Powersolve HSEUiREG07201 Series User manual

HSEUiREG07201(R2) MANUAL
HSEUiREG07201
72
0W Lab Power Supply
DIN
-
Rail
Features
:
•Real time voltage programming
•Real time & value C/V-monitoring
•Reference voltage f. autonomous programming
•Remote Shutdown
•Sense control 2V per load line
•Power Good Relay DC-ok
•Quick down programming option PS
•Precise dynamics on load change
•Series & parallel operation N+1
•Natural convection
•Electronic Inrush Limiter 13,8Arms
•Up to 90% efficiency
•EMI/EMS EN61000-6-2,3, EN55032 class B
•EN61010-1, EN61010-2-201, EN62368-1
Model
Voltage
programmable
Current
programmable
HSEUiREG0
72
0
1
.018
0
–
18Vdc
0
–
40
,0
A
HSEUiREG0
72
0
1
.0
30
0
–
30Vdc
0
–
30
,0
A
HSEUiREG0
72
0
1
.0
50
0
–
5
0Vdc
0
–
1
8
,0
A
HSEUiREG0
72
0
1
.0
90
0
–
60Vdc
0
–
15,0A
HSEUiREG0
72
0
1
.0
90
0
–
90Vdc
0
–
10
,0
A
HSEUiREG0
72
0
1
.
130
0
–
1
3
0Vdc
0
–
7,0
A
HSEUiREG0
72
0
1
.18
0
0
–
180Vdc
0
–
5
,0
A
HSEUiREG0
72
0
1
.
240
0
–
240Vdc
0
–
3,
8
A
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Technical description
The Camtec HSEUiREG models are high-precision lab power supplies „Made in Germany“. These
power supplies are designed for power systems in the testing automation.
For more than 25 years the Camtec Power Supplies manufactures high-end switch mode power supplies in
Germany. A field breakdown of below 0,004% over a 10-year period under review approves our ambitious
quality concept. Each manufactured Camtec product passes several 100% tests for each detailed function and
a full-load Burn-In test.
Although it is not required from the safety norms our production applies a routine safety test to each
manufactured device, even if it is an extra low-voltage model. The components in the assembled device pass
stress aging to achieve an even level and to prevent from delayed failures. Our internal product engineering
guidelines provide a clear target: Camtec product reputation must say „mount and forget“. Quality is never a
mere promise for our team.
The HSEUiREG laboratory power supplies provide low noise and ripple, a very quick programming, and a
precise setting at high load changes. With an efficiency up to 90% the devices are highly energy efficient.
Equipped with high-end capacitors of outstanding lifetime our power supplies guarantee a very long and
reliable operation time. The circuit design of the HSEUiREG Series allows cope playing with complex loads.
The internal protection circuits protect the power supply and the connected system, even in exceptional
situations. The HSEUiREG series is protected from high transients by strong filters with high energy efficiency.
All inputs and outputs are electrically isolated. The design specifications call for the highest standards of safety
and interference suppression. The unit is designed in accordance with the EN61010-1, EN61010-2-201,
EN62368-1, EN60950-1, and the EMC-compatibility with EN55032.
The special heat emission design supports easy baseplate cooling with the help of an optional wall mount
plate.
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Features
Idling behavior
The HSEUiREG Series is permanently open-circuit proof.
When an output voltage is preset it comes stable. If a load is
switched suddenly, the unit stabilized within <1ms. An
overshoot of the output voltage is irrelevant.
Start behavior
The power supply has a start delay of 420ms to stabilize all
measuring circuits for the interface messages accurately.
The power supply starts with a ramp (soft start) of 100ms.
The output voltage does not overshoot - regardless of
whether a load is connected or not.
Galvanic isolation and insulation
The switching power supply is galvanically isolated between
the input and the output. The sensing, Ureg, Ireg, Umon,
Imon and Iref are connected to the DC power output.
Voltage programming (Ureg)
The output voltage of the HSEUiREG power supply can be
adjusted by a control signal. The setting is linear to the input
signal.
Current programming (Ireg)
The output current of the HSEUiREG power supply can be
adjusted by a control signal. The setting is linear to the input
signal.
Voltage Monitor (Umon)
The power supply provides real-time monitoring of the output
voltage. It is the exact and real value at the output terminals.
If the sense line is used, the real value is measured directly
at the load. The latency signal preset to the measured value
is negligible since the control circuit is constructed
completely analogously.
Current Monitor (Imon)
The power supply provides real-time monitoring of the output
current. It is the exact and real value at the output terminals.
The latency signal preset to the measured value is negligible
since the control circuit is constructed completely
analogously.
Constant Voltage or Constant Current Mode (CV/CC)
The device can optionally be operated as a DC voltage
source or a constant current source. The operating mode is
signaled via LED.
Reference Voltage (Uref)
The devices feature an auxiliary reference voltage to operate
external potentiometers. The Uref voltage can be set to 5,2V
or 10,4V 5mA via the DIP-switch.
Sense Mode
The power supply has a sense mode to compensate for
voltage drops of 2V per load line.
External Shutdown (SD)
All the models are featured with an external shutdown
(switch/open collector)
Digitale Interface
The standard equipment of the power supply is an analog
interface.
Optionally, the unit can be equipped upon request with a
digital USB 2.0 interface. Options include a software and a
DOM interface for easy control over standard software like
LabView or others.
DC Power Good Relay
The power good relay connection indicates over device
temperature and low AC supply voltage.
Over Temperature Thermal Shutdown (OT)
The device has a thermal monitoring: shutdown with
automatic restart.
Fast Down Programming & PowerSink (PS)
For fast down programming an internal PowerSink is offered
as an option. The current sink discharges the output
electrolytic capacitors and eleminates back feed energy.
A further output allows to control external PowerSink
modules. The internal current sink for quick programming
must be installed at the factory.
ST-HD (ST Heat Dissipation)
Our aligned and controlled heat dissipation design opens
possibilities that are formerly being reserved to custom
design power supplies: Hard mount of the HSEUiREG power
supply modules on a wall allows easy access to base plate
cooling.
In practice that means that one can mount the modules onto
a thermal conducting wall to unsure that a sigificat part of the
losses wil be transported directly out of the power supply
unit.
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Technical Data Table
AC Input Range
90
-
132Vac, 184
-
264Vac
(115/230Vac input
selector, factory setting is 230Vac)
AC I
n
put Frequency
47
-
63Hz
DC Input Range
250
-
375Vdc
(input selector set to 230Vac)
AC Input Rated
115Vac <
12,7
A, 230Vac <
7,2
A
DC
Input Rated
250Vdc
<
3,6
A
375
Vdc
<
2,4
A
DC V
oltage
programmable
0
-
18Vdc
0
-
30Vdc
0
-
50Vdc
0
-
60Vdc
0
-
90Vdc
0
-
130Vdc
0
-
180Vdc
0
-
240Vdc
DC C
urren
t programmable
0
-
40A
0
-
30A
0
-
18A
0
-
15A
0
-
10A
0
-
7
A
0
-
5
A
0
-
3
,8
A
Over Voltage Protection
22Vdc
35Vdc
59Vdc
70Vdc
105Vdc
150Vdc
210Vdc
280Vdc
Over Current Protection
44A
33A
19,8A
16,5A
11A
7,7A
5,5A
4,2A
Ripple Noise 230Vac 20MHz
40mVpp
40mVpp
100mVpp
120mVpp
150mVpp
200mVpp
300mVpp
400mVpp
Load Regulation 0
-
100%
< ±0,05%
< ±0,05%
< ±0,05%
< ±0,05%
< ±0,05%
< ±0,05%
< ±0,05%
< ±0,05%
Power Maximum
72
0
W
, 90
-
132Vac, 184
-
264Vac
Cooling
Natural convection
Efficiency
Up to
9
0
%
230Vac
at full load
Short Circuit Resistance
yes
Open Circuit Protected
yes
Base Load (OCP)
Non required
(
open circuit protected
)
Load
Regulation Time
<1ms on load switch 10
-
100%
Accuracy
Ureg:
≤
± 0,
5%
,
Ireg:
≤
± 1
,5
%
,
Umon:
≤
± 0,5%
,
Imon:
≤
± 1
,5
%
, Uref:
≤
±1
,0
%
Temperatur
e Control
ye
s
, therm
al shutdown
& autorecovery
(+
6
0°C,
outside
measuring point distance
5
0mm)
Hold Up Time
>
4
0ms 230Vac
ma
ins buffering at full load
Inrush Current
<
9,8
A
rms
<
13,8
Apeak 230Vac
a
c
tive
electronic
inrush protection
(
no
simple
NTC)
MCB (Circuit Breaker)
16A curve
B
@ 230Vac
/ 25A curve B @ 115Vac
Start
-
up Delay
T
yp.
420m
s
@
230Vac, 590ms
@
115Vac
Softstart
T
yp. 100ms
Start
-
up from Shutdown
Typ.
33
0m
s
Ambient Temperature
-
2
0°C…+
6
0
°C
operating, derating 2,5%/°C >
5
0°C
Storage Temperature
-
40°C…+85°C
A
mbient Conditions
Humidity 95
%
non
-
condensing
@
25°C
, climate class 3K3,
pollution degree 2
ROHS
2011/65/EU, (EU)2015/863
REACH
EG No. 1907/2006
EMI
EN55032 class B, EN61000
-
6
-
3
EMS
EN61000
-
6
-
2
S
afety
EN61010
-
1, EN61010
-
2
-
201, EN62368
-
1,
EN60950
-
1,
EN60204
-
1
Protection
Class
I
PE connection
required
Isolation
Input to
Output
3000Vac
Isolation
Input to
Case
2500Vac
Isolation
Output to
Case
500Vdc,
≥
6
0Vdc
2
5
00Vdc
MTBF (IEC61709)
400
000h
(Meantime Between Failure
s
:
statistic
time
between failures
after
repairs
)
MTTF
(IEC61709)
14
7
212
h
(Meantime To Failure: statistic time to ever fails
)
Dimensions (HxWxD)
1
30
x
20
0x1
15
mm
Weight
3,1
k
g
/
6
,8
lbs
AC Terminals
Input Screw Terminal 3x 0,5
–
16mm²
AWG26
–
AWG6
(L,N,PE)
, technical data see “connections”
DC Terminals
Output Screw Terminal 4x 0,5
–
16mm²
AWG26
–
AWG6
(+ + /
-
-
)
,
technical data see “connections”
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Manual
a
nd Techni
cal Details
Programming Time Vout [ms]
Model
0
-
18V
0
-
30V
0
-
50V
0
-
60V
0
-
90V
0
-
130V
0
-
180V
0
-
240V
Rise Time
0
-
100%, 10/100% load, [ms] typ.
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
Slew Rate 90
-
10%, 10/100% load, [ms] typ.
37/3,7
104/10,4
51/5,1
74/7,4
57/5,7
53/5,3
100/10
83/8,3
Slew Rate PS
-
Option 100
-
0%, 0% load, [ms] typ.
100
100
100
100
100
100
100
100
Output Capacity, [mF] typ.
10,4
10,4
1,85
1,85
0,64
0,28
0,28
0,13
Analog
Interface
CON
-
A
(
Connector Model
Weidmue
ller
159746
0000
=
included
)
Pin
Name
Typ
e
Func
tion
Signal
Remarks
1
Ureg +
Input
Voltage Programming Select 0-5V, 0-10V,
0-20mA, 4-20mA
1 MΩworking resistance with Vprog
500 Ωworking resistance with Iprog
2
Ureg
-
Input
3
Ireg +
Input
Current Programming Select 0-5V, 0-10V,
0-20mA, 4-20mA
1 MΩworking resistance with Vprog
500 Ωworking resistance with Iprog
4
Ireg
-
Input
5
Umon +
Output
Voltage Monitor Select 0-5Vdc/5mA,
0-10Vdc/5mA
6
Umon
-
Output
7
Imon +
Output
Current Monitor Select 0-5Vdc/5mA,
0-10Vdc/5mA
8
Imon
-
Output
9
SD +
Input
Control Signal Shutdown
Switch / Open Collector
10
SD
-
Input
11
Uref +
Output
Reference Voltage Select 5,2Vdc or 10,4Vdc
5mA
1
2
Uref
-
Output
Analog Interface
CON
-
B
(Connector Model Weidmueller 1
597
4
0000 = included)
Pin
Name
Type
Function
Signal
Remarks
1
DC
-
OK
Output
Closers, Signal DC OK Relay Potential-free break contact
2
DC
-
OK
Output
3
AUX +
Output
4
Sense +
Input
5
Sense
-
Input
6
AUX
-
Output
Analog Interface CON
-
C
(Connector Model Weidmueller
1597360000
= not included)
PS +
PS +
Output
External Power-Sink Trigger This connection is without function
for the standard HSEUiREG1500
PS
-
PS
-
Output
Configuration of the Analog Interface via Dip
-
Switch
Mode
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
0
-
5V
0
0
0
0
0
1
0
0
0
0
0
-
10V
0
1
0
0
1
0
0
1
1
1
0
-
20mA
1
1
0
1
1
0
0
1
1
1
4
-
20mA
1
0
1
1
0
0
1
1
1
1
LED Signal Indication
LED Over Temp. Shut Down Constant [V] Constant [C]
CV OFF OFF ON OFF
CC OFF OFF OFF ON
OT ON OFF OFF OFF
SD OFF ON OFF OFF
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Monitor Outputs
Monitor Connections
Potentiometer Programming
Programming Inputs
Shutdown
Power OK Relay
LED Indication
CV
GRN
Constant
voltage
CC
YEL
Constant current
SD
YEL
S
hutdown
OT
RED
Over temperature
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Programmi
ng
/
Monitoring V/C
A
nalog
Interface
(Ureg
/Ireg)
(Umon/Imon)
The standard programming of the HSEUiREG Series is an analog interface. The output voltage is linearly
proportional to the adjusted analog control signal. If the control signal 0V and/or 0A applies the power supply
delivers 0V at the output. The power supply is already working from 0V output voltage and low load with high
precision.
The monitor signal is analog linear to the output voltage. The monitor signal for current and voltage is the real
value that is measured directly at the output of the power supply. If a sense line is connected to compensate for
the voltage drop across the load lines, the monitor signal is exactly the value that is measured at the connection
point of the sense line. The description of the power supply in the sense operation is carried out in a separate
section.
The analog inputs and outputs are non-floating. The mass is connected to the DC negative output.
The adapter provides the ability to select the desired input / output via a DIP switch. The burden of the control
voltages is 1MΩ. The burden of the current interface is 500Ω. The latency to full compensation of V/C on the
interface from 0-100% is 15ms for all HSEUiREG models.
If the power supply is operated with a low load, the down-programming time up to the desired set point may be
very long. The power supply has large built-in capacitors and an enormous energy reserve. A similar effect
occurs by skidding input energy, which is not easily removed from the power supply. A PowerSink (PS) modul
can be ordered as an option for each HSEUiREG power supply unit. The PS option is used for fast down
programming and the degradation of skidding energy fed. The option must be equipped in the factory.
For further information about the PS option, please refer to the technical details in a section PS-option.
C
ompensation
of Load
Line Drop Voltage
(Sense +/
-
)
,
standard operation mode
The HSEUiREG power supply has a Sense Mode to compensate for the voltage drop over long load lines. The
compensation amounts to a maximum of 2V per load line. Under certain circumstances, it can be expected to
apply more complicated external interference suppression. If sense is not used, Sense + and Sense - shall
necessarily be connected by short bridges to AUX + and AUX - (factory setup). Make sure that +/- connections
are matching! WARNING! Reverse polarity of the sense lines can cause damages to the power supply unit.
Sense operation: Remove the bridges between Sense +, Sense -. Connect the sense lines directly to the load.
Pay attention to the polarity of plus and minus of the load to prevent damage to the power supply. To avoid
interference, twist the sense lines. To reduce inductive effects, we recommend that the load lines position is
close to each other. To supply a pulsating load, the use of an electrolytic capacitor and a cermic capacitor has
proved. The internal Over Voltage Protection (OVP) of the power supply controls the DC power directly to the
DC output terminals. In case of an error the OVP acts automatically (see OVP values corresponding table).
The sense terminals are directly connected to the power outputs.
Lokal Sensing Remote Sensing
(factory setup) (twisted sense lines)
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Compensation Load Line Voltage
Drop
(Sense ++/
--
)
battery
c
harger
operation mode
Remote Sensing as a battery charger
If the HSEUiREG power supply unit is used as a battery charger, it is recommended to refrain from sensing. It
can lead to severe damage to the power supply, if the polarity of the sense line is confused (field experience:
such error often occurs when system service is required, e.g., when the batteries are changed). If it is
necessary to use sensing, proceed as described in the figure below. Proven approaches are 250mA for the
fuses and 3...5A load capacity of diodes.
WARNING! Reverse polarity of the sense lines can cause damages to the power supply unit.
External Shutdown (
SD
)
The power supply is set to the Shutdown mode, when the
control input is either shorted via a relay contact, a switch
contact or an NPN transistor with open collector (voltage drop
<1V, current typ. 2mA).
If the shutdown repeals the power supply starts again.
Using the soft-start, the current and the voltage rises within
continuously to the default set values.
Power
-
OK Relay (DC Power Good)
The alarm signal DC OK has potential-free relay contacts. The contacts are closed (relay
coil is energized) when the power output is active. In shut dwon mode (SD) the contacts
are closed.
The contacts are open when the power output is inhibited by OT or low AC supply voltage
at the AC inputs. Contact load (resistive load): 30Vdc/1A, 60Vdc/0.3A, 30Vac/0.5A.
Over Voltage Protection
(OVP)
If an over-voltage occurs to the output (for example, defective components, external feed voltage), it is followed
by the shutdown of the power output. A periodic restart attempts (ticker operation period 400ms).
Over Temperature Shutdown
(OT)
The alarm LED OT lits when the temperature of the power supply is higher than the over-temperature
protection threshold.
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
C
/
V Chart and Operating Point
The output voltage set Vout is always linear proportional to the control signal Ureg.
The desired control signal is selected via the DIP switcher:
0-5V, 0-10V, 0-20mA oder 4-20mA.
Model Value UA1 (V) Value IA1 (A) Value UA2 (V) Value IA2 (A) Pmax (IA1/IA2)
HSEUiREG07201.018 18Vdc 40,0A
18Vdc
40,0A
720/720W
HSEUiREG07201.030 30Vdc 24,0A
24Vdc
30,0A
720/720W
HSEUiREG07201.050 50Vdc 14,4A
40Vdc
18,0A
720/720W
HSEUiREG07201.060 60Vdc 12,0A
48Vdc
15,0A
720/720W
HSEUiREG07201.090 90Vdc 8,0A
72Vdc
10,0A
720/720W
HSEUiREG07201.130 130Vdc 5,5A
103Vdc
7,0A
715/721W
HSEUiREG07201.180
180Vdc 4,0A 144Vdc 5,0A 720/720W
HSEUiREG07201.240
240Vdc 3,0A 190Vdc 3,8A 720/722W
Inrush Current Protection (electronic)
The power supply unit has an electronic current limiter
(230Vac=9,8Arms/13,8Apeak).
It is a precisely working circuit instead of a usual simple NTC
solution. The accuracy is ±10%, regardless of the operating
temperature and the duty cycles (interval ≥10s). We
recommend the smallest circuit breaker a characteristic B
with 25A for 115Vac and with 16A for 230Vac.
Temperatur
e
Derating
The maximum ambient temperature during operation is + 60°C. If the
overtemperature protection is activated, the power supply is switched off.
The measuring point is 50mm outside the power supply. The power supply unit
starts automatically when it has cooled down.
Series Operation
Two or more units of the same model and output voltage can be operated up to a total voltage of 300Vdc in
series. Due to the dielectric strength of the internal components used, only the models with an output voltage of
90Vdc and later are approved for series operation. Other power supplies are not approved for series operation
above 60Vdc.
If the units are remotely controlled via the analog interface it is compulsory to use a potential-free control
voltage!
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Parallel
Operation
&
N+1 Decoupling
To increase the overall power of the power supply, two or
more devices of the same model with the same output
voltage may be operated in parallel. We recommend
using a busbar for the DC power connector. Make sure
that the cable lengths and cable cross-sections of all
power supplies to the busbar or to the star point are
identical. Allow proper connection for low contact
resistance. If you want to use the sensing function,
connect it also to the star point or busbar. To avoid
measurement errors, select the line length from the
neutral point or from the busbar to the load as short as
possible and use the maximum possible conductor cross-
section.
Up to 5 pcs HSEUiREG can be paralleled.
The HSEUiREG models have no internal O-ring diode, to
operate the devices redundant N+1. We recommend
using our RED00202 DIN-rail redundant device.
Electrical Safety (Factory
-
Test / Field
-
T
est Owner)
¹) ≥60Vdc= 2500Vdc
Type and factory test are the manufacturer. While repeating damage can
happen to the power supply unit. For the field test (owner) follow the below instruction:
a) Use suitable test equipment, raising the voltage slowly
b) Short circuit L1 and N, and all the DC output terminals.
c) Use only test voltages of 50/60Hz. The outputs are unearthed and
therefore they have no resistance to GND/PE.
d) If the residual voltage is ≥60Vdc, observe the safety standards.
Use only specially insulated screwdriver to trim the Ua/Ia.
T
A
B
C
1
)
D
Type Test
60s
2500Vac
3000Vac
500Vdc
500Vdc
Factory Test
5s
2000Vac
2000Vac
500Vdc
500Vdc
Field Test
2s
2000Vac
2000Vac
500Vdc
500Vdc
Cut
-
off
current setting
>20mA
>20mA
>1mA
>1mA
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Available Options
PS Option
for Quick Downward Programming
(PSOPT)
Quick Down Programming:
The input capacitance of a power supply can be discharged only slowly at low load. A quick downward
programming of the output voltage of an almost non-loaded power supply is not possible. This fact leads to
undesirably long cycle times on a test bench. The PS option works as an electronic circuit. It communicates
with the control circuit of the power supply and therefore permits a much higher dynamics of the system, as an
external passive base load.
Maximum continuous power capability is 5W. Maximum switching frequency is 1Hz. The switching frequency
must be reduced if external electrolytic capacitors are used.
Back-Feed Energy:
In the back-feed power by a consumer a regenerative current is charging the output capacitors. The output
voltage will increase. The following formula shows dv/dt=i/C.
When an electronic current sink is used, the output voltage remains constant at the set value. The current sink
provides a quick dynamic response.
Fig 1 Fig 2 Fig 3
A Power Sink (see Fig. 1) enables fast down programming at low load conditions or without a load. For
comparison, see Figure 2 (without) and Figure 3 (with PS option).
The PS-option must be installed in the plant because it is not accessible from the outside. It is necessary to
match the power supply after installation and perform electrical safety testing. We therefore recommend a
required a necessary PowerSink option to be purchased with the power supply unit.
Retrofit PS option:
Individual trained HSEUiREG dealer are pre-retrofit able. Alternatively, a HSEUiREG power supply may also be
sent to the factory. Please apply for this an RMA number from our service.
Test Certificate and Calibration
Optionally we offer with the delivery of a HSEUiREG power supply a Manufacturer's Inspection Certificate of
electrical setpoint / actual values. The power supply then is "calibrated". Such Manufacturers Calibration
Certificate for each power supply can uniquely be assigned via the device serial number.
A manufacturer calibration of a HSEUiREG can frequently be done via controlled recirculation on a regular
basis. Please request the help of your local HSEUiREG dealer or contact us directly:
service@camtec-gmbh.com
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Mechanics
ST
-
HD Baseplate
Cooling & Temperature Management
The temperature management of the HSEUiREG series provides a direct dissipation of the main energy losses.
The internal coolers of the output diodes and the power FETs connect to the back-plate cooler. It is possible to
dissipate about 40 – 50% of the energy losses out of a system while using the Baseplate cooling bundle
2201002001 to hard mount the unit to a plane and heat conductive surface.
64
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Mechanics & Installation Instruction of the
HSEUiREG
Stable metal/aluminium housing IP20. To allow adequate convection, a free air space of 50mm (top/bottom)
and 10mm (sidewalls) is required; and for active devices 15mm space from the sidewalls. For proper air
convection it is necessary to install the HSEUiREG. One can use the DIN-Rail installation (equiped standard)
with our patented 35mm DIN-Rail bracket according to EN60715. It is easy to mount/dismount while snaping it
onto the 35mm DIN-Rail - no tools necessary. A wallmount back plate (option) is availble, too.
It is not allowed to install the
HSEUiREG
in other mounting direction then
as shown
in the
drawings.
Back Plate Option / DIN-Rail Standard
(The HSEUiREG is always delivered for DIN-rail mount, the back-plate is an optional part that shall be mounted from the
customer. The threads from the DIN-rail mounting brackets shall be used. All screws are included into the Back-Plate Kit.)
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Connections
Clamping Yoke Connector Specifications
Input / Output connections Signal connections plugs
Tightening torque min. – max. 1,2 – 2,2Nm (blade 1,0x5,5 DIN5264 ) 0,2 – 0,25Nm (blade 0,4x2,2 DIN5264)
Touch-safe protection acc. to DIN VDE 0470 IP20 plugged/ IP10 unplugged Not applicable
Clamping range, min. – max. 0,5 – 16mm² / AWG26 – AWG6 0,2 – 1,5mm² / AWG28 – AWG14
Solid, H05(07) V-U min. – max. 0,5 – 16mm² 0,2 – 1,5mm²
Stranded, H05(07) V-U min. – max. 6 – 16mm² 0,2 – 1,5mm²
Flexible, H05(07) V-U min. – max. 0,5 – 16mm² 0,2 – 1,5mm²
w. plastic collar ferrule, DIN 46228 pt 4 min. – max. 2,5 – 10mm² 0,2 – 1,5mm²
w. wire end ferrule, DIN 46228 pt 1, min. – max. 2,5 – 10mm² 0,2 – 1,5mm²
Plug gauge in accordance with EN 60999 a x b; ø 5,4 x 5,1mm; 5,3mm 2,4 x 1,5mm; 2,3mm
Pitch (P) 10,16mm 3,5mm
Wire Stripping Length (fine wired)
Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length
0,25mm² H0,25/5 5mm H0,25/10 HBL 8mm
0,5mm² H0,5/6 6mm H0,5/12 OR 8mm
1,0mm² H1,0/6 6mm H1,0/12 GE 8mm
2,5mm² H2,5/12 12mm H2,5/19D BL 14mm
4,0mm² H4,0/12 12mm H4,0/20 GDR 14mm
6,0mm² H6,0/20 12mm H6,0/20 SW 14mm
10,0mm² H10,0/12 12mm H10,0/22 EB 15mm
The length of ferrules is to be chosen depending on the rated voltage. The outside diameter of the plastic collar should not be larger than
the pitch (P)
Ordering Information
Ordering Codes
Product Code
Info
rmation
Article Number
HSEUiREG
0
72
01
.018
(R2)
0
-
18Vdc
304108
4
0
0
1CA
HSEUiREG0
72
01.030(R2)
0
-
30Vdc
304108
4
002CA
HSEUiREG0
72
01.050(R2)
0
-
5
0Vdc
304108
4
003CA
HSEUiREG
0
7201.060(R2)
0
-
60Vdc
3041084021CA
HSEUiREG0
72
01.090(R2)
0
-
90Vdc
304108
4
004CA
HSEUiREG0
72
01.130(R2)
0
-
130Vdc
304108
4
005CA
HSEUiREG0
72
01.180(R2)
0
-
180Vdc
304108
4
006CA
HSEUiREG0
72
01.240(R2)
0
-
240Vdc
304108
4
007CA
HSEUiREG
0
7201
.018PS(R2)
PowerSink / Quick Downward Programming
304108
4
011CA
HSEUiREG
0
7201
.030PS(R2)
PowerSink / Quick Downward Programming
304108
4
012CA
HSEUiREG
0
7201
.0
5
0PS(R2)
PowerSink / Quick Downward Programming
304108
4
013CA
HSEUiREG
0
7201.060PS(R2)
PowerSink / Quick Downward Programming
3041084031CA
HSEUiREG
0
7201
.090PS(R2)
PowerSink / Quick Downward Programming
304108
4
014CA
HSEUiREG
0
7201
.
1
3
0
PS(R2)
PowerSink / Quick Downward Programming
304108
4
015CA
HSEUiREG
0
7201
.
18
0PS(R2)
PowerSink / Quick Downward Programming
304108
4
016CA
HSEUiREG
0
7201
.
24
0PS(R2)
PowerSink / Quick Downward Programming
304108
4
017CA
Certif
ica
te Calibration
Separate
works certificate
manufacturer
calibration
-
Back P
late Kit
Hart mount plate kit
including screws
2201002001CA
UI.DRIVE INTERFACE
USB2.0 Interface & software download
3041093001CA
www.powersolve.co.uk
020321

HSEUiREG07201(R2) MANUAL
Safety regulations: Please read these instructions completely before using the equipment. Keep these
instructions
on
to hand.
The device
may only be operated
by trained
specialist staff
.
Installation:
1) The device is designed for devices and systems
that meet the standard requirements for hazardous
voltages, power, and fire prevention.
2.) Installation and service only by trained specialists.
The AC power must be switched off. The work is to be
labelled; accidental reconnection of the system must
be prevented.
3.) Opening the device, its modification, loosening
bolts, or operation outside the specified herein
specification or in an unsuitable environment, has the
immediate loss of warranty to follow. We disclaim any
responsibility for any resulting damage to persons or
things.
4.) Note: The device must not be operated without an
upstream circuit breaker (CB). We recommend the use
of B-Type 16A for 230Vac and 25A for 115Vac. It is
prohibited to use the unit without PE. It may be
necessary upstream device has a power switch.
Warning:
Non-compliance these warnings can result in fire
and serious injury or death.
1. Never operate device without PE connection.
2. Before connecting the device to the AC
network, make wires free of voltage and ensure
that it cannot accidentally switch on.
3. Allow neat and professional cabling.
4. Never open nor try to repair the unit. Inside
are dangerous voltages that can cause electrical
shock hazard.
5. Avoid metal pieces or other conductive
material to fall into the item
6. Do not operate the device in damp or wet
conditions
7. Do not operate the unit under EX-conditions
All parameters after 15 minutes of continuous operation at full load / 25°C / 230Vac 50/60Hz, unless otherwise indicated.