Powrmatic MC300 multi User manual

MC300 Multi User Instructions Issue 1.3 June 2015
Every effort is made to ensure accuracy at time of going to press. However as part of our policy of continual product improvement, we reserve the right to alter specifications without prior notice.
HEATING DIVISION
Hort Bridge
Ilminster, Somerset TA19 9PS
Tel: 01460 53535 Fax: 01460 52341
BSI Registered Firm
FM 414
Ind. & Comm. Air Heaters;
Air Moving Equipment;
Flues & Chimneys; Natural
Smoke & Heat Ventilators;
Powered Supply & Extract
Fans & Systems. ISO 9001
Users
Instructions
MC300 Multi
with Remote Units

1
1. General Description
The MC300 Multi is a high specification heating controller to meet the demands of modern fuel efficient heating equipment
and the latest energy saving and environmental guidelines.
It is designed to control up to 5 heaters using 24V DC signals over small diameter multicore cable. The MC300 Multi is the
master unit and each controlled heater is fitted with a remote board to interface the MC300 Multi signals with the heater
controls.
Optimum start technology is available that will continually monitor the heating systems previous performance to determine the
optimum time to turn the heating on to raise the space temperature to the required level for when occupancy begins. Optimum
stop can also be selected which can save energy at the end of the heating period.
The control uses a simple menu based structure for entering User settings and is protected by 2 levels of password. The User
password may be set to restrict access to certain User controls. The second password is for use by commissioning and servicing
engineers and allows access to parameters normally used only in the initial setting of the controller, a fault log and system reset
facility.
The user keypad allows easy selection of the heating and fan only modes, the override functions and fault reset. These may
also be locked in various combinations to allow different levels of user accessibility.
The MC300 Multi can give a readout of the hours the burner has operated, to help accessing servicing intervals and after being
programmed with the correct data, can also give an indication of the running costs of the heating appliance. In addition a
forward service date can be programmed. When the due date is reached a notification will be shown which alternates with the
normal display. This notification can only be removed by a Service Engineer.
The MC300 Multi can be used to directly control both Hi/Lo and Modulating burners, the latter by an internally generated
0-10V signal.
2. Specifications
MC300 Multi
General
Electricity supply 230V 50Hz Fused at 6A.
Internal Fuses F1 20mm 6.3A 230V.(HRC), F2 20mm 500mA 230V. (Non replaceable)
Display 2 line 5mm L.C.D.
Day set point range 10 - 30°C.
Night set point range 1 - 15°C.
Temperature accuracy 0.5 °C.
Overall switching differential Adjustable 0.5 - 10.0°C for Hi/Lo burner types.
Sensing Element Internal or remotely mounted up to 100m from control.
Switching contacts ratings 12A. 230V.ac. (resistive). All Volt Free
Modulating Control 0-10V dc
Heating ON Indicator Green L.E.D. when the heater is a single-stage burner, Red when the burner is a
Hi-Low type, and Yellow when the burner is a Modulating type.
Fault (Lockout) Indicator Orange L.E.D.
Protection Rating IP20
Clock
- The unit date range is from 01/01/2001 to 31/12/2099
- Leap years are recognised
- BST begins on the last Sunday in March and ends on the last Sunday in October. The time changes at 01:00 GMT.
- The clock may gain or lose up to 10 minutes in a year.
Time Switch
- 14 timers are provided in the software, and each can be assigned to any single day of the week, or to day groupings such as
weekdays or weekends. This allows greatest flexibility in operating the heating whenever required.
- It is possible to schedule timers so that one starts before another has finished. The heating will be on while any timer is
requiring Heat On, and the heating will turn off only when all timers have reached Heat Off. The requested temperature will
be set by the most recent timer to switch On. When an overlapping timer switches Off, the requested temperature will be set
by the remaining timer(s).
- No timer can be programmed to run past midnight, because it is assigned to a day of the week. If timed heating is required
across midnight, it must be provided by two timers, one ending at 23:59 and the other starting at 00:00. At midnight, all manual
over-rides and extensions are cleared.
Optimum Start
- The MC300 multi achieves Optimum start by keeping a moving record of how many minutes it takes to increase the
temperature per degree in each 3° band of temperature from 5°C to 20°C. The current overnight temperature is referenced and
the MC300 can estimate how many minutes are required to bring the temperature to the required level. When Optimum Start is
enabled the switch-on time for the heater is then advanced accordingly to achieve the required temperature by the Heat On
time i.e. the warmer the night time temperature the closer the switch on time will be to the Heat On time
Optimum Stop
- The MC300 Multi keeps a note of how many minutes are taken for the temperature to drop the number of degrees entered
against this parameter when the heating period ends. When Optimum Stop is enabled, the MC300 Multi switches off the
heating that number of minutes early.

2
5 User Controls
5.1 Direct Control
If configured during the commissioning stage the User has the following direct control of the heater without using the menu.
- If the Fault LED is on because the heater is at lockout, the user can reset the heater by pressing the Reset button.
- The User can switch the heating ON or OFF by pressing the Heat button.
- The User can start or cancel extension time by pressing the Heat button longer than 3 seconds.
- The User can run the fan without heating, by pressing the Fan button.
5.2 User Settings
5.2.1 General
The second line of the display shows what keypad buttons are active.
After changing settings press to save the new setting. To return to the normal display press Xor do not touch any keys for 15
or more seconds.
Keys , , –and +will auto-repeat if held down longer than approximately half a second. The +key will automatically wrap
round from the maximum value to the minimum value and the –key will wrap the other way.
5.2.2 Description of User Settings
Temperature
This shows the temperature set by the currently active programme, and it is the target temperature for thermostatic control.
The user can increase or decrease the value to adjust comfort. This will not alter the set temperature associated with the
programme, but it will temporarily alter the target temperature for thermostatic control.
The effect of altering the temperature lasts until the current programme expires or until another programme changes the set
temperature requirement.
Note: the range of adjustment permitted may be limited during commissioning. Temperature adjustment can be disabled by a
setting within the user menu.
Clock Set
Sets the current date and the time of day. The correct date allows the MC300 to know the day of the week, allows for
automatic BST-GMT changeovers, carries out the holiday shutdown function and permits override password entry.
Programme Settings
The MC300 has 14 programmes, each of which can be assigned to any day of the week. Each programme can be given an ON
time, an OFF time and a set temperature. The user may organize the programmes in any way that suits. The simplest would be
one programme ON in the morning, OFF at the end of the afternoon, active Monday to Friday.
If two or more programmes are active at the same time, for instance one is ON all day and another is ON between 11:00 and
13:00, then the set temperature of the second programme will apply between 11:00 and 13:00, and the set temperature of the
first programme will apply during the rest of the working day. Programme times increment in 5 minute steps.
Extension time (if set) applies when all programmes have reached the end of their set period for that day.
Optimum start applies at the beginning of the first programme to switch on and optimum stop applies at the end of the last
programme to switch off.
Holiday date
A future date can be set so that the heating will not operate on that date, and remains “OFF” for a consecutive number of days
from that date. The date includes the year number, ensuring that the holiday shutdown date is not automatically repeated the
following year.
During the holiday period the heater will only operate if the temperature falls below the frost temperature and if frost
temperature operation is selected “ON” in the engineer menu. The night temperature setting is ignored during holidays.
During the holiday period, manual operation of the fan or heater is permitted. Any manual operation still on at midnight will be
automatically cancelled.
Run Mode
The MC300 has three Run modes: WINTER, SUMMER and OFF.
Winter - the heating operates when any programme is in a “HEAT ON” period. The heating also operates to maintain the
Night Temperature if this has been set. The heating also operates when the temperature drops below the frost
temperature.
Note: Summer/Winter mode has no connection with the clock change from GMT to BST.
Summer - the fan operates to circulate air when switched on manually. With certain types of heater or certain types of
installation, Fan-only operation may not be appropriate and the fan control circuit should not be used.
In SUMMER the heating never operates unless the temperature drops below the frost temperature. During
commissioning the frost temperature operation will be set to be ON or OFF. If the frost setting is OFF, the heater
will not operate under frost conditions in any User mode.
OFF - the heater never operates unless the temperature drops below the frost temperature (see above).
User Button Permissions
This menu option facilitates the user to enable or disable the following controls separately if it is required to restrict
unauthorised access to user controls. Note: User permissions are only effective when User access to the menu is protected by a
password.
Reset - Allows operation of the reset button
Change temperature - Allows temporary adjustment of the current set temperature
Heat Override - Allows switching ON/OFF and extension of Heat ON time
Fan override - Allows switching ON/OFF of the fan
Set Password
The user may enter a 4-digit password here. Once set, the password must be given before selected user controls may be
accessed or changed. “Set password” cannot be entered unless the password has been given.
As delivered, the MC300 has no User password restrictions, the user password being set to 0000. Entering a password of 0000
will remove all restrictions.
Extension time
A user can extend the heating to operate beyond the switch-off time of the last programme of the day, in 30minute increments,
by pressing the Heat button. This menu option allows a maximum extension period to be set, in units of 30minutes. If set to 0
minutes, extension is not permitted. Factory default setting: 1hour. Maximum setting 3hours.
Cost Log
This option shows the total hours run and the total cost of running since the log was last cleared. The display will show the
date when it was last cleared. For this option to function it is necessary to enter the fuel cost and heater rating (see Engineer
Menu for the latter). The cost log should be cleared whenever the heater type is changed.
For Hi/Lo heaters, there are two heater power entries and the MC300 will calculate the run cost according to the level of heat
requested. In the case of modulating control heaters, the cost is an estimate based on half the full heater power.
Password
Once a password has been set, the password must be entered at this menu option to allow access to selected user controls.
Once entered the password gives access to the User menu functions for 60 minutes. To re-apply the restrictions before the end
of the 60 minute period, select the ‘Enter password’ option and press without entering any digits. The display will show
‘Password CLOSED’.
Service Date
When the MC300 is installed the Commissioning Engineer may have entered a date for when the heating equipment requires
servicing. When this date is reached the MC300 fault indicator will be illuminated and the display will alternate between the
normal display and "Service due, call engineer". The Service Engineer can clear this display by entering a new service date
when the heating equipment has been serviced.
4 Keypad Layout
4.1 User keypad (3 Buttons)
4.2 Indicators
4.3 Display
The display normally shows
- the current air temperature as measured by the sensor, or the average temperature if two sensors are fitted.
- the time of day using 24-hr notation. The colon flashes once per second to confirm that the clock is running.
- the day of the week. Programmes are associated with individual days of the week or day-groups such as weekday or
weekend.
- Pn where n represents the active programme number.
- the current setting of the heater: ON or OFF, as determined by the internal programmes (the display will say ON even if
the MC300 is not currently calling for heat because the thermostat is satisfied) or
- for High/Low and Modulating burners an indication of the heat demand: HEAT HI or HEAT LO for Hi-Low burners, or a
simple bar-graph display for modulating control heaters where 1 bar is low fire and 10 bars is high fire.
- “Frost guard” is displayed when Frost/setback is set to ON and the space temperature is lower than the Frost/setback
temperature setting.
Heating On - Is illuminated when the MC300 is calling for heat (It does not confirm that the heating is actually
working). It shows Green when the heater is a single-stage burner, Red when the heater is a Hi-Low type, and
Yellow when the heater has a Modulating burner.
Fault - Flashes when the burner control is at lockout, solid light when a service call is due (if this has been set) or
when there is a sensor fault. The bottom line of the display will alternate between normal display and type of fault.
Reset Button - Press to reset the burner controls from lockout, (when this facility is available on the heater).
Note: If the lockout cannot be reset from the Master control check the individual heaters connected to the master.
Each will have a local reset facility
Reset
Heat Button - (Note: this facility may be limited or disabled by the User).
If heating is ON (via programme)
- pressing the Heat button for less than 2 seconds overrides the programme to OFF. Any extension time that has
been set is cancelled.
- pressing the heat button for more than 3 seconds determines that heat will remain on for an extension time after
the programmed off time. The extension timer will increase in 30 minute steps, up to the maximum allowed
period, and then revert to 0 minutes. Release the button when the required extension period is showing.
If heating is OFF (via override)
- pressing the Heat button removes override and reverts to the current programme.
If heating is OFF (via programme)
- pressing the Heat button for less than 2 seconds brings on heating for 30 minutes.
- pressing the heat button for more than 3 seconds will increase the on time in 30 minute steps, up to the maximum
allowed period, and then revert to 0 minutes. Release the button when the required heating period is showing.
Heat
Fan Button -
In WINTER mode and OFF mode, the Fan button has no control over the air heater fan.
In SUMMER mode, the Fan button switches on the fan for air circulation, and another press switches it off. If the
fan is left on, it will be automatically switched off at midnight. If the fan is running because the heating is on and
the fan is in AUTO or CONST mode, the Fan button cannot switch it off.
If the fan is in ON mode, it always runs, in WINTER, SUMMER and OFF. The Fan button cannot switch it off.
Fan
3 Local Overrides
Depending on the system design local overrides may be fitted in the vicinity of each or some of the heaters to provide the
following override functions.
Heating Off
A thermostat or switch which when operated will turn the adjacent heater OFF.
Heating On
A thermostat or switch which when operated will turn the adjacent heater ON.
Fan On
A thermostat or switch which when operated will turn the fan of the adjacent heater ON.

3
5 User Controls
5.1 Direct Control
If configured during the commissioning stage the User has the following direct control of the heater without using the menu.
- If the Fault LED is on because the heater is at lockout, the user can reset the heater by pressing the Reset button.
- The User can switch the heating ON or OFF by pressing the Heat button.
- The User can start or cancel extension time by pressing the Heat button longer than 3 seconds.
- The User can run the fan without heating, by pressing the Fan button.
5.2 User Settings
5.2.1 General
The second line of the display shows what keypad buttons are active.
After changing settings press to save the new setting. To return to the normal display press Xor do not touch any keys for 15
or more seconds.
Keys , , –and +will auto-repeat if held down longer than approximately half a second. The +key will automatically wrap
round from the maximum value to the minimum value and the –key will wrap the other way.
5.2.2 Description of User Settings
Temperature
This shows the temperature set by the currently active programme, and it is the target temperature for thermostatic control.
The user can increase or decrease the value to adjust comfort. This will not alter the set temperature associated with the
programme, but it will temporarily alter the target temperature for thermostatic control.
The effect of altering the temperature lasts until the current programme expires or until another programme changes the set
temperature requirement.
Note: the range of adjustment permitted may be limited during commissioning. Temperature adjustment can be disabled by a
setting within the user menu.
Clock Set
Sets the current date and the time of day. The correct date allows the MC300 to know the day of the week, allows for
automatic BST-GMT changeovers, carries out the holiday shutdown function and permits override password entry.
Programme Settings
The MC300 has 14 programmes, each of which can be assigned to any day of the week. Each programme can be given an ON
time, an OFF time and a set temperature. The user may organize the programmes in any way that suits. The simplest would be
one programme ON in the morning, OFF at the end of the afternoon, active Monday to Friday.
If two or more programmes are active at the same time, for instance one is ON all day and another is ON between 11:00 and
13:00, then the set temperature of the second programme will apply between 11:00 and 13:00, and the set temperature of the
first programme will apply during the rest of the working day. Programme times increment in 5 minute steps.
Extension time (if set) applies when all programmes have reached the end of their set period for that day.
Optimum start applies at the beginning of the first programme to switch on and optimum stop applies at the end of the last
programme to switch off.
Holiday date
A future date can be set so that the heating will not operate on that date, and remains “OFF” for a consecutive number of days
from that date. The date includes the year number, ensuring that the holiday shutdown date is not automatically repeated the
following year.
During the holiday period the heater will only operate if the temperature falls below the frost temperature and if frost
temperature operation is selected “ON” in the engineer menu. The night temperature setting is ignored during holidays.
During the holiday period, manual operation of the fan or heater is permitted. Any manual operation still on at midnight will be
automatically cancelled.
Run Mode
The MC300 has three Run modes: WINTER, SUMMER and OFF.
Winter - the heating operates when any programme is in a “HEAT ON” period. The heating also operates to maintain the
Night Temperature if this has been set. The heating also operates when the temperature drops below the frost
temperature.
Note: Summer/Winter mode has no connection with the clock change from GMT to BST.
Summer - the fan operates to circulate air when switched on manually. With certain types of heater or certain types of
installation, Fan-only operation may not be appropriate and the fan control circuit should not be used.
In SUMMER the heating never operates unless the temperature drops below the frost temperature. During
commissioning the frost temperature operation will be set to be ON or OFF. If the frost setting is OFF, the heater
will not operate under frost conditions in any User mode.
OFF - the heater never operates unless the temperature drops below the frost temperature (see above).
User Button Permissions
This menu option facilitates the user to enable or disable the following controls separately if it is required to restrict
unauthorised access to user controls. Note: User permissions are only effective when User access to the menu is protected by a
password.
Reset - Allows operation of the reset button
Change temperature - Allows temporary adjustment of the current set temperature
Heat Override - Allows switching ON/OFF and extension of Heat ON time
Fan override - Allows switching ON/OFF of the fan
Set Password
The user may enter a 4-digit password here. Once set, the password must be given before selected user controls may be
accessed or changed. “Set password” cannot be entered unless the password has been given.
As delivered, the MC300 has no User password restrictions, the user password being set to 0000. Entering a password of 0000
will remove all restrictions.
Extension time
A user can extend the heating to operate beyond the switch-off time of the last programme of the day, in 30minute increments,
by pressing the Heat button. This menu option allows a maximum extension period to be set, in units of 30minutes. If set to 0
minutes, extension is not permitted. Factory default setting: 1hour. Maximum setting 3hours.
Cost Log
This option shows the total hours run and the total cost of running since the log was last cleared. The display will show the
date when it was last cleared. For this option to function it is necessary to enter the fuel cost and heater rating (see Engineer
Menu for the latter). The cost log should be cleared whenever the heater type is changed.
For Hi/Lo heaters, there are two heater power entries and the MC300 will calculate the run cost according to the level of heat
requested. In the case of modulating control heaters, the cost is an estimate based on half the full heater power.
Password
Once a password has been set, the password must be entered at this menu option to allow access to selected user controls.
Once entered the password gives access to the User menu functions for 60 minutes. To re-apply the restrictions before the end
of the 60 minute period, select the ‘Enter password’ option and press without entering any digits. The display will show
‘Password CLOSED’.
Service Date
When the MC300 is installed the Commissioning Engineer may have entered a date for when the heating equipment requires
servicing. When this date is reached the MC300 fault indicator will be illuminated and the display will alternate between the
normal display and "Service due, call engineer". The Service Engineer can clear this display by entering a new service date
when the heating equipment has been serviced.
4.4 Programming keypad (6 Buttons)
Back Button - Press to enter User Menu, go
back to previous screen.
Back
Decrease Button - Press to decrease values.
Decrease
Increase Button - Press to increase values.
Increase
Next Button - Press to enter User Menu, go
forward to next screen.
Next
Select Button - Press to accept changes.
Select
Quit Button - Press to exit without saving
changed values.
Quit
X
Note: may be shown as OK, Xas Cancel

4
5 User Controls
5.1 Direct Control
If configured during the commissioning stage the User has the following direct control of the heater without using the menu.
- If the Fault LED is on because the heater is at lockout, the user can reset the heater by pressing the Reset button.
- The User can switch the heating ON or OFF by pressing the Heat button.
- The User can start or cancel extension time by pressing the Heat button longer than 3 seconds.
- The User can run the fan without heating, by pressing the Fan button.
5.2 User Settings
5.2.1 General
The second line of the display shows what keypad buttons are active.
After changing settings press to save the new setting. To return to the normal display press Xor do not touch any keys for 15
or more seconds.
Keys , , –and +will auto-repeat if held down longer than approximately half a second. The +key will automatically wrap
round from the maximum value to the minimum value and the –key will wrap the other way.
5.2.2 Description of User Settings
Temperature
This shows the temperature set by the currently active programme, and it is the target temperature for thermostatic control.
The user can increase or decrease the value to adjust comfort. This will not alter the set temperature associated with the
programme, but it will temporarily alter the target temperature for thermostatic control.
The effect of altering the temperature lasts until the current programme expires or until another programme changes the set
temperature requirement.
Note: the range of adjustment permitted may be limited during commissioning. Temperature adjustment can be disabled by a
setting within the user menu.
Clock Set
Sets the current date and the time of day. The correct date allows the MC300 to know the day of the week, allows for
automatic BST-GMT changeovers, carries out the holiday shutdown function and permits override password entry.
Programme Settings
The MC300 has 14 programmes, each of which can be assigned to any day of the week. Each programme can be given an ON
time, an OFF time and a set temperature. The user may organize the programmes in any way that suits. The simplest would be
one programme ON in the morning, OFF at the end of the afternoon, active Monday to Friday.
If two or more programmes are active at the same time, for instance one is ON all day and another is ON between 11:00 and
13:00, then the set temperature of the second programme will apply between 11:00 and 13:00, and the set temperature of the
first programme will apply during the rest of the working day. Programme times increment in 5 minute steps.
Extension time (if set) applies when all programmes have reached the end of their set period for that day.
Optimum start applies at the beginning of the first programme to switch on and optimum stop applies at the end of the last
programme to switch off.
Holiday date
A future date can be set so that the heating will not operate on that date, and remains “OFF” for a consecutive number of days
from that date. The date includes the year number, ensuring that the holiday shutdown date is not automatically repeated the
following year.
During the holiday period the heater will only operate if the temperature falls below the frost temperature and if frost
temperature operation is selected “ON” in the engineer menu. The night temperature setting is ignored during holidays.
During the holiday period, manual operation of the fan or heater is permitted. Any manual operation still on at midnight will be
automatically cancelled.
Run Mode
The MC300 has three Run modes: WINTER, SUMMER and OFF.
Winter - the heating operates when any programme is in a “HEAT ON” period. The heating also operates to maintain the
Night Temperature if this has been set. The heating also operates when the temperature drops below the frost
temperature.
Note: Summer/Winter mode has no connection with the clock change from GMT to BST.
Summer - the fan operates to circulate air when switched on manually. With certain types of heater or certain types of
installation, Fan-only operation may not be appropriate and the fan control circuit should not be used.
In SUMMER the heating never operates unless the temperature drops below the frost temperature. During
commissioning the frost temperature operation will be set to be ON or OFF. If the frost setting is OFF, the heater
will not operate under frost conditions in any User mode.
OFF - the heater never operates unless the temperature drops below the frost temperature (see above).
User Button Permissions
This menu option facilitates the user to enable or disable the following controls separately if it is required to restrict
unauthorised access to user controls. Note: User permissions are only effective when User access to the menu is protected by a
password.
Reset - Allows operation of the reset button
Change temperature - Allows temporary adjustment of the current set temperature
Heat Override - Allows switching ON/OFF and extension of Heat ON time
Fan override - Allows switching ON/OFF of the fan
Set Password
The user may enter a 4-digit password here. Once set, the password must be given before selected user controls may be
accessed or changed. “Set password” cannot be entered unless the password has been given.
As delivered, the MC300 has no User password restrictions, the user password being set to 0000. Entering a password of 0000
will remove all restrictions.
Extension time
A user can extend the heating to operate beyond the switch-off time of the last programme of the day, in 30minute increments,
by pressing the Heat button. This menu option allows a maximum extension period to be set, in units of 30minutes. If set to 0
minutes, extension is not permitted. Factory default setting: 1hour. Maximum setting 3hours.
Cost Log
This option shows the total hours run and the total cost of running since the log was last cleared. The display will show the
date when it was last cleared. For this option to function it is necessary to enter the fuel cost and heater rating (see Engineer
Menu for the latter). The cost log should be cleared whenever the heater type is changed.
For Hi/Lo heaters, there are two heater power entries and the MC300 will calculate the run cost according to the level of heat
requested. In the case of modulating control heaters, the cost is an estimate based on half the full heater power.
Password
Once a password has been set, the password must be entered at this menu option to allow access to selected user controls.
Once entered the password gives access to the User menu functions for 60 minutes. To re-apply the restrictions before the end
of the 60 minute period, select the ‘Enter password’ option and press without entering any digits. The display will show
‘Password CLOSED’.
Service Date
When the MC300 is installed the Commissioning Engineer may have entered a date for when the heating equipment requires
servicing. When this date is reached the MC300 fault indicator will be illuminated and the display will alternate between the
normal display and "Service due, call engineer". The Service Engineer can clear this display by entering a new service date
when the heating equipment has been serviced.

5
5 User Controls
5.1 Direct Control
If configured during the commissioning stage the User has the following direct control of the heater without using the menu.
- If the Fault LED is on because the heater is at lockout, the user can reset the heater by pressing the Reset button.
- The User can switch the heating ON or OFF by pressing the Heat button.
- The User can start or cancel extension time by pressing the Heat button longer than 3 seconds.
- The User can run the fan without heating, by pressing the Fan button.
5.2 User Settings
5.2.1 General
The second line of the display shows what keypad buttons are active.
After changing settings press to save the new setting. To return to the normal display press Xor do not touch any keys for 15
or more seconds.
Keys , , –and +will auto-repeat if held down longer than approximately half a second. The +key will automatically wrap
round from the maximum value to the minimum value and the –key will wrap the other way.
5.2.2 Description of User Settings
Temperature
This shows the temperature set by the currently active programme, and it is the target temperature for thermostatic control.
The user can increase or decrease the value to adjust comfort. This will not alter the set temperature associated with the
programme, but it will temporarily alter the target temperature for thermostatic control.
The effect of altering the temperature lasts until the current programme expires or until another programme changes the set
temperature requirement.
Note: the range of adjustment permitted may be limited during commissioning. Temperature adjustment can be disabled by a
setting within the user menu.
Clock Set
Sets the current date and the time of day. The correct date allows the MC300 to know the day of the week, allows for
automatic BST-GMT changeovers, carries out the holiday shutdown function and permits override password entry.
Programme Settings
The MC300 has 14 programmes, each of which can be assigned to any day of the week. Each programme can be given an ON
time, an OFF time and a set temperature. The user may organize the programmes in any way that suits. The simplest would be
one programme ON in the morning, OFF at the end of the afternoon, active Monday to Friday.
If two or more programmes are active at the same time, for instance one is ON all day and another is ON between 11:00 and
13:00, then the set temperature of the second programme will apply between 11:00 and 13:00, and the set temperature of the
first programme will apply during the rest of the working day. Programme times increment in 5 minute steps.
Extension time (if set) applies when all programmes have reached the end of their set period for that day.
Optimum start applies at the beginning of the first programme to switch on and optimum stop applies at the end of the last
programme to switch off.
Holiday date
A future date can be set so that the heating will not operate on that date, and remains “OFF” for a consecutive number of days
from that date. The date includes the year number, ensuring that the holiday shutdown date is not automatically repeated the
following year.
During the holiday period the heater will only operate if the temperature falls below the frost temperature and if frost
temperature operation is selected “ON” in the engineer menu. The night temperature setting is ignored during holidays.
During the holiday period, manual operation of the fan or heater is permitted. Any manual operation still on at midnight will be
automatically cancelled.
Run Mode
The MC300 has three Run modes: WINTER, SUMMER and OFF.
Winter - the heating operates when any programme is in a “HEAT ON” period. The heating also operates to maintain the
Night Temperature if this has been set. The heating also operates when the temperature drops below the frost
temperature.
Note: Summer/Winter mode has no connection with the clock change from GMT to BST.
Summer - the fan operates to circulate air when switched on manually. With certain types of heater or certain types of
installation, Fan-only operation may not be appropriate and the fan control circuit should not be used.
In SUMMER the heating never operates unless the temperature drops below the frost temperature. During
commissioning the frost temperature operation will be set to be ON or OFF. If the frost setting is OFF, the heater
will not operate under frost conditions in any User mode.
OFF - the heater never operates unless the temperature drops below the frost temperature (see above).
User Button Permissions
This menu option facilitates the user to enable or disable the following controls separately if it is required to restrict
unauthorised access to user controls. Note: User permissions are only effective when User access to the menu is protected by a
password.
Reset - Allows operation of the reset button
Change temperature - Allows temporary adjustment of the current set temperature
Heat Override - Allows switching ON/OFF and extension of Heat ON time
Fan override - Allows switching ON/OFF of the fan
Set Password
The user may enter a 4-digit password here. Once set, the password must be given before selected user controls may be
accessed or changed. “Set password” cannot be entered unless the password has been given.
As delivered, the MC300 has no User password restrictions, the user password being set to 0000. Entering a password of 0000
will remove all restrictions.
Extension time
A user can extend the heating to operate beyond the switch-off time of the last programme of the day, in 30minute increments,
by pressing the Heat button. This menu option allows a maximum extension period to be set, in units of 30minutes. If set to 0
minutes, extension is not permitted. Factory default setting: 1hour. Maximum setting 3hours.
Cost Log
This option shows the total hours run and the total cost of running since the log was last cleared. The display will show the
date when it was last cleared. For this option to function it is necessary to enter the fuel cost and heater rating (see Engineer
Menu for the latter). The cost log should be cleared whenever the heater type is changed.
For Hi/Lo heaters, there are two heater power entries and the MC300 will calculate the run cost according to the level of heat
requested. In the case of modulating control heaters, the cost is an estimate based on half the full heater power.
Password
Once a password has been set, the password must be entered at this menu option to allow access to selected user controls.
Once entered the password gives access to the User menu functions for 60 minutes. To re-apply the restrictions before the end
of the 60 minute period, select the ‘Enter password’ option and press without entering any digits. The display will show
‘Password CLOSED’.
Service Date
When the MC300 is installed the Commissioning Engineer may have entered a date for when the heating equipment requires
servicing. When this date is reached the MC300 fault indicator will be illuminated and the display will alternate between the
normal display and "Service due, call engineer". The Service Engineer can clear this display by entering a new service date
when the heating equipment has been serviced.
19.0°C 11:06 Tue
P1 HEAT ON
Temperature 20.0
< - + >
Clock set
< >
Prog settings
< >
Holiday Date
< >
Run Mode: WINTER
< - + >
Permissions
< >
Date: 25/05/2011
< >
Next
Next
Next
Next
Next
Next
Next
Next
Next
Next
Next
Next
SetPassword ****
< - + >
Extend time 1.00
< - + >
Cost Log
< >
Password ****
< - + >
Press - or +to decrease or increase day temperature set point (17°C to 23°C. Adjustment may be disabled or limited by other
unit settings). Press to save change, Xto exit without saving
Normal display. (Winter mode with ON/OFF burner shown). Displays, depending on operating mode and burner type,
temperature at sensor, time, day, programme status, whether heating and/or fan are ON or OFF, level of burner modulation.
Press to alter date or time. Press or to select gure to change, gure will pulse. Change by pressing -or +. Press to
go to next gure. Pressing after seconds will allow changes to be discarded (X) or saved ().
Press to set/alter programmes. Press -or +to select programme number (1 to 14). Press . Press -or +to set HEAT ON time.
Press to move to next digits and then to HEAT OFF time. Press to move to Temperature setting. Press -and +to set
temperature. Press to move to day setting. Change by pressing -or +. Pressing again will allow changes to that
programme be saved () or discarded (X). Start screen for this section reappears, press Xto nish or repeat above sequence for
further programmes.
Press to set/alter Holiday Date. Press -or +to set start date. Press to go to next gure. Press after setting year to set
number of days. Press -or +to set number of days. Pressing again will allow changes to Holiday Date to be discarded (X) or
saved ().
Press to set/alter Permissions. Set each permission using -or +. Press to go to the next permission. Pressing after the
nal permission (Fan Control) will allow changes to Permissions be discarded (X) or saved () .
Press to access Cost Log. Screen shows date log started. Press to view log hours and then log cost. Pressing again will
give the option of clearing the log. Note: Clearing the log resets the start date to the current date.
Press -or +to increase/decrease extension time. Discard (X) or save () change.
The rst * will be pulsing. Press -or +to enter the rst password number. Press to go to the next digit and repeat until a 4
digit password is entered. Press and the screen will show [ SetPassword SET ].
The rst * will be pulsing. Press -or +to enter the rst password number. Press to go to the next digit and repeat until the 4
digit password is entered. Press and the screen will showVALID or FAIL. If FAIL displays check password and repeat entry
sequence.The User password, if set, must be entered for access to User functions.
Press -or +to toggle through modes. Discard (X) or save () changes.
5.3 User Operation flow chart
Use or to navigate through menu. Pressing X (Quit) at any of the displays shown below will return you to the normal
display. Bottom line of display shows which keys can be used in menu programming modes. Displays shown shaded are the
only ones visible when the MC300 is password protected.
Table of contents
Popular Thermostat manuals by other brands

York
York Hx 3 S1-THXU280 User's information manual

Honeywell
Honeywell CM900 installation guide

Salus
Salus AS20WRF Installer's/user's manual

DELTA DORE
DELTA DORE Tybox 117+ Installation and user guide

Bosch
Bosch CRC R-1 Installation and operating instructions

suntouch
suntouch SunStat ConnectPlus 500900-SB user manual