
1
acutherm.com | THERMA-FUSER - Manual
THERMA-FUSER
INSTALLATION INSTRUCTIONS
Damaged Freight Claim Procedure
When the diffusers are received, inspect for damage which
may have occured during shipment. If damage is evident, it
should be noted on the carrier's freight bill. A written request
for inspection by the carrier's agent should be made at once.
Storage
Cartons should always be stacked on end with the arrows
on the cartons pointing up. Do not stack cartons flat on the
sides. Excessive weight may cause damage to the diffusers.
Do not store for prolonged times at temperatures exceeding
130°F/56°C.
Identification
Diffusers are factory shipped one per carton. The model
designation is on the diffuser and on the carton.
FIG. 1 DIMENSIONS TF-C, TF-CW, TF-HC, TF-D AND TF-RA
Installation Precautions
When installing diffusers, make sure construction debris does not enter the diffuser or duct system.
Because the models TF-C, TF-CW and TF-HC control room temperature by sensing the room air induced up the center of the
room, care should be taken not to disturb room air induction and entrainment. For example, location next to walls or dropped
lights results in the reflection of primary air back at the Therma- Fuser diffuser and should be avoided. A three-way blow Therma-
Fuser diffuser should be used in this instance if either the light or the Therma-Fuser diffuser cannot be relocated.
Installation Instructions
1. Inspect the carton for damage before opening. Notify carrier if external damage exists. Submit all claims for shipping damage
to the carrier.
2. Move diffusers (in cartons) to installation area. Note unit identification.
3. Remove cardboard box and cardboard insert. Discard packing material.
4. If other than 4 way blow pattern is factory installed, note the "AIRFLOW" markings on the top of the diffuser and locate those
sides in the proper direction.
5. Install in ceiling grid. Install T-bar support wire close to each corner of diffuser. Make sure that only wire suspended T-bars are
used to support diffuser weight. (Adaptor frames are available for other than lay in ceilings.)
6. Connect and secure the supply duct to the collar. Flexible duct should NOT be formed in a centerline radius of less than 1½
times the duct diameter. Improper installation may result in different performance from published ratings.
7. Do NOT reset the temperature set point on the TF-C, TF-CW and TF-HC models until the space is occupied. It is factory
preset for average conditions (74°F/23°C).
8. Balance the system. See Balancing.
9. After the air conditioning system is started and after the space is occupied, where necessary adjust the temperature set
point on TF-C, TF-CW and TF-HC models to suit the occupant. See Adjusting Temperature.
Operating Instructions
Operating instructions for models TF-C, TF-CW and TF-HC are located on the back of the appearance panel.
Inlet
Designation
OD
Inches
±1/16
mm
±3
6 515/16 150
8 715/16 200
10 915/16 250
12 1115/16 300
THERMA-FUSER
™
THERMALLY POWERED VAV DIFFUSER
IINNSSTTAALLLLAATTIIOONN,,BBAALLAANNCCIINNGG&&MMAAIINNTTEENNAANNCCEE
FORM 12.2 REV 1704
MODULAR VAV SYSTEMS
Models: TF-C VAV cooling only.
TF-CW VAV cooling and warm up heating.
TF-HC VAV cooling and VAV heating.
TF-D Manually adjustable blades.
TF-RA Return air.
(See Fig. 1 for dimensions.)
DAMAGED FREIGHT CLAIM PROCEDURE
When the diffusers are received, inspect for damage which may
have occured during shipment. If damage is evident, it should be
noted on the carrier's freight bill. A written request for inspection
by the carrier's agent should be made at once.
STORAGE
Cartons should always be stacked on end with the arrows on the
cartons pointing up. Do not stack cartons flat on the sides.
Excessive weight may cause damage to the diffusers.
Do not store for prolonged times at temperatures exceeding
130°F/56°C.
IDENTIFICATION
Diffusers are factory shipped one per carton. The model designa-
tion is on the diffuser and on the carton.
INSTALLATION PRECAUTIONS
When installing diffusers, make sure construction debris does not
enter the diffuser or duct system.
Because the models TF-C, TF-CW and TF-HC control room tem-
perature by sensing the room air induced up the center of the
room, care should be taken not to disturb room air induction and
entrainment. For example, location next to walls or dropped
lights results in the reflection of primary air back at the Therma-
Fuser diffuser and should be avoided. A three-way blow Therma-
Fuser diffuser should be used in this instance if either the light or
the Therma-Fuser diffuser cannot be relocated.
INSTALLATION INSTRUCTIONS
1. Inspect the carton for damage before opening. Notify carrier if
external damage exists. Submit all claims for shipping damage
to the carrier.
2. Move diffusers (in cartons) to installation area. Note unit iden-
tification.
3. Remove cardboard box and cardboard insert. Discard packing
material.
4. If other than 4 way blow pattern is factory installed, note the
"AIRFLOW" markings on the top of the diffuser and locate
those sides in the proper direction.
5. Install in ceiling grid. Install T-bar support wire close to each
corner of diffuser. Make sure that only wire suspended T-bars
are used to support diffuser weight. (Adaptor frames are avail-
able for other than lay in ceilings.)
6. Connect and secure the supply duct to the collar. Flexible duct
should NOT be formed in a centerline radius of less than 1½
times the duct diameter. Improper installation may result in
different performance from published ratings.
7. Do NOT reset the temperature set point on the TF-C, TF-CW
and TF-HC models until the space is occupied. It is factory
preset for average conditions (74°F/23°C).
8. Balance the system. See Balancing.
9. After the air conditioning system is started and after the space
is occupied, where necessary adjust the temperature set point
on TF-C, TF-CW and TF-HC models to suit the occupant. See
Adjusting Temperature.
OPERATING INSTRUCTIONS
Operating instructions for models TF-C, TF-CW and TF-HC are
located on the back of the appearance panel.
OPENING THE APPEARANCE PANEL
(TF-C, TF-CW, TF-HC, TF-D)
The appearance panel is attached with a latch clip on one side
and hinges on the opposite side.
To open the appearance panel (on a Therma-Fuser diffuser
installed in the ceiling):
1. Locate the side of the Therma-Fuser diffuser with the thermo-
stat(s). Using two hands, one on each side of the latch clip
bracket, place your fingers above the appearance panel and
firmly pull down to disengage the clip. The appearance panel
will rotate and hang down vertically on the hinges.
To close the appearance panel:
1. Rotate the panel upward.
2. Latch the panel by pushing the clip into the small square hole
in the bracket.
NECK SECTION
*595±2mm Square with 16±2mm lip available—specify 595mm square.
Fig 1. Dimensions TF-C, TF-CW, TF-HC, TF-D and TF-RA
Inlet
Desig-
nation
6
8
10
12
OD
Inches
±
1
/
16
5
15
/
16
7
15
/
16
9
15
/
16
11
15
/
16
mm
±3
150
200
250
300
TABLE OF CONTENTS
Installation Instructions . . . . . . . . . . . . . . . . . . 1
Balancing (TF-C, TF-CW and TF-HC) . . . . . . . 2
Balancing (TF-D). . . . . . . . . . . . . . . . . . . . . . . . . 2
Adjusting Temperature . . . . . . . . . . . . . . . . . . . 2
Blow Patterns (TF-C, TF-CW, and TF-HC) . . . 3
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Trouble Shooting (TF-C, TF-CW, and TF-HC). 4
Ten Year Warranty. . . . . . . . . . . . . . . . . . . . . . . 4
Continued on next page
*595±2MM SQUARE WITH 16±2MM LIP AVAILABLE—SPECIFY 595MM SQUARE.