PPI neuro 100EX User manual

neuro 100EX
User Manual
Enhanced
Universal Process Indicator

CONTENTS
User Manual
neuro 100EX
1. FRONT PANEL LAYOUT 1
2. BASIC OPERATION 3
3. SET-UP MODE ACCESS AND OPERATION 5
4. ALARM PARAMETERS 7
5. RETRANSMISSION PARAMETERS 9
6. INPUT CONFIGURATION 10
7. SUPERVISORY PARAMETERS 14
8. USER LINEARISATION PARAMETERS 16
9. HARDWARE ASSEMBLY & CONFIGURATIONS 17
10. MECHANICAL INSTALLATION 24
11. ELECTRICAL CONNECTIONS 26

1
FRONT PANEL LAYOUT
The indicator front panel comprises of digital readouts, LED indicators and tactile keys as shown in Figure 1.1 below.
Figure 1.1
Upper Readout
Lower Readout
Enter Key
Up Key
Down Key
Page Key
Alarm-3 Status
Alarm-1 Status
PPI
neuro 100 EX
ACK OPR
AL3 AL4
AL1 AL2 Alarm-2 Status
Alarm-4 Status
Alarm Acknowledge Key Operator Key
READOUTS
The Upper Readout is a 5 digit, 7-segment bright red LED display and usually displays the PV (Process Value). In Set-up
Mode, the Upper Readout displays parameter values/options.
The Lower Readout is a 5 digit, 7-segment bright green LED display and usually displays Process Value Units. In case of any
active Alarm(s), the Lower Readout flashes Alarm Status information. In Set-up Mode, the Lower Readout displays the names
(identifier tags) for the parameters.
INDICATORS
The front panel comprises 4 LED indicators that show Alarm status. Refer Table 1.1 below for details.
KEYS
There are six tactile keys provided on the front panel for configuring the indicator, setting-up the parameter values and
selecting Operation / Display Modes. Refer Table 1.2 below.
Table 1.1
Flashes while Alarm-1 is active.
AL1
AL2 Flashes while Alarm-2 is active.
LED Status
AL3 Flashes while Alarm-3 is active.
AL4 Flashes while Alarm-4 is active.
User Manual
neuro 100EX
Section 1

2
User Manual
neuro 100EX
Table 1.2
OPR
OPERATOR
PAGE
ACK
ENTER
Symbol Key Function
PAGE
DOWN
UP
ALARM
ACKNOWLEDGMENT
Press to access ‘Operator-Page’ parameters.
(The parameters are listed and described in section 2 :
Basic Operations)
Press to store the set parameter value and to scroll to the next
parameter on the PAGE.
Press to enter or exit set-up mode.
Press to increase the parameter value. Pressing once
increases the value by one count; keeping pressed speeds up
the change.
Press to decrease the parameter value. Pressing once
decreases the value by one count; keeping pressed speeds up
the change.
Press to acknowledge any pending Alarm(s). This also turns-
off the Alarm relay.

3
BASIC OPERATION
Table 2.1
PV above Max. Range
PV below Min. Range
Message Error Type Cause
Thermocouple / RTD broken
Sensor Open
Under-range
Over-range
ALARM STATUS UNDER PV ERROR CONDITIONS
For Alarm activation, the under-range condition is treated as minimum PV, whereas the over-range and open conditions are
treated as maximum PV. Thus, Process High Alarm turns ON under Over-range/Open error. Similarly, Process Low Alarm
turns ON under Under-range error.
OPERATOR PAGE AND PARAMETERS
The parameters that require frequent settings are organized on a separate page, called the Operator Page. The availability of
operator parameters is controlled at supervisory level and the parameter setting cannot be locked by the Master Lock.
Accessing Operator Page & Adjusting Parameters
Step through the following sequence to open the Operator Page and to adjust the operator parameter values.
1. Press and release ‘OPR’ key. The Lower Readout shows prompt for the first available operator parameter and the Upper
Readout shows value for the parameter.
2. Use UP / DOWN keys to adjust the value and then press ENTER key to store the set value and scroll to the next parameter.
The automatically reverts to MAIN Display Mode upon scrolling through the last operator parameter. indicator
Alternatively, use PAGE key to return to MAIN Display Mode.
Note:
The Operator Page can also be accessed through PAGE-0. (The pages and parameters are explained in next section).
The operator parameters are described in Table 2.2. Note that the parameters presented on Operator Page depend upon the
functions selected/enabled and supervisory level permissions.
POWER-UP
Upon power-up, all displays and indicators are lit on for approximately 3 seconds. This is followed by the indication of the
indicator model name on the Upper Readout and the firmware version on the Lower Readout, for
approximately 1 second.
MAIN DISPLAY MODE
After the Power-up display sequence, the Upper Readout starts showing the measured PV (Process Value) and the Lower
Readout displays the user set Units for Process Value. This is the MAIN Display Mode that shall be used most often.
Alarm Status Information
In case of any Alarm (or Alarms) becoming active, the Lower Readout flashes the related Alarm details in the format ‘Ax.YY’,
where x is the Alarm Number (1, 2, 3 or 4) and YY is Alarm Type (Lo or Hi) For example means Alarm-1 is active and
the set Alarm Type is Low. In case of multiple Alarms, each Alarm Status is flashed sequentially with 3 Seconds time interval.
PV Error Indications
The PV Error type is flashed on the Upper Readout. For different errors and the causes, refer Table 2.1 below.
User Manual
neuro 100EX
Section 2

4
Table 2.2
Throughout the range for
the selected Input Type.
(Default :
For Process Low : -200.0
For Process High : 1376.0)
Parameter Description Settings
(Default Value)
View Only
(Default : NA)
MAXIMUM PV
This indicates the highest value attained by the Process Value.
This is a read only value and is available only if Min/Max
monitoring is enabled.
MINIMUM PV
This indicates the lowest value attained by the Process Value.
This is a read only value and is available only if Min/Max
monitoring is enabled.
RESET COMMAND
Available only if Min/Max monitoring is enabled. Set this
parameter to ‘Yes’ followed by correct password entry (through
next parameter) to clear the current Min/Max values and start
afresh monitoring the PV for new Min/Max values.
No
Yes
(Default : No)
RESET PASSWORD
For resetting the Min/Max values, set the reset command to ‘Yes’
and then enter the correct password.
0 to 250
(Default : 0)
ALARM-1 SETPOINT
The setpoint for Alarm-1. This parameter is not available if the
selected Alarm type for Alarm-1 is ‘None’.
ALARM-2 SETPOINT
The setpoint for Alarm-2. This parameter is not available if the
selected Alarm type for Alarm-2 is ‘None’.
ALARM-3 SETPOINT
The setpoint for Alarm-3. This parameter is not available if the
selected Alarm type for Alarm-3 is ‘None’.
ALARM-4 SETPOINT
The setpoint for Alarm-4. This parameter is not available if the
selected Alarm type for Alarm-4 is ‘None’.
View Only
(Default : NA)
User Manual
neuro 100EX
The operator parameter list mainly includes :
a) Min / Max Process Monitoring Parameters.
b) Setpoint Values for all 4 Alarms ( Alarm-1 to Alarm-4).

5
The various parameters are arranged in different groups, called PAGES, depending upon the functions they represent. Each
group is assigned a unique numeric value, called PAGE NUMBER, for its access.
The parameters are always presented in a fixed format: The Lower Readout displays the parameter prompt (Identification
Name) and the Upper Readout displays the set value. The parameters appear in the same sequence as listed in their
respective sections.
SET-UP MODE
The Set-up Mode allows the user to view and modify the parameter values. Follow the steps below for setting the parameter
values:
1. Press and release PAGE key. The Lower Readout shows PAGE and the Upper Readout shows page number 0. Refer
Figure 3.1.
2. Use UP / DOWN keys to set the desired PAGE NUMBER.
3. Press and release ENTER key. The Lower Readout shows the prompt for the first parameter listed in the set PAGE and the
Upper Readout shows its current value. If the entered PAGE NUMBER is invalid (contains no parameter list or any
associated function), the reverts to the MAIN Display Mode.indicator
4. Press and release the ENTER key until the prompt for the required parameter appears on the Lower Readout. (The last
parameter in the list rolls back to the first parameter).
5. Use UP / DOWN keys to adjust the parameter value. (The display flashes if UP key is pressed after reaching the maximum
value or DOWN key is pressed after reaching the minimum value).
6. Press and release the ENTER key. The new value gets stored in the indicator’s non-volatile memory and the next
parameter in the list is displayed.
The Figure 3.1 illustrates the example of altering the value for the parameter ‘Input type’.
Figure 3.1
SET-UP MODE : ACCESS AND OPERATION
User Manual
neuro 100EX
Press PAGE
key to enter Set-up mode
Press ENTER
key to open the Page
Use UP/DOWN
keys to set the Page Number
Default Page Page NumberMAIN Display
Mode
Use UP/DOWN
keys to change the value
Press ENTER key
to store the value &
move to next parameter
First Parameter
on PAGE-12
Next Parameter
on PAGE-12
New Parameter
value
Section 3
or
or

6
Notes
1. Each page contains a fixed list of parameters that are presented in a pre-determined sequence. Note however that availability of a few
parameters, called Conditional Parameters, depend upon the settings for some other parameters. For example, the parameter ‘Alarm
Setpoint’ is available if corresponding ‘Alarm type’ is set to other than ‘none’.
2. To exit the set-up mode and return to the MAIN Display Mode, press and release PAGE key.
3. If no key is pressed for approximately 30 seconds, the set-up mode times out and reverts to the MAIN Display Mode.
MASTER LOCKING
The indicator facilitates locking all the PAGES (except Operator PAGE) by applying Master Lock Code. Under Locking, the
parameters are available for view only and cannot be adjusted. The Master Lock, however, does not lock the operator
parameters. This feature allows protecting the rather less frequently used parameters against any inadvertent changes while
making the frequently used operator parameters still available for any editing.
For enabling / disabling the Lock, step through the following sequence:
Locking
1. Press and release PAGE key while the indicator is in the MAIN Display Mode. The Lower Readout shows PAGE and the
Upper Readout shows 0.
2. Use UP / DOWN keys to set the Page Number to 123 on the Upper Readout.
3. Press and release ENTER key. The indicator returns to the MAIN Display Mode with the Lock enabled.
The Figure 3.2 below illustrates the Locking procedure.
Figure 3.2
UnLocking
Repeat the Locking procedure twice for unlocking.
User Manual
neuro 100EX
Press PAGE
key to enter Set-up mode
Use UP/DOWN
keys to set the ‘Locking’ Code
Press ENTER key to
Lock & Return to
MAIN Mode
Default Page Locking Code MAIN Mode
MAIN Mode
or

7
ALARM PARAMETERS
Visit www.ppiindia.net for technical notes on ALARM for detailed understanding of the parameters / terminologies
used for describing the Alarm parameters in this section.
The parameters required for configuring Alarms are grouped on PAGE-10. The configuration includes selecting the type of
Alarm, setting the hysteresis value, enabling / disabling start-up Alarm suppression, etc. Refer Table 4.1 for parameter
description & settings.
Table 4.1
ALARM INHIBIT
Yes
The Alarm activation is suppressed until the PV is within Alarm
limits from the time the indicator is switched ON. This allows
suppressing the Alarm during the start-up Alarm conditions.
No
The Alarm is not suppressed during the start-up Alarm conditions.
ALARM HYSTERISIS
This parameter value sets a differential (dead) band between the
ON and OFF Alarm states. Keep it large enough to avoid frequent
switching of the Alarm relay.
No
Yes
(Default : No)
Settings
(Default Value)
Parameter Description
ALARM SET POINT
This parameter sets the Process High or Process Low limit for
Alarm.
ALARM NUMBER
Select Alarm Number for parameter setting. For example; setting
the value to 1, selects Alarm-1.
ALARM TYPE
None
Disable the Alarm .
Process Low
The Alarm activates when the PV equals or falls below the ‘Alarm
Setpoint’ value.
Process High
The Alarm activates when the PV equals or exceeds the ‘Alarm
Setpoint’ value.
1 to 4
(Default : 1)
Min. to Max. of selected
input type range
(Default : For
Process Low : -200.0
& Process High : 1376.0)
None
Process Low
Process High
(Default : None)
(Default : 2.0)
For DC Lin. Volts/Current
1 to 30000 Counts
For Thermocouple/RTD
1 to 3000 or 0.1 to 3000.0
User Manual
neuro 100EX
Section 4

8
ALARM LATCH
No
The Relay switches ON/OFF with Alarm switching.
Yes
The Relay Output switches (ON for Normal Logic / OFF for
Reverse logic) upon Alarm activation. However, Alarm de-
activation does not affect the Relay status. The Relay status can
only be regained by pressing ‘Acknowledge-key’ provided the
Alarm has de-activated.
ALARM LOGIC
Select ‘Normal’ if Alarm is to activate an Audio / Visual alarm.
Select ‘Reverse’ if Alarm is to Trip the system.
Settings
(Default Value)
Parameter Description
Reverse
Normal
(Default : Normal)
No
Yes
(Default : No)
User Manual
neuro 100EX

9
RETRANSMISSION PARAMETERS
The parameters required for configuring Retransmission are grouped on PAGE-11. The configuration includes selecting the
Output type, Recorder Low & High settings etc. Refer Table 5.1 for parameter description & settings.
Table 5.1
RECORDER HIGH
Set the Higher PV Limit that shall correspond to the maximum
recorder output signal level (20 mA / 10 V / 5 V).
(Default : -200.0)
Min. to Max. Range
Specified for the
Selected Input Type
Set the Lower PV Limit that shall correspond to the minimum
recorder output signal level (0 mA / 4 mA / 0 V).
RECORDER LOW
(Default : 0 to 20 mA)
0 to 20 mA
4 to 20 mA
0 to 5 Volts
0 to 10 Volts
RECORDER OUTPUT TYPE
Select type in accordance with the hardware module fitted. Select
0-20 or 4-20 mA, if Current output module is fitted. Select 0-5 or 0-
10 V, if Voltage output module is fitted.
Settings
(Default Value)
Parameter Description
Min. to Max. Range
Specified for the
Selected Input Type
(Default : 1376.0)
User Manual
neuro 100EX
Section 5

10
INPUT CONFIGURATION PARAMETERS
The indicator needs to be appropriately configured for sensor Input type PV indication, digital filter etc. The PAGE-12
parameters are listed below in Table 6.1.
Table 6.1
Settings
(Default Value)
Parameter Description
DIGITAL FILTER
Sets the time constant, in Seconds, for the low-pass digital filter
applied to the measured PV. The filter helps smoothing /
averaging the signal input and removing the undesired noise. The
higher the filter value the lower the indication response to the PV
changes and vice-a-versa.
0.5 to 60.0 Seconds
(in steps of 0.5 Seconds)
(Default : 2.0 sec.)
(Default : )EU
Refer Table 6.2
Refer Table 6.3
(Default : 0.1)
Select Input type in accordance with the type of Thermocouple or
RTD, sensor or Transducer output connected for process value
measurement. Ensure proper hardware jumper settings.
INPUT TYPE
Set the Process Value indication resolution (decimal point). All the
resolution based parameters (hysteresis, alarm setpoints etc.)
then follow this resolution setting.
RESOLUTION
Select Temperature units in °C or °F for Thermocouple or Pt100
sensor.
For DC Linear inputs (mA/mV/V), select appropriate Units from
the list in Table 6.2. Note however that the selected Units are for
the purpose of Lower Readout indication only.
UNITS
Refer Table 6.3
(Default : Type K)
DC RANGE HIGH
(Available for DC Linear Inputs)
Sets process value corresponding to maximum DC Linear signal
input.
(e.g., 5 V, 10 V, 20 mA, etc.)
OFFSET
This value is algebraically added to the measured PV to derive the
final PV that is displayed and used for Alarm / Retransmission.
Final PV = Measured PV + Offset
-19999 to 30000
(Default : 100.0)
DC RANGE LOW
(Available for DC Linear Inputs)
Sets process value corresponding to minimum DC Linear signal
input.
(e.g., 0 V, 0 mA, 4 mA, etc.)
-19999 to 30000
(Default : 0.0)
For DC Lin. Volts/Current
-19999 to 30000 Counts
For Thermocouple/RTD
-1999 to 3000 or
-1999.9 to 3000.0
(Default : 0)
User Manual
neuro 100EX
Section 6

11
User Manual
neuro 100EX
Table-6.2
Lower Readout Units
°C
°F
Kelvin
Engineering Units
Percentage
Pascals
Mpascals
Kpascals
Bar
Milli bar
PSI
kg/sq cm
mm water gauge
Inches water gauge
mm mercury
Torr
Litres per hour
Litres per minute
% Relative Humidity
% O2
% CO2
% Carbon Potential
Temperature
Pressure
Flow

12
User Manual
neuro 100EX
Lower Readout Units
volts
Amps
Milli amps
Milli Volts
Ohms
Parts per million
Revolutions per pinute
Milli seconds
Seconds
Minutes
Hours
PH
%PH
Miles per hour
Milli grams
Grams
Kilo grams
cm (Centimeter)
mm (Millimeter)
Inch
Foot
Mile
Meter
Kilometer
Electricity
Time
Weight
Length /
Height /
Distance

13
User Manual
neuro 100EX
Table 6.3
-19999 to 30000 units
1 °C/°F
or
01°C/°F
1 °C/°F
or
0.1 °C/°F
1
0.1
0.01
0.001
units
Option
Resolution
What it means Range (Min. to Max.)
Type J Thermocouple
Type K Thermocouple
Type T Thermocouple
0.0 to +9600°C / +32.0 to +1760.0°F
-200.0 to +1376.0°C / -328.0 to +2508.0°F
-200.0 to +387.0°C / -328.0 to +728.0°F
Type R Thermocouple
Type S Thermocouple
Type B Thermocouple
Type N Thermocouple
3-wire, RTD Pt100
-199 to +600°C / -328 to +1112°F
or
-199.9 to +600.0°C / -328.0 to +1112.0°F
0.0 to +1771.0°C / +32.0 to +3219.0°F
0.0 to +1768.0°C / +32.0 to +3214.0°F
0.0 to +1826.0°C / +32.0 to +3218.0°F
0.0 to +1314.0°C / +32.0 to +2397.0°F
0 to 50mV DC voltage
0 to 200mV DC voltage
0 to 1.25V DC voltage
0 to 5.0V DC voltage
0 to 10.0V DC voltage
1 to 5.0V DC voltage
0 to 20mA DC current
4 to 20mA DC current
Reserved for customer specific Thermocouple type not listed above. The
type shall be specified in accordance with the ordered (optional on
request) Thermocouple type.

14
SUPERVISORY PARAMETERS
The supervisory level responsibilities include exercising control over operator, making process related decisions and
controlling the availability of process data for remote use. The PAGE-13 parameters allow implementation of supervisory level
decisions. The Table 7.1 below lists supervisory parameters.
Table 7.1
BAUD RATE
Communication speed in ‘Bits per Second’. Set the value to match
with the host baud rate.
PASSWORD FOR RESETTING
PV HIGH-LOW
This parameter allows protection against inadvertent resetting of
Min/Max values. That is, the reset command is executed only if the
operator enters the password that matches with this parameter
value.
Settings
(Default Value)
Parameter Description
This parameter enables or disables the PV monitoring for Min /
Max values. Set to ‘Yes’ for enabling the feature.
PROCESS VALUE HIGH-LOW MONITORING
Supervisory permission for enabling recorder (retransmission)
output.
RECORDER
Supervisory permission for Alarm setpoint adjustments on
Operator Page. Set to ‘Enable’ for permission.
ALARM SP ADJUSTMENT
ON OPERATOR PAGE
Supervisory permission for use of the rear panel terminals for
connecting remote switch for Alarm acknowledge.
REMOTE ACKNOWLEDGE SWITCH
Enable
Disable
(Default : Disable)
Yes
No
(Default : No)
0 to 250
(Default : 0)
4800
9600
19200
38400
57600
(Default : 9.6)
Enable
Disable
(Default : Disable)
Enable
Disable
(Default : Disable)
User Manual
neuro 100EX
Section 7

15
Settings
(Default Value)
Parameter Description
SERIAL ID NUMBER
Unique numeric code assigned to the for identification by indicator
the host. Set the value as required by the host.
1 to 127
(Default : 1)
SERIAL WRITE PERMISSION
Setting to ‘No’ disallows the host to set / modify any parameter
value. The host, however, can read the value.
Yes
No
(Default : No)
User Manual
neuro 100EX
PARITY
One of the communication error trapping features. Select the data
packet parity as implemented by the host protocol.
None
Even
Odd
(Default : Even)

16
USER LINEARISATION PARAMETERS
The parameters listed on this page are used to implement the linearisation curve on the process value represented by the DC
linear output of a transmitter. The parameters affect the measured PV only if the ‘User Linearisation’ feature is ‘Enabled’ and if
the input type is DC Linear. That is, the PV measured using Thermocouple or RTD is not affected by the linearisation
parameters. The Table 8.1 below lists the user linearisation parameters.
Visit www.ppiindia.net for technical notes on USER LINEARISATION for detailed understanding of the parameters /
terminologies used for describing the parameters in this section.
Table 8.1
Settings
(Default Value)
Parameter Description
Enable / Disable user linearisation feature.
USER LINEARIZATION
Select number of segments for the purpose of input PV curve
linearisation by setting the number of total break points.
TOTAL BREAK POINTS
Protection password for access to the linearisation related
parameters. Set to 333 as valid password.
USER LINEARIZATION SETTING CODE
1 to 32
(Default : 2)
0 to 9999
(Default : 0)
BREAK POINT NUMBER
Select the break point for which the X, Y co-ordinates are to be set.
1 to 32
(Default : 1)
-19999 to 30000
(Default : Undefined)
ACTUAL VALUE FOR
BREAK POINT (X CO-ORD)
Set the actual measured (X co-ordinate) value.
Set the computed or derived (Y co-ordinate) value.
DERIVED VALUE FOR
BREAK POINT (Y CO-ORD) -19999 to 30000
(Default : Undefined)
Yes
No
(Default : No)
User Manual
neuro 100EX
Section 8

17
HARDWARE ASSEMBLY AND CONFIGURATIONS
The Figure 9.1 below shows the indicator outer-case viewed with front label upright.
ELECTRONIC ASSEMBLY
The basic electronics assembly (without any plug-in modules), comprises of 4 Printed Circuit Boards (PCB). When viewed
from the front; the CPU PCB is to the left, Power-supply PCB is to the right, Output PCB is in the center and the Display PCB is
behind the bezel.
The electronic assembly can be removed from the plastic enclosure and placed back as described and illustrated in Figure
9.2.
Figure 9.1
PPI
neuro 100 EX
+
+
+–
–
–+–
NO CNO NO NO
CCC
RLYRLYRLY RLY
SSR / DC Lin
OP-1
SSR / DC Lin
OP-2 OP-3 OP-4
SSR SSR
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
+–
LN
Ext. Voltage
B+ B–GND
SERIAL COMM
85 to 265 VAC
1
2
3
4
5
6
7
8
9
10
+–
+
+––
NO C
RLY
DC LINEAR
DI-1 DI-2
SSR / DC Lin
OP-5
T/C
Pt100
31
32
33
34
35
36
37
38
39
PPI
neuro 102 EX
Sr.No.:
IO Code:
Ventilations
Bezel
Front Label
Connection Diagram
Rear
Terminals
Enclosure
Panel Mounting
Clamp
Pullout
Latch
User Manual
neuro 100EX
Section 9

18
Figure 9.2
Removing Assembly from Enclosure
Hold the indicator upside down and press the pullout latch to unlock the front bezel from the enclosure (Refer Figure 9.2
above). Pull the bezel outward. The electronics assembly comes out with the bezel.
Placing Assembly Back into Enclosure
Hold the Enclosure and the Bezel such that the Latching Slot on the Enclosure and the Pullout Latch on the Bezel face upward
(See Figure 9.2). Insert the bezel gently into the Enclosure until the Bezel snap fits.
User Manual
neuro 100EX
Removal
Placing Back
PulloutLatch
Latching Slot
PPI
neuro 100 EX
Table of contents
Other PPI Touch Panel manuals