the event.
15) Press button again, the LCD will show
the start time of the Sleep event of the program
for Monday to Friday.
16) Follow steps 4) to 10) to set the start time and
cooling/heating setpoint of Sleep event or
disable the event.
17) Follow steps 3) to 16) to adjust the Saturday
program.
18) Follow steps 3) to 16) to adjust the Sunday
program.
19) It will return to the normal operation mode
itself in 15 seconds with no key being pressed.
Page 12

Programming Information Sheet
The following program tables are designed to assist the user in
programming.
Program Wake Day Back Sleep
Monday
to
Friday
Start time
Set cool
Set heat
Saturday
Start time
Set cool
Set heat
Sunday
Start time
Set cool
Set heat
Page 13

Page 14
APPENDIX A - TECHNICAL SPECIFICATIONS
Electrical Requirements
Power supply 24VAC ± 10%
Line frequency 50 Hz
Components Power Consumption
Touchpad 0.5 VA
Damper controller 2.5 VA
Environmental Requirements
Operating temperature 0°C to 60°C
Altitude 0 to 2000 metres
Operating relative humidity 10% to 80%
Avoid static electricity hazards
Avoid electromagnetic radiation sources
Avoid dust contamination
Avoid highly corrosive environments
Touchpad
Power input 24VAC 50Hz
Dimensions 78mm Wide x 118mm High
x 13mm Deep
Transformer
Input Voltage 240VAC, 50Hz
Output Voltage 24VAC, 50Hz
Wattage 24W
Supply Air Sensor NTC type, 10kΩ at 25°C
Battery AAAM rechargeable battery, 3.6V

Page 15
Code Items Description
7153 Zonemaster Single
Zone VAV
Single zone VAV touchpad (1)
Rechargeable battery (1)
Adaptor (1)
Mounting bracket kit (1)
Technical manual (1)
7186 Supply Air Sensor Supply air sensor with 7M lead
7155 NEAT 24V
Transformer Plug 24V transformer with plug
7161 Control Cable 7M Pre-made control cable 7M
APPENDIX B - SINGLE VAV PRODUCT CODE


by
Table of contents
Other Polyaire Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Fike
Fike FIK-2351T Installation and maintenance instructions

Tekmar
Tekmar tN2 house control 400 Installation and operation manual

LP-RESEARCH
LP-RESEARCH LPMS-B2 manual

ISG INFRASYS
ISG INFRASYS E380 operating manual

Viessmann
Viessmann VITOPLANAR Installation and operating instructions

Carrier
Carrier ZONECC2KIT-B Installation and start-up instructions

OJ
OJ ETOG-55 instructions

Omron
Omron E5CD-B manual

Rheem
Rheem Raypack Temp-Tracker B-40 Installation & operating instructions

WallyHome
WallyHome 810-00008 product manual

Platinum CCTV
Platinum CCTV PT-BF5421-T Installation and setup

S+S Regeltechnik
S+S Regeltechnik HYGRASGARD RFF-UP Operating Instructions, Mounting & Installation