Masibus 1008S User manual

User’s Manual
FLOW INDICATOR TOTALISER 1008S
Masibus Automation & Instrumentation Pvt. Ltd.
B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India
+91 79 23287275-79 +91 79 23287281-82
Email: support@masibus.com
Web: www.masibus.com

User Manual 1
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
CONTENTS
1. INTRODUCTION.................................................................................................3
2. SAFETY AND WARNING PRECAUTIONS....................................................5
2.1 Safety Precautions............................................................................................5
2.2 Warning Precautions........................................................................................5
3. SPECIFICATIONS................................................................................................7
3.1 Measured input signal........................................................................................7
3.2 Loop Power Supply Specification .....................................................................7
3.3 Retransmission Output.......................................................................................7
3.4 Contact Input (Digital input)..............................................................................7
3.5 Contact Output...................................................................................................8
3.6 Display Unit Specification.................................................................................8
3.7 Electrical Specification......................................................................................8
3.8 Isolation specification........................................................................................8
3.9 Environmental Specification..............................................................................9
3.10 Alarm Specification..........................................................................................9
3.11 Display Specification........................................................................................9
3.12 Communication.................................................................................................9
3.13 Other Specification ...........................................................................................9
4. FRONT AND REAR PANEL DESCRIPTION...............................................10
4.1 Front Panel Description ...................................................................................10
4.2 Rear Panel Diagram.........................................................................................10
4.2.1 Rear Panel Diagram Of 1008S Standard ....................................................10
4.2.2 Rear Panel Diagram Of 1008S With Mass Flow........................................11
5. MECHANICAL GUIDELINES........................................................................12
5.1 Mounting Details .............................................................................................12
5.2 Mounting Steps................................................................................................12
6. TERMINAL CONNECTION DETAILS .........................................................13
6.1 Terminal Connection Details Of 1008S Standard .............................................13
6.2 Terminal Connection Detail Of 1008S With Mass Flow...................................13
7. WIRING DIAGRAM..........................................................................................14
7.1 Wiring Diagram Of 1008S Standard..................................................................14
7.2 Wiring Diagram Of 1008S With Mass Flow.....................................................15
8. OPERATING DETAILS....................................................................................16
8.1 Display Section:...............................................................................................16
8.2 Keyboard Section.............................................................................................16
8.3 Run Mode.........................................................................................................16
8.3.1 Run Mode Parameters Details ...................................................................17
8.4 Edit Mode.........................................................................................................18
8.4.1 Program mode............................................................................................19
8.4.2 Configuration mode...................................................................................20
8.4.3 Calibration mode....................................................................................26

User Manual 2
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
8.5 Parameter Flow..................................................................................................27
8.5.1 Parameter Flow Of 1008S Standard ...........................................................27
8.5.2 Parameter Flow Of 1008S With Mass Flow...............................................29
9. CALIBRATION PROCEDURE........................................................................31
9.1 Input Calibration..............................................................................................31
9.2 Output Calibration ...........................................................................................31
9.2.1 Out zero and Out span.................................................................................31
10. COMMUNICATION GUIDELINES..............................................................32
10.1 Introduction....................................................................................................32
10.2 Function Code for Modbus............................................................................32
10.3 Modbus RTU protocol addresses for RS 485 Communication .....................32
10.3.1 Addresses Of 1008S Standard ..................................................................32
10.3.2 Addresses Of 1008S With Mass Flow......................................................34
11. Miscellaneous.....................................................................................................37
12. Troubleshooting ................................................................................................38

User Manual 3
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
1. INTRODUCTION
Foreword
Thank you for purchasing FLOW INDICATOR TOTALISER 1008S. This
manual describes the basic functions and operation methods of 1008S.
Please read through this user‟s manual carefully before using the product.
Overview
This is a microcontroller based Indicator - Totaliser unit, with very high
performance to price ratio. It is highly versatile, accurate and different from the
conventional indicators.
The instrument is made in 96 x 96 x 110 mm size with DIN standard
panel cutout of 92 x 92 mm.
Front is sealed membrane type to withstand dusty environment. On
back plate detachable terminals are provided for easy connection.
The programming, calibration and operation of the instrument are by
four simple keys and with two independent displays groups: one for flow rate
and one for batch total.
Operation of the instrument is menu driven with user understandable
prompts. For protecting programmed data password protection facility is
provided. Integrated total, batch total and roll count are cleared by special
password.
The product is made to accept current (4-20 mA, 0-20mA), Voltage
(1-5Volt, 0-5 Volt) input, pulse input & Digital input. It is available as a single
input version only. The instrument is providing with the five-point calibration.
The unit can be calibrated in installed condition itself by front panel keys at
predefined points.
The set Parameters and integrated total are stored in serial NVRAM.
No battery back up is required.
Notice
The contents of this manual are subject to change without notice as a result of
continuing improvements to the instrument‟s performance and functions.
Every effort has been made to ensure accuracy in the preparation of
this manual. Should any errors or omissions come to your attention, however,
please inform MASIBUS Sales office or sales representative. Under no
circumstances may the contents of this manual, in part or in whole, be
transcribed or copied without our permission.
Trademarks
Our product names or brand names mentioned in this manual are the
trademarks or registered trademarks of Masibus Automation and
Instrumentation (P) Ltd. (herein after referred to as MASIBUS).

User Manual 4
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
Adobe, Acrobat, and Postscript are either registered trademarks or
trademarks of Adobe Systems Incorporated. All other product names
mentioned in this user's manual are trademarks or registered trademarks of
their respective companies.
Checking the Contents of the Package
Unpack the box and check the contents before using the product. If the
product is different from that which you have ordered, if any parts or
accessories are missing, or if the product appears to be damaged, contact
your sales representative.
Product Ordering Code:
The FLOW INDICATOR TOTALISER 1008S unit has a nameplate
affixed to the one side of the enclosure. Check the model and suffix codes
inscribed on the nameplate to confirm that the product received is that which
was ordered.
ORDERING CODE
Model
Input Types
Digital
Input
Power Supply
Communic
ation
Relay
Retransmis
sion O/P
Mounting
Mass Flow
Measurement
1008S
X
X
XX
X
X
X
XX
X
C
4-20mA
N
None
A1
85-265V
AC
N
None
N
NONE
N
None
P0
Panel
N
None
D
0-20mA
Y
Yes
A3
24V DC
2
RS485
2
2 Relays
Y
Yes
W1
Wall-IP55
PT
PT
Compensati
on
E
1-5V DC
4
4 Relays
FP
Wall-FLP
SS
Saturated
Steam Flow
F
0-5V DC
SH
Super
Heated
Steam
G
0-10V DC
N
0-10 KHz
S
SPECIAL*
X -Specify from table
*Consult Factory

User Manual 5
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
2. SAFETY AND WARNING PRECAUTIONS
2.1 Safety Precautions
oBefore installation or beginning of any troubleshooting procedures power to all
equipments must be switched off and isolated. Units suspected of being faulty must
be disconnected and removed first and brought to a properly equipped workshop for
testing and repair. Component replacement and interval adjustments must be done
by a Masibus authorized or trained person only.
2.2 Warning Precautions
oIt is recommended that power of these units to be protected by fuses, circuit breakers
or external over current rated at the minimum value possible.
oAll wiring must confirm to appropriate standards of good practice and local codes and
regulations. Wiring must be suitable for voltage, current, and temperature rating of the
system.
oUnused control terminals should not be used as jumper points as they may be
internally connected, causing damage to the unit.
oVerify the ratings of the output devices and the inputs are as specified.
oProvide Power from a single-phase instrument power supply. If there is a lot of noise
in the power line, insert an insulating transformer into the primary side of the line and
use a line filter on the secondary side. As counter measures against noise, do not
place the primary and secondary power cables close to each other.
Note:
oInformation in this manual is subject to change without prior notice or
permission due to continuous improvement.

User Manual 6
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
CAUTION:
High voltage transients may occur when switching inductive loads such as
some contactors or solenoid valves. Through the internal contacts, these
transients may introduce disturbances which could affect the performance of
the instrument.
For this type of load it is highly recommended that a “snubber” is connected
across the normally open contact of the relay switching though load. The
snubber recommended consists of a series connected resistor/capacitor
(typically 15nF/100 Ohms). A snubber will also prolong the life of the relay
contacts. A snubber should also be connected across the output of a trip
output to prevent false triggering under line transient conditions.

User Manual 7
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
3. SPECIFICATIONS
3.1 Measured input signal
NUMBER OF INPUTS
1(one) with Optional 2 & 3
INPUT TYPE
DC Input
Current Input
*Pulse
Input
Integrated/
Batch Total
0-5 V
1-5 V
0-20
mA
4-20
mA
MEASURING RANGE
0-30000 Range
0 - 99999999
ACCURACY
± 0.025% of full scale ± 1 Count
**0.45 %
BURN OUT DETECTION
Available for 1 to 5VDC, 4 to 20 mA, 0 to 10 KHz.
INPUT RESISTANCE
250 Ohms Internal for current Input
320K Ohms for Voltage Input
ALLOWABE SIGNAL
SOURCE RESISTANCE
DC input voltage: 1KΩ or less . Effect from allowable signal
source Resistance: 0.031 % / 100Ω or less
ALLOWABLE INPUT
VOLTAGE
DC voltage: ±20V DC
NOISE REJECTION RATIO
Common Mode: > 100db
Normal mode: > 40db
RESPONSE TIME
Input to relay o/p: < 1 second.
Input to Analog o/p: < 1 second or less, 63 % ( 10 - 90%)
(Time required for o/p to reach 63% of the maximum
excursion when PV changes from 10% to 90%)
RESOLUTION
16 bit
POLARITY PROTECTION
Not provided
MEMORY BACKUP
EEPROM
Note:
Input type is factory set.
* Max. Pulse level<=24V , Min. pulse level > 1.0V
** ±(0.45% of Reading + 1 Digit)
3.2 Loop Power Supply Specification
LOOP POWER SUPPLY
24VDC ± 5% @ 50mA
3.3 Retransmission Output
NUMBER OF OUTPUT
POINTS
1
OUTPUT SIGNAL
4 to 20 mA DC
ON LOAD RESISTANCE
500Ω or less
OUTPUT ACCURACY
0.25% of full scale +1 count
RESOLUTION
12 bits (5A)
3.4 Contact Input (Digital input)
NUMBER OF INPUTS
4
USAGE
Input 1 : Stop Batch
Input 2 : Integration total zero(Therefore Batch total and roll
count will be zero)
Input 3 : Start Batch
Input 4 : Batch total zero

User Manual 8
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
INPUT TYPE
Non- voltage contact input or transistor open collector input
INPUT CONTACT
CAPACITY
12VDC,10mA or more (for non –voltage contact input)
ON/ OFF DETERMINATION
For non-voltage contact input
ON = contact resistance of 1KΩ or less,
OFF = contact resistance of 20KΩ or more
For transistor contact input
ON = 2V or less
OFF = leak current of 100µA or less
MINIMUM RETENTION
TIME FOR STATUS
DETECTION
About 1 Second
3.5 Contact Output
USAGE
Flow alarm and batch
NUMBER OF RELAY CONTACT
OUTPUTS
4 (2 Flow alarm relays, 2 Batch relays)
RELAY CONTACT RATING
250VAC/5Amps
RELAY CONTACT TERMINAL
3(Common, NO, NC)
3.6 Display Unit Specification
PROCESS VALUE DISPLAY
0.56” 5 digit 7- segment red display
INTEGRATED TOTAL DISPLAY
0.40” 8 digit 7- segment red display
PARAMETER DISPLAY
Same integrated total display
STATUS INDICATING LAMP
Red LED‟s
3.7 Electrical Specification
POWER SUPPLY
85 to 265 VAC, 50Hz ; 24VDC(optional)
POWER
CONSUMPTION
<10Va
WITHSTANDING
VOLTAGE
Between primary terminal and secodary terminal :
1500VAC(For 1 min)
Between primary terminal and ground terminal : 500VDC(for
1 min)
Between ground terminal and Secondary terminal : 500V AC
(for 1 minute).
(Primary terminal: Power supply, relay output)
(Secondary terminal: Analog input/output signal terminals,
contact input terminal)
3.8 Isolation specification
ISOLATION RESISTANCE
Between power supply terminal and ground terminal: 500
VDC, 50MΩ
MEASURED INPUT
TERMINAL
Isolated from other input/output terminals. Not isolated from
24Vdc supply (Transmitter power supply) and internal circuit.
24V DC SUPPLY FOR
TRANSMITTER
Not isolated from the measured input terminal & internal
circuit, isolated from other input/output terminals.
RETRANSMISSION
OUTPUT TERMINAL
Isolated from other input/output terminals and internal circuit.
CONTACT INPUT
TERMINAL
Isolated from other input/output terminals and internal circuit.
RELAY CONTACT O/P
Isolated from other input /output terminals and internal

User Manual 9
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
TERMINAL (DIGITAL INPUT)
circuit.
RS-485 COMMUNICATION
TERMINAL
Isolated from other input/output terminals and internal circuit.
POWER SUPPLY
TERMINAL
Isolated from other input / output terminals and internal
circuit.
GROUND TERMINAL
Isolated from other input/ output terminals and internal
circuit.
3.9 Environmental Specification
OPERATING TEMPERATURE
0 to 55C
STORAGE TEMPERATURE
0 to 70C
HUMIDITY
30 to 90% RH (non-condensing)
WARM UP TIME
>10 Minute
EFFECT OF AMBIENT
TEMPERATURE
For Voltage Input: 0.005% of FS/ C or less
For analog output: 0.010% of FS/ C or less
3.10 Alarm Specification
ALARM TYPES
Flow high limit, Flow low limit
BATCHING ALARM
Pre warn and set point
SETTING RANGES FOR
PROCESS VALUE
ALARMS
Flow (PV) Alarms:
Min = Zero of individual I/P type
Max = Span of individual I/P type
3.11 Display Specification
PV DISPLAY
5 digit red 7 segment display for flow rate
INTEGRATED TOTAL
8 digit red 7 segment display for integrated total
PARAMETER DISPLAY
Same 8 digit red 7 segment display integrated total
STATUS DISPLAY
Red LEDs (for alarm & Batch)
3.12 Communication
PROTOCOL
Modbus RTU serial
STANDARD
EIA RS-485
MAX. COMMUNICATION DISTANCE
1200 mtrs. (For 9600 bps RS 485)
COMMUNICATION METHOD
2 wire half duplex (RS 485)
DATA FRAME
N, 8, 1
COMMUNICATION RATE
9600, 19200 bps
MAX. CONNECTABLE
CONTROLLERS/ INDICATOR
32
ADDRESS RANGE
1 to 99
3.13 Other Specification
SQUARE ROOT EXTRACTION
Applicable
DIGITAL FILTER
Applicable
TIME BASE UNIT
Second, minute, hour, day
CONVERSION FACTOR
0.00 to 99.99
FIVE POINT LINEARIZATION
Applicable
PULSE OUT PUT
Maximum pulse: 20 pulses/Sec.
Excitation Voltage: <24Vdc with maximum 10
mAdc
LOW FLOW CUT OFF
Applicable

User Manual 10
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
4. FRONT AND REAR PANEL DESCRIPTION
4.1 Front Panel Description
4.2 Rear Panel Diagram
4.2.1 Rear Panel Diagram Of 1008S Standard

User Manual 11
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
4.2.2 Rear Panel Diagram Of 1008S With Mass Flow

User Manual 12
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
5. MECHANICAL GUIDELINES
5.1 Mounting Details
Structure: Front fascia IP54 complied(not certified), Enclosure GP (IP20)
Body construction: Polycarbonate plastic.
Case color: Dark grey
Weight: 0.45Kg
Instrument Dimension: 96 W* 96H*125D max behind panel with terminal (all in mm)
Mounting Method: Panel mounting
Panel cut-out: 92W* 92H (all in mm)
Wiring: 2.5sq.mm
Standard Accessories: 2 mounting clamp
5.2 Mounting Steps
Following steps should be followed for proper installation of the instrument.
Mount the instrument in the panel cutout of 92mm x 92mm.
Fix the instrument with the panel using two side brackets.
All the electrical connections to be done at back panel on screw type terminals
Make sure that no wire is connected loosely to avoid generation of spark and RFI. Before
connecting the mains, check the mains configuration on the back panel.
Ensure that the instrument is properly earthed.
Check voltage between earth and neutral terminal. It should be less than 2 volts AC. If
this voltage is greater then it results in unstable reading. In such a case use ISOLATION
TRANSFORMER to provide mains to the instrument.

User Manual 13
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
6. TERMINAL CONNECTION DETAILS
6.1 Terminal Connection Details Of 1008S Standard
1
Line
MAINS
85-265
VAC
11
COM 1
Low
Alarm
Relay
23
RxTx+
RS 485 Serial
2
Neutral
12
NO 1
24
RxTx-
3
Earth
13
NC 1
25
OUT+
CURRENT
O/P : 4-20 mA
4
DIN1 +Ve
Digital
Inputs
14
COM 2
High
Alarm
Relay
26
OUT-
5
DIN2 +Ve
15
NO 2
27
I/P -Ve
I/P 4-20 mA
6
DIN3 +Ve
16
NC 2
28
I/P +Ve
7
DIN4 +Ve
17
COM 3
WP
29
Pulse
I/P-
I/P PULSE
8
DIN -Ve
18
NO 3
30
Pulse
I/P+
9
POUT +Ve
Pulse o/p
19
NC 3
31
+24V DC (50mA)
10
POUT -Ve
20
COM 4
EP
21
NO 4
Relay
22
NC 4
6.2 Terminal Connection Detail Of 1008S With Mass Flow
1
Line
MAINS
85-265
VAC
11
COM 1
Low
Alarm
Relay
23
RxTx+
RS 485
Serial
2
Neutral
12
NO 1
24
RxTx-
3
Earth
13
NC 1
25
OUT+
CURRENT
O/P : 4-20
mA
4
DIN1 +Ve
Digital
Inputs
14
COM 2
High
Alarm
Relay
26
OUT-
5
DIN2 +Ve
15
NO 2
27
I/P3 +Ve
ANALOG I/P
Ma/V
6
DIN3 +Ve
16
NC 2
28
-Ve
7
DIN4 +Ve
17
COM 3
WP
29
I/P2 +Ve
8
DIN -Ve
18
NO 3
30
-Ve
9
POUT +Ve
Pulse o/p
19
NC 3
31
I/P1 +Ve
10
POUT -Ve
20
COM 4
EP
32
PIN –Ve
Pulse i/p
21
NO 4
Relay
33
PIN +Ve
22
NC 4
34
+24V DC (50mA)

User Manual 14
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
7. WIRING DIAGRAM
7.1 Wiring Diagram Of 1008S Standard

User Manual 15
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
7.2 Wiring Diagram Of 1008S With Mass Flow

User Manual 16
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
8. OPERATING DETAILS
The following paragraphs give detailed description of how to operate the unit.
Before using the instrument, make sure to study and understand this section.
8.1 Display Section:
The unit has two windows/groups of display:
Upper:
Five digits 7-segment, 0.56” Red LED display:
It displays Flow rate/Process variable.
Lower:
Eight digits 7-segment 0.40” Red LED display:
In normal mode of operation, Batch total/Integration Total is displayed. While in EDIT
mode, parameters are displayed in this window.
8.2 Keyboard Section
Unit has 4 key membrane keypad organized as 4 x 1 matrix.
Following Table explain the Operation of the Keys used for configuration.
SET OR INDEX
1.It will allow user to enter in EDIT mode, when instrument is in
RUN mode.
2. It will scroll menu and submenu when it is enabled
3. It will save edited data.
START OR
SHIFT
1. It will enter into the submenu, when main menu is enabled
and shows submenu‟s value.
2. It will select the digit to modify, when value is edited.
3. It will start batch, if pressed, when IT & BT are being
displayed
STOP OR
INCREMENT
1. It will increment value of digit selected or constant selected.
2. It will stop batch, if pressed, when BT/IT are being displayed.
3. For Pause batch press stop key for 1 second.
4. If we press stop key for 3 second then batch becomes zero.
ESCAPE
1.It will escape to previous status, with reference to its current
status.
Sequence of status:
IT MENU SUB-MENU
Parameter‟s Value
Escape sequence
When Esc key is pressed in Menu, the instrument will come in
RUN Mode. If user wants to go in EDIT mode, he will have to
enter the correct password again.
2. When Esc key is pressed in RUN Mode, it will directly enter
in to the set point menu. This function is only applicable when
type of instrument is totaliser.
8.3 Run Mode
Whenever mains is switched on to the unit,
Engineering value proportional to the input signal will be displayed as Process variable.
Decimal point is displayed at selected position.
Last saved batch total/integration total will be displayed on the lower window.

User Manual 17
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
8.3.1 Run Mode Parameters Details
No.
Name
Description
Max digits
Limits
1
Batch
Total
This parameter displays
the Total flow since batch
is started („BT‟)
Max. 8
0 - 99999999
For
Standard
Model
2
Integrated
Total
This parameter displays
the Total flow since Last
Reset. („IT‟)
Max. 8
0 - 99999999
3
Roll
Count
This parameter displays
the roll over count of the
Integrated Total from
„99999999‟ to „0‟ („Rc‟)
Max. 4
0 - 9999
4
P1*
Show first ch. flow
Max. 4
0 - 9999
*For Mass
Flow
Model
5
P2*
Show second ch. flow
Max. 4
00.00-99.99
6
P3*
Show third ch. flow
Max. 4
0.000-9.999
Batch total:
This is an eight digit totalized value, displayed as Batch total. As per the selected time
base, Zero and Full-scale settings, this total is updated continuously, proportional to
input. When New Batch Starts or Integration total is reset this value also gets
initialized to 0.
Integration total:
This is an eight digit totalized value, displayed as integrated total. As per the selected
time base, Zero and Full-scale settings, this total is updated continuously,
proportional to input.
Rollover Count (RC):
This is a two-digit value, displayed as the rollover that takes place when integrated
total gets higher than higher limit. When the integrated total crosses high limit, this
count is incremented by one.
So the total integration will be equal to
(Rollover Count) x (hi limit + 1) + Integrated Total (It)
Integrated total, batch total and roll count are cleared by special password.
On power fail detection, current value of Batch total, integrated total and rollover
count are stored in NVRAM.
Mass Flow Parameter Description(Optional)
P1: This is a 4-digit value of flow rate value. It is proportional to flow input. (1st
channel)
P2: This is a 4-digit value of Pressure. It is proportional to pressure input .(2nd
channel)
P3: This is a 4-digit value of Temperature. It is proportional to temperature input .(3rd
channel)
Next section will describe the different Item of individual submenu.

User Manual 18
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
Start & Stop function:(In Run Mode)
START key:
If this key pressed batching relays (WP/EP) gets ON & BATCH TOTAL = 0.It
means a new batch is started. If START key is pressed again and again, it
will not start the batch until WP/EP relays gets OFF.
Relays get OFF by two ways:
1. STOP key
2. BATCH TOTAL crosses the value of SETPOINT.
STOP key:
If user presses STOP key in running batch, batching relays (WP/EP) gets off.
If again STOP key is pressed again and again only batching relays gets
ON/OFF (only if BATCH TOTAL < (WP/EP) values. No new batch will be
started by STOP key.
When batch total value crosses the WP/EP value, relays gets OFF and batch
is over.
Again if START key is pressed then a new batch will start making BATCH
TOTAL = 0. Batching relays gets ON.
8.4 Edit Mode
In this mode user can verify or modify, various parameters.
To enter the EDIT mode, correct password is to be entered.
Password Protection
When INDEX key is pressed, following prompt will be displayed at lower panel 7-segment
display.
“bAt tot”, then
“Int tot” , then
“roL Cnt “ , then
“PASSUord” .
User Can select the Parameter –any of the above prompt to display corresponding value
by pressing INDEX key and then pressing “START KEY”(It is digit select key for editing
the parameters),
At the selection of password, value “0000” is displayed.
Enter the correct password value with the help of START (digit select key) and STOP key
(Incr key) and press INDEX KEY (INDEX key is used as ENTER key)
If correct password is entered & INDEX key is pressed, it will show the first mode PROG
MOD. If wrong password is entered, then “0000” MSG will be displayed again at lower
display window.
Parameter Description
There are total three Menu Items:
Three parameters are displayed after entering correct password.
These parameters related with totaliser are mentioned in the following table.
1.
Program Mode
2.
Configuration Mode
3.
Calibration Mode

User Manual 19
Flow Indicator Totaliser 1008S
REF NO: m18A/om/101
Issue No: 17
8.4.1 Program mode
Programming menu provides facility to configure the relay for different function.
8.4.1.1 Program Mode parameters Details
Low alarm and high alarm:
Value of Low alarm should be lower than that of high alarm. If user tries to set value
of Low alarm greater than high alarm Value, error message will be displayed.
Similarly, if user set value of High alarm lower than low alarm Value, error message
will be displayed. Alarms value cannot be set greater than Full-scale Value (FS).
Comparison with Zero and full-scale:
Low Alarm value should be greater then Zero value. If user tries to set value of Low
alarm less than Zero Value, error message will be displayed.
If (Low Alarm< Zero value), “error” message appears.
High-Alarm value should be greater than Full-scale value. . If user tries to set value of
High-alarm greater than Full-scale value, error message will be displayed.
If (High Alarm > full-scale value), “error” message appears.
Set point and pre-warn:
Error message will be displayed if, set point value is lower than pre-warn and vice
versa.
When we press key in RUN Mode we can directly enter in to Set point
and pre-warn menu. This function is only applicable when type of instrument is
totaliser.
Alarm ON-OFF :(submenu no 5 to 8):
Using these settings, user can set alarm/relay availability. If particular relay is set as
„yes‟, that particular alarm indication will be present over the display card and relay
action will come into effect.
N
o.
Name
Description
No of
digit
Lo
limit
Hi limit
1
High Alarm
Alarm
conditions for
flow rate.
5
0
30000
2
Low Alarm
5
0
30000
3
Pre warn
Alarm
Batch control
values.
6
0
999999
4
Set Point
Alarm
6
0
999999
5
Lo Alarm
Relay
Low alarm
relay
-
Yes/No
6
Hi Alarm
Relay
High alarm
Relay
-
Yes/No
7
Pre-warn
Relay
Pre-warn
Relay
-
Yes/No
8
Set Point
Relay
Set Point
Relay
-
Yes/No
9
Filter
number
2
1
25
Table of contents